| Plan Review Stops For Permit 01071349 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-02 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-03-05 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-02-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-02-01 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-01 00:00:00 | THE STANDBY POWER FOR THE ATRIUM | | | REQUIRED BY SBC 414.7 IS NOT SHOWN. | | | | | | PROVIDE A WRITTEN DESCRIPTION OF HOW | | | THESMOKE CONTROL IN OTHER THAN THE | | | ATRIUM | | | AREA WILL BE ACCOMPLISHED SEE SBC 414.8 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-11 |
Time |
13:54 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2001-12-11 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2001-12-11 00:00:00 | BUILDING PLAN EVIEW | | | PERMIT # 01071349 | | | 621 CLEARWATER PARK RD | | | CONT: LCI CONSTRUCTION | | | ARCH: BEHAR, FONT & PARTNERS | | | TEL: (305) 740-5442 | | | | | | SBC= STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- COMMENT IS NOT FROM PREVIOUS REVIEW: | | | THE OPEN STAIRWELL IN THE CENTER OF THE | | | BUILDING IS BEING CONSIDERED AS A ATRIUM | | | RATHER THAN A OPEN STAIRWAY. A OPEN | | | STAIRWAY CAN ONLY COMMUNICATE BETWEEN | | | 2 FLOORS. | | | SECTION 414.2 WILL REQUIRE A SMOKE | | | EXHAUST SYSTEM. SUCH SYSTEMS SHALL | | | EXHAUST 40,000 CFM. | | | | | | PLANS NEED TO BE ASSESSED BY PALM BEACH | | | COUNTY BUILDING DEPART FOR COUNTY IMPACT | | | FEES. | | | | | | RADON FEES TO BE PAID TO CITY,$212.37. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-21 |
Time |
13:20 |
Rev Time |
10.00 |
| Received By |
jwitmer |
Date |
2001-08-21 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01071349 | | | 621 CLEARWATER PARK RD | | | CONT: LCI CONSTRUCTION | | | TEL:659-5111 | | | ARCH: BEHAR, FONT & PARTNERS | | | TEL: (305) 740-5442 | | | | | | SBC= STANDARD BUILDING CODE | | | SBC*=STANDARD BUILDING CODE AMENDMENTS | | | | | | 1)-SBC* 1804.2.7.2 SOILS REPORT GIVING | | | THE MINIMUM BEARING VALUE. | | | | | | 2)- SHEET S-10 FOUNDATION NOTES #3 PILE | | | CAPACITY,16" PILE DIA. VS. 45' PILE | | | LENGTH. SEE SBC 1809.2.2. DIMINSIONS | | | AS TO SUPERVISION THAT WILL BE REQUIRED. | | | | | | 3)- SBC 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED, 1809.2.3. SHOW COMPLIANCE | | | THROUGH METHOD IN (1809.2.3.1 OR | | | 1809.2.3.2.) | | | | | | 4)- SHOW COMPLIANCE WITH SBC 1809.2.4 | | | CONCRETE PILE W/ REINFORCING, 4#7'S | | | VERTICALLY FULL LENGTH& #3 TIES @ 12"OC | | | | | | 5)- SHEET S-10 PILE CAP IMBEDMENT SEE | | | SBC 1805.10.1 | | | | | | 6)- SBC T 600 TYPE OF BUILDING? | | | | | | 7)- SBC TABLE 600 EXTERIOR WALLS NORTH | | | SOUTH WALLS, OVER ALLOWABLE OPENING | | | SIZES OVER 10' TO 20', 20% ALLOWABLE | | | OPENINGS, OPENINGS ARE LIMITED TO A | | | PERCENTAGE OF THE WALL AREA. THE WALL | | | AREA IS CONSIDERED TO INCLUDE THE AREA | | | FROM FLOOR LEVEL TO THE CEILING OF EACH | | | STORY. | | | | | | 8)- SBC 104.2.2.PRODUCT APPROVALS ARE RE | | | QUIRED FOR EACH SET OF PLANS. | | | | | | 9)- 1606.2.6.2COMPONENTS & CLADDING SHOW | | | PRODUCT APPROVAL FOR WIND FOR THE ROOF | | | HATCH. | | | | | | 10)- SHEET A-1.4 THE DETAIL FORTHE ROOF | | | OVER THE ELEVATOR SHAFT & OPEN STAIRWELL | | | HAVE A PITCHED ROOF? | | | | | | 11)- A-1.1 STORAGE ROOM #119 DOESN'T | | | MEET THE REQUIREMENTS OF SBC 1027.1.1 | | | FOR SINGLE EXIT STORAGE WHEN THE FOLDING | | | PARTITION FOR THE MEETING ROOM IS IN USE | | | | | | | | | 12)-PLEASE PROVIDE THE PRECASR JOIST LAY | | | OUT AS WELL AS THE STEEL STAIR AND CALCU | | | LATIONS. | | | | | | 13)-SHEET A-8.4 ADD INFORMATION REQUIRED | | | TERRACE DETAIL 7 & 8, MANUFACTURES SPEC- | | | IFICATIONS & TEST REPORRTS INDICATING | | | COMPLIANCE WITH SBC 1503.3.2/1503.4.12. | | | | | | 14)- SHEET A-4.2.1 SEC @ STAIR 1 THE | | | GUARDRAIL IS 42" HIGH, THE HANDRAIL IS | | | ONLY 34" HIGH, SBC 1015.3 OPEN GAURD- | | | RAILS SHALL HAVE INTERMEDIATE RAILS OR | | | ORNAMENTAL PATTERNS SUCH THAT A 4" DIA. | | | SPHERE CAN NOT PASS THROUGH ANY OPENING. | | | | | | 15)- SHEET A-4.12 SBC 1814.2.4WALL FLOOR | | | JOINTS & PENETRATIONS SHALL BE MADE | | | WATERTIGHT USING APPROVED METHODS & MATE | | | RIALS. | | | | | | 16)- SHEET A-8.3 DEPICTS DETAILS 7-9 | | | WALL VENNEERS, AS PER MANUFACTURES SPEC? | | | SBC 1403.2.5 REQUIREMENTS FOR ATTCHMENT. | | | | | | 17)- INTERIOR FINISH SCHEDULE PER SBC | | | TABLE 803.3 FLAME SPREAD/ SMOKE DEVELOP- | | | MENT. | | | PLAN REVIEW | | | JIM WIMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-14 |
Time |
16:23 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-04-14 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2003-03-10 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-14 |
Time |
10:44 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-03-05 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2003-03-10 00:00:00 | UNSAT | | | ~~~~~ | | | FOUNTAIN NEEDS SEPERATE PERMIT PER DVP. | | | | | | WRT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-21 |
Time |
06:47 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-11-21 |
Time |
06:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-12 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-12 |
Time |
18:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-07 |
Time |
06:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-07 |
Time |
06:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-16 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-16 |
Time |
07:47 |
Sent To |
|
|
| Notes |
| 2001-08-16 00:00:00 | ***************** UNSAT ************** | | | | | | 1) NOTE: PLEASE SHOW ALL CONTINUOUS | | | LOADS AT 125% (LIGHTING ETC. PER 230-42 | | | AND 215-3. | | | | | | 2)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | IN OFFICES NEED TO MEET LOCAL CODE | | | 210-50. EACH 12' OF WALL SPACE. PLEASE | | | NOTE THAT SOME OFFICES SEEM TO EXCEED | | | 12' SPACING. | | | | | | 3)NOTE:PLEASE VERIFY FIRE PUMP AND/OR | | | REQUIREMENTS. IF THERE IS GOING TO BE | | | A FIRE PUMP? THEN PLEASE SHOW ON ELECTRI | | | CAL RISER DIAGRAM WITH OCP/DISC/ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-12-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-12-03 |
Time |
11:05 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-12-03 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2001-12-03 00:00:00 | PASSED WITH PROVISOS: | | | 1. A SEPARATE PERMIT APPLICATION AND | | | FEES FOR UNDERGROUND UTILITIES/ SITE | | | WORKS IS REQUIRED PRIOR TO ANY EARTH | | | WORKS. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-08-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-08-03 |
Time |
12:53 |
Rev Time |
5.00 |
| Received By |
mamini |
Date |
2001-08-03 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2001-08-03 00:00:00 | FAILED: | | | 1. ALL DRIVEWAYS ALONG CITY'S R.O.W | | | SHOULD BE CONSTRUCTED PER CITY STANDARD. | | | SEE ATTACHED | | | 2. ALL OFF-STREET PARKING STALLS SHOULD | | | BE PAINTED WITH DOUBLE 4" WIDE PER CITY | | | REQUIREMENT. | | | 3. SHEET A-1.0 (ARCHITECTURAL) SHOWS | | | DUMPSTER 13'-10" BY 13'-10", SHEET A-8.1 | | | (ARCHITECTURAL) SHOWS 13'-4" BY 13'-4", | | | PLEASE VERIFY.NOTE THAT CITY REQUIRES | | | DUMPSTER TO BE 12'-0" DEEP WITH 12'-6" | | | OPENING BETWEENTHE GATE POSTS. | | | THE 2 1/2" CONCRETE FILLED PIPE SHOULD | | | BE LOCATED 18" FROM THE BACK WALL(A 10' | | | PRECAST WHEELSTOP COULD BE USED ALSO). | | | 4. PLEASE VERIFY IF THE 249'-18" R.C.P | | | NEEDS TO BE SHIFTED TO WEST IN ORDER TO | | | PROVIDE ADEQUTE SPACE FOR THE PROPOSED | | | A1-4' M.H NEXT TO EXISTING CATCH BASIN | | | IN CLEARWATER PARK ROAD. | | | 5. A RPZ BACKFLOW PREVENTER WILL NEED TO | | | BE INSTALLED AT THE WATER METER ON | | | PRIVETE PROPERTY. ALL BACKFLOW | | | PREVENTERS SHALL BE COMPLETELY HIDDEN | | | FROM VIEW WITH SHRUB. | | | 6. A SEPARATE IRRIGATION METER IS | | | SUGGESTED.A PROPER BACKFLOW PREVENTER | | | WILL NEED TO BE INSTALLED ON THIS LINE. | | | 7. ANY WORK WITHIN PUBLIC R.O.W WILL | | | REQUIRE A SEPARATE PERMIT FROM CITY | | | ENGINEER'S OFFICE , 659-8040. | | | ANY NEW CONNECTION TO CITY SERVICES WILL | | | REQUIRE A SEPARATE PERMIT FROM PUBLIC | | | UTILITIES ENGINEERING SERVICES | | | DEPARTMENT, 659-8040. | | | 8. PLEASE PROVIDE PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR ENTIRE SITE, | | | IT SHOULD BE SIGNED AND SEALED BY THE | | | DESIGN ENGINEER.THIS DATA WILL BE USED | | | TO CALCULATE THE STORM CHARGES TO THE | | | PROPERTY. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-12-06 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-12-06 |
Time |
15:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-03-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-06 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-06 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-12-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-31 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-31 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2001-12-31 00:00:00 | 1) ATRIUM NOTES SECTION A1.1 INDICATES | | | THAT THE ATRIUM SMOKE EXHAUST WILL | | | BE TESTED BY A THIRD PARTY PRIOR TO | | | ISSUANCE OF FINAL CERTIFICATE. PLEASE | | | BE ADVISED THAT THE ATRIUM SYSTEM WILL | | | BE TESTED WITH CITY OFFICIALS AFTER | | | BEING NOTIFIED BY THE CONTRACTOR. PLEASE | | | PROVIDE TESTING REQUIREMENTS FOR THE | | | ATRIUM SYSTEM ON THE PLANS. | | | 2) ALSO NO DETAILS PROVIDED ON THE | | | LOCATION, TYPE, OR IDENTITY OF THE | | | FIREFIGHTER SMOKE EXHAUST PANEL | | | REQUIRED PER NFPA 101, THE LIFE SAFETY | | | CODE, SECTION 6-2.2.3.5, SECTION (G) | | | 3) THE NOTES REGARDING THE STOVE AND | | | ASSOCIATED EQUIPMENT WILL PROBABLY NOT | | | BE ALLOWED. ALL OF THE REQUIREMENTS OF | | | NFPA 96 MUST BE MET SINCE THE | | | RESIDENTIAL STOVE WILL BE LOCATED IN | | | A COMMERCIAL BUILDING. | | | 4) HOW DOES THE ATRIUM SMOKE EXHAUST | | | WORK SHOULD LOSS OF POWER OCCURS. | | | 5) THE FIRE DEPARTMENT CONNECTION FOR | | | THE SPRINKLER SYSTEM MUST FACE TOWARDS | | | THE FIRE HYDRANT AND NOT AWAY FROM IT. | | | 6) PLEASE INDCIATE NUMBER OF AIR | | | CHANGES FOR ATRIUM SMOKE EXHAUST SYSTEM | | | AND ANY ALL DEVICES THAT WILL ACTIVATE | | | IT. | | | 7) SINCE DOORS OPEN FOR MAKE-UP AIR | | | ARE THERE ANY PROBLEMS WITH SECURITY | | | ASSOCIATED WHEN THESE DOORS OPEN. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-29 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-29 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2001-11-29 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON THE | | | BUILDING NOT THE PLANS. | | | 2) A KNOX-BOX WILL BE REQUIRED FOR | | | FIRE RESCUE ACCESS. | | | 3) ALL OUTSIDE STEPS AND SURFACES ARE | | | TO BE SLIP RESISTANT. | | | 4) A STOVE IS NOTED IN THE PANTRY. | | | PLEASE INDICATE WHAT THE STOVE WILL BE | | | USED FOR. ANY COOKING THAT PRODUCES | | | SMOKE OR GREASE LADEN VAPORS MUST BE | | | PROTECTED BY A HOOD,DUCT, AND | | | EXTINGUISHING SYSTEM. PLEASE EXPLAIN. | | | 5) PLEASE EXPLAIN NOTES ON DOOR NOTES | | | "EXIT DOORS CONNECTED TO SECURITY | | | SYSTEM". | | | 6) STORAGE # 1, 107 IS LOCATED ADJACENT | | | TO AN EXIT. THIS AREA CANNOT INTERFERE | | | WITH ACCESS TO THE EXIT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-06 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-06 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2001-08-06 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER SYSTEM DRAWINGS. | | | 3) THE SIAMESE CONNECTION SHOWN ON | | | THE DRAWINGS IS NOT IN AN ACCEPTABLE | | | LOCATION. THE HOSE WILL KINK AND | | | WILL REDUCE PRESSURE. THIS CONNECTION | | | IS TO BE WITHIN 150 FEET OF A FIRE | | | HYDRANT. | | | 4) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | 5) PLEASE EXPLAIN USE OF OPEN STAIRS | | | AND WHAT FIRE PROTECTION FEATURES ARE | | | PLANNED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-04-14 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-14 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-14 |
Time |
10:44 |
Sent To |
E |
|
| Notes |
| 2003-04-14 00:00:00 | BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-04-02 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-02 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-02 |
Time |
15:19 |
Sent To |
B |
|
| Notes |
| 2003-04-02 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-24 |
Time |
16:13 |
Sent To |
B |
|
| Notes |
| 2003-03-24 00:00:00 | TO HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-13 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-13 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2003-03-13 00:00:00 | COMM BOARD #25 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-27 |
Time |
08:43 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-11-27 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2002-11-27 00:00:00 | MECH REV PERMIT 02101629 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-10-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-25 |
Time |
08:28 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-10-25 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2002-10-25 00:00:00 | MECH REV PERMIT 02101629 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-03-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-11 |
Time |
09:41 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-03-11 |
Time |
09:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-01-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-05 |
Time |
08:43 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-01-05 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2002-01-05 00:00:00 | *******************DENIED*************** | | | | | | CLARIFY SMOKE SYSTEM SEQUENCE OF | | | OPERATION FOR THE ATRIUM.PLAN | | | INDICATES AHU 1, 9 & 15 WILL SHUT DOWN. | | | PLAN SHEET M.01 SHOWS AHU 3 ALSO | | | SUPPLIES AIR AND TRANSFERS AIR TO THE | | | ATRIUM.WHY IS THIS UNIT NOT INCLUDED | | | IN THE SHUTDOWN? | | | | | | INDICATE ON PLAN RATING OF "SHAFT" | | | ENCLOSING DUCTS AND REFRIGERANT LINES. | | | CLARIFY SEPARATION ON THE SOUTH SHAFT, | | | PLAN SHEET M.02 & M.03 DO NOT INDICATE | | | ANY SEPARATION BETWEEN THE REFRIGRANT | | | LINES AND DUCTWORK.AS PER NFPA 90A | | | 3-3.4.3, SHAFTS THAT CONSITITUE AIR | | | DUCTS OR THAT ENCLOSE AIR DUCTS USED | | | FOR THE MOVEMENT OF ENVIRONMENTAL AIR | | | SHALL NOT ENCLOSE:(F) PIPING. | | | | | | INDICATE CALCULATION FOR ATRUIM ON PLAN | | | SHOWING COMPLIANCE WITH 414.4.2. | | | | | | SEE FIRE DEPT COMMENTS ON KITCHEN HOOD. | | | | | | PLEASE PROVIDE TEST CRITERIA FOR SMOKE | | | EVACUATION PRIOR TO FINAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
|
Date |
2001-12-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-08 |
Time |
09:09 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-12-08 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2001-12-08 00:00:00 | | | | PROVISO: | | | | | | AIR BALANCE SCHEDULE DOES NOT INCLUDE | | | CALCULATIONS FOR "EMERGENCY EXHAUST" | | | FOR EXHAUST FAN #12, FOR OPEN STAIRWAY. | | | | | | | | | CONDENSER UNIT RACK SHALL BE A MINIMUM | | | OF 18" BETWEEN THE ROOF SURFACE AND THE | | | BOTTOM OF THE SUPPORT RAIL. (COUNTY | | | WIDE AMENDMENTS 1997 SMC 304.2.5) | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | AND FIRE SUPRESSION, SUBMIT PLANS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-16 |
Time |
14:07 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-08-16 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2001-08-16 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.PLEASE CLARFIY PLAN SHEET NOTES ON | | | THE REFRIGERANT SHAFTS, ARE THEY | | | BOTH VENTED?ON PLAN SHEETS M.02 | | | AND M.03 THE NOTES CHANGE AS DO THE | | | SHAFTS.PLEASE PROVIDE DETAIL OF | | | VENTED SHAFT ENCLOSURES AND ACCESS | | | DOORS PENETRATING FIRE RATED WALLS. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULETO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | | | | NOTE:PLAN SHEET M.06 DETAIL 8, 18" | | | MINIMUM FROM ROOF SURFACE TO THE | | | BOTTOM OF THE SUPPORT RAIL AS | | | PER AMENDED 1997 304.2.5. | | | | | | FAN SHUTDOWN BY DUCT SMOKE | | | DETECTOR WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS (NFPA 90A 4-4.4.3). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-18 |
Time |
08:26 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-03-18 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2002-03-18 00:00:00 | PASSED/PROVISO | | | | | | SERVICE PLATFORM REQUIRED FOR W/HEATER | | | MINIMUM 30"X30". |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-01-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-18 |
Time |
11:44 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2002-01-18 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2002-01-18 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEWS: SHT-5.1 EN- | | | LARGED TOILET PLAN 1ST FLOOR. INSIDE | | | DEPTH OF STALL TO BE 5'9". SHOWN IS 5'9" | | | TO OUTSIDE OF STALL. PLEASE SHOW CORRECT | | | MEASUREMENTS INSIDE STALLS. | | | 2) SHT-5.1 STALL DOORS SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE OF HDCP FIX- | | | TURES. FACBC SEC 4.22.2 | | | 3) FROM PREVIOUS REVIEW, WATER HEATER #2 | | | SHOW COMPLIANCE WITH PERMINATE SHIPS | | | LADDER & WORKING PLATFORM FOR HEATER | | | ABOVE DROP CEILING. | | | 4) SHT P.08 SHOW DETAIL ON HOW AIR | | | CHAMBERS SHALL BE RECHARGEABLE. FROM | | | PREVIOUS REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-12-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-08 |
Time |
10:57 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-12-08 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2001-12-08 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SMC-97 - FACBC-97 | | | | | | 1) SHT A-5.1, ENLARGED TOILET PLAN 1ST | | | FLOOR. INSIDE DEPTH OF STALL TO BE 5'9" | | | BUT IT SHOWS 5'9" TO OUTSIDE OF STALL. | | | 2) WATER HEATER #2. RESPONSE ACKNOWLEDG- | | | ED BUT A PERMINATE SHIPS LADDER IS STILL | | | REQUIRED. ALSO PER SMC-97 SEC 304.4.1, | | | A LEVEL WORKING PLATFORM EXTENDING 30" | | | FROM BASE OF EQUIPMENT AND A 36" HIGH | | | WORKING SPACE IS REQUIRED AT THE CONTROL | | | SIDE OF EQUIPMENT. ACCESS PANEL SHALL | | | COMPLY WITH SMC SEC 304.4.1 | | | 3) WATER HEATER #2. PER MODEL COUNTYWIDE | | | AMENDMENTS TO THE STANDARD MECHANICAL | | | CODE SEC 304.4.2, A DISCONNECT SWITCH, A | | | SERVICE OUTLET CONVIENT TO EQUIPMENT, & | | | A LIGHT LOCATED ON THE SERVICE SIDE OF | | | THE EQUIPMENT WHICH IS CONTROLLED AT THE | | | ACCESS. | | | 4) SHT P.08 NOTE #16 AIR CHAMBERS SHALL | | | COMPLY WITH PDI-WH 201, SEE ATTACHED | | | SHEET FOR APPROVED METHOD OF RECHARGING. | | | EITHER REMOVE ALL AIR CHAMBERS OR COMPLY | | | WITH ACCESS AND RECHARGEABILITY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-08 |
Time |
18:55 |
Rev Time |
3.00 |
| Received By |
jleech |
Date |
2001-08-08 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | DENIED; | | | | | | 1.PAGE C-5 BACKFLOW PREVENTER REQUIRED | | | ON WATER SERVICE TO BUILDING. ALSO IF | | | IRRIGATION SYSTEM IS TO USE CITY WATER | | | PROTECTION IS REQUIRED AND SHALL BE | | | INSTALLED BY THE PLUMBING CONTRACTOR. | | | 2.PAGE A-5.1 (ENLARGED TOILET PLAN 1 FL) | | | HANDICAP STALLS, DOOR CANNOT SWING | | | INTO CLEAR FLOOR SPACE OF THE LAV. | | | FACBC 4.22.2. INSIDE DEPTH SHALL BE | | | 5' 9" FOR THE STALLS SEC.4.17.3. | | | 3.ELEVATION 1 HANDICAP TOILET | | | MESSUREMENTS OFF WALLS IS 18" NOT 19" | | | SEE FIG.30. | | | 4.GENERAL NOTE #1 "ALL WALLS IN REST- | | | ROOMS TO BE DRYWALL AND PAINT". | | | ELEVATIONS SHOW TILE. PLEASE CLARIFY. | | | 5.PAGE A-5.2 ELEVATION 3 SAME AS PLAN | | | REVIEW NOTE #3. | | | 6.HANDICAP URINAL SHALL COMPLY WITH | | | FACBC 4.18.3. NO MEASUREMENT GIVEN | | | FOR URINALS. | | | 7.2ND AND 3RD FLOOR HANDICAP STALLS MEN | | | AND WEMANS INSIDE DIAMENTION SHALL BE | | | 5'-9" SEC.4.17.3. | | | 8.PAGEA-5.2.1 SHOWER SHALL COMPLY WITH | | | SEC.4.21.3 AND FIG. 36. | | | 9.PAGE A-5.4.1 LOUNGE SINK SHALL COMPLY | | | WITH 4.24.2 34" HIGH. | | | 10.SHOW COMPLIANCE WITH 94 SPC TABLE 407 | | | FOR MINIMUM PLUMBING FIXTURES SHOW | | | CALKULATIONS DRINKING FOUNTAIN | | | REQUIRED ON FIRST FLOOR. | | | 11.P-6 CONDENSATE ISOMETRIC DRAINS | | | SHOULD BE VENTED THOUGH THE ROOF. | | | 12.WATER HEATER # 2 SHALL BE READILY | | | ACCESSIBLE. INSTALL ON FINISH FLOOR | | | OR INSTALL A FIXED SHIPS LADDER NEXT | | | TO HEATER. SPC 501.7 AND READILY | | | ACCESSIBLE DEFINITION CHAPTER 2. | | | 13.PAGE P.08 NOTE 16 AIR CHAMBERS SHALL | | | BE APPROVED ENGINEERED WATER HAMMER | | | ARRESTERS AND SHALL COMPLY WITH SEC. | | | 607.8.2 AND 607.8.3 AND INSTALLED PER | | | MANUFACTOR'S RECOMENDATIONS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-08-29 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-29 |
Time |
09:26 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-29 00:00:00 | LANDSCAPE PLAN APPROVED JM LAND/ARCH | | | 8-28-01 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-01 |
Time |
13:39 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|