Plan Review Details - Permit 01071349
Plan Review Stops For Permit 01071349
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-03-05 Cont ID  
Sent By shernand Date 2003-04-02 Time 15:20 Rev Time 0.00
Received By hpiskura Date 2002-03-05 Time 13:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-02-01 Cont ID  
Sent By hpiskura Date 2002-02-01 Time 11:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-02-01 00:00:00THE STANDBY POWER FOR THE ATRIUM
 REQUIRED BY SBC 414.7 IS NOT SHOWN.
  
 PROVIDE A WRITTEN DESCRIPTION OF HOW
 THESMOKE CONTROL IN OTHER THAN THE
 ATRIUM
 AREA WILL BE ACCOMPLISHED SEE SBC 414.8

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-11 Cont ID  
Sent By jwitmer Date 2001-12-11 Time 13:54 Rev Time 4.00
Received By jwitmer Date 2001-12-11 Time 13:54 Sent To  
Notes
2001-12-11 00:00:00BUILDING PLAN EVIEW
 PERMIT # 01071349
 621 CLEARWATER PARK RD
 CONT: LCI CONSTRUCTION
 ARCH: BEHAR, FONT & PARTNERS
 TEL: (305) 740-5442
  
 SBC= STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- COMMENT IS NOT FROM PREVIOUS REVIEW:
 THE OPEN STAIRWELL IN THE CENTER OF THE
 BUILDING IS BEING CONSIDERED AS A ATRIUM
 RATHER THAN A OPEN STAIRWAY. A OPEN
 STAIRWAY CAN ONLY COMMUNICATE BETWEEN
 2 FLOORS.
 SECTION 414.2 WILL REQUIRE A SMOKE
 EXHAUST SYSTEM. SUCH SYSTEMS SHALL
 EXHAUST 40,000 CFM.
  
 PLANS NEED TO BE ASSESSED BY PALM BEACH
 COUNTY BUILDING DEPART FOR COUNTY IMPACT
 FEES.
  
 RADON FEES TO BE PAID TO CITY,$212.37.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By jwitmer Date 2001-08-21 Time 13:20 Rev Time 10.00
Received By jwitmer Date 2001-08-21 Time 13:20 Sent To  
Notes
2001-08-21 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01071349
 621 CLEARWATER PARK RD
 CONT: LCI CONSTRUCTION
 TEL:659-5111
 ARCH: BEHAR, FONT & PARTNERS
 TEL: (305) 740-5442
  
 SBC= STANDARD BUILDING CODE
 SBC*=STANDARD BUILDING CODE AMENDMENTS
  
 1)-SBC* 1804.2.7.2 SOILS REPORT GIVING
 THE MINIMUM BEARING VALUE.
  
 2)- SHEET S-10 FOUNDATION NOTES #3 PILE
 CAPACITY,16" PILE DIA. VS. 45' PILE
 LENGTH. SEE SBC 1809.2.2. DIMINSIONS
 AS TO SUPERVISION THAT WILL BE REQUIRED.
  
 3)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, 1809.2.3. SHOW COMPLIANCE
 THROUGH METHOD IN (1809.2.3.1 OR
 1809.2.3.2.)
  
 4)- SHOW COMPLIANCE WITH SBC 1809.2.4
 CONCRETE PILE W/ REINFORCING, 4#7'S
 VERTICALLY FULL LENGTH& #3 TIES @ 12"OC
  
 5)- SHEET S-10 PILE CAP IMBEDMENT SEE
 SBC 1805.10.1
  
 6)- SBC T 600 TYPE OF BUILDING?
  
 7)- SBC TABLE 600 EXTERIOR WALLS NORTH
 SOUTH WALLS, OVER ALLOWABLE OPENING
 SIZES OVER 10' TO 20', 20% ALLOWABLE
 OPENINGS, OPENINGS ARE LIMITED TO A
 PERCENTAGE OF THE WALL AREA. THE WALL
 AREA IS CONSIDERED TO INCLUDE THE AREA
 FROM FLOOR LEVEL TO THE CEILING OF EACH
 STORY.
  
 8)- SBC 104.2.2.PRODUCT APPROVALS ARE RE
 QUIRED FOR EACH SET OF PLANS.
  
 9)- 1606.2.6.2COMPONENTS & CLADDING SHOW
 PRODUCT APPROVAL FOR WIND FOR THE ROOF
 HATCH.
  
 10)- SHEET A-1.4 THE DETAIL FORTHE ROOF
 OVER THE ELEVATOR SHAFT & OPEN STAIRWELL
 HAVE A PITCHED ROOF?
  
 11)- A-1.1 STORAGE ROOM #119 DOESN'T
 MEET THE REQUIREMENTS OF SBC 1027.1.1
 FOR SINGLE EXIT STORAGE WHEN THE FOLDING
 PARTITION FOR THE MEETING ROOM IS IN USE
  
  
 12)-PLEASE PROVIDE THE PRECASR JOIST LAY
 OUT AS WELL AS THE STEEL STAIR AND CALCU
 LATIONS.
  
 13)-SHEET A-8.4 ADD INFORMATION REQUIRED
 TERRACE DETAIL 7 & 8, MANUFACTURES SPEC-
 IFICATIONS & TEST REPORRTS INDICATING
 COMPLIANCE WITH SBC 1503.3.2/1503.4.12.
  
 14)- SHEET A-4.2.1 SEC @ STAIR 1 THE
 GUARDRAIL IS 42" HIGH, THE HANDRAIL IS
 ONLY 34" HIGH, SBC 1015.3 OPEN GAURD-
 RAILS SHALL HAVE INTERMEDIATE RAILS OR
 ORNAMENTAL PATTERNS SUCH THAT A 4" DIA.
 SPHERE CAN NOT PASS THROUGH ANY OPENING.
  
 15)- SHEET A-4.12 SBC 1814.2.4WALL FLOOR
 JOINTS & PENETRATIONS SHALL BE MADE
 WATERTIGHT USING APPROVED METHODS & MATE
 RIALS.
  
 16)- SHEET A-8.3 DEPICTS DETAILS 7-9
 WALL VENNEERS, AS PER MANUFACTURES SPEC?
 SBC 1403.2.5 REQUIREMENTS FOR ATTCHMENT.
  
 17)- INTERIOR FINISH SCHEDULE PER SBC
 TABLE 803.3 FLAME SPREAD/ SMOKE DEVELOP-
 MENT.
 PLAN REVIEW
 JIM WIMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-04-14 Cont ID  
Sent By btrobaug Date 2003-04-14 Time 16:23 Rev Time 0.50
Received By btrobaug Date 2003-04-14 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-03-10 Cont ID  
Sent By shernand Date 2003-04-14 Time 10:44 Rev Time 0.50
Received By btrobaug Date 2003-03-05 Time 16:50 Sent To  
Notes
2003-03-10 00:00:00UNSAT
 ~~~~~
 FOUNTAIN NEEDS SEPERATE PERMIT PER DVP.
  
 WRT

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-11-21 Time 06:47 Rev Time 0.50
Received By dpalmer Date 2002-11-21 Time 06:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-12 Cont ID  
Sent By dpalmer Date 2002-03-12 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2002-03-12 Time 18:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-07 Cont ID  
Sent By dpalmer Date 2001-12-07 Time 06:16 Rev Time 0.00
Received By dpalmer Date 2001-12-07 Time 06:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-16 Cont ID  
Sent By dpalmer Date 2001-08-16 Time 07:47 Rev Time 0.00
Received By dpalmer Date 2001-08-16 Time 07:47 Sent To  
Notes
2001-08-16 00:00:00***************** UNSAT **************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125% (LIGHTING ETC. PER 230-42
 AND 215-3.
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACING
 IN OFFICES NEED TO MEET LOCAL CODE
 210-50. EACH 12' OF WALL SPACE. PLEASE
 NOTE THAT SOME OFFICES SEEM TO EXCEED
 12' SPACING.
  
 3)NOTE:PLEASE VERIFY FIRE PUMP AND/OR
 REQUIREMENTS. IF THERE IS GOING TO BE
 A FIRE PUMP? THEN PLEASE SHOW ON ELECTRI
 CAL RISER DIAGRAM WITH OCP/DISC/ETC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-12-03 Cont ID  
Sent By mamini Date 2001-12-03 Time 11:05 Rev Time 3.00
Received By mamini Date 2001-12-03 Time 11:04 Sent To  
Notes
2001-12-03 00:00:00PASSED WITH PROVISOS:
 1. A SEPARATE PERMIT APPLICATION AND
 FEES FOR UNDERGROUND UTILITIES/ SITE
 WORKS IS REQUIRED PRIOR TO ANY EARTH
 WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-08-03 Cont ID  
Sent By mamini Date 2001-08-03 Time 12:53 Rev Time 5.00
Received By mamini Date 2001-08-03 Time 12:53 Sent To  
Notes
2001-08-03 00:00:00FAILED:
 1. ALL DRIVEWAYS ALONG CITY'S R.O.W
 SHOULD BE CONSTRUCTED PER CITY STANDARD.
 SEE ATTACHED
 2. ALL OFF-STREET PARKING STALLS SHOULD
 BE PAINTED WITH DOUBLE 4" WIDE PER CITY
 REQUIREMENT.
 3. SHEET A-1.0 (ARCHITECTURAL) SHOWS
 DUMPSTER 13'-10" BY 13'-10", SHEET A-8.1
 (ARCHITECTURAL) SHOWS 13'-4" BY 13'-4",
 PLEASE VERIFY.NOTE THAT CITY REQUIRES
 DUMPSTER TO BE 12'-0" DEEP WITH 12'-6"
 OPENING BETWEENTHE GATE POSTS.
 THE 2 1/2" CONCRETE FILLED PIPE SHOULD
 BE LOCATED 18" FROM THE BACK WALL(A 10'
 PRECAST WHEELSTOP COULD BE USED ALSO).
 4. PLEASE VERIFY IF THE 249'-18" R.C.P
 NEEDS TO BE SHIFTED TO WEST IN ORDER TO
 PROVIDE ADEQUTE SPACE FOR THE PROPOSED
 A1-4' M.H NEXT TO EXISTING CATCH BASIN
 IN CLEARWATER PARK ROAD.
 5. A RPZ BACKFLOW PREVENTER WILL NEED TO
 BE INSTALLED AT THE WATER METER ON
 PRIVETE PROPERTY. ALL BACKFLOW
 PREVENTERS SHALL BE COMPLETELY HIDDEN
 FROM VIEW WITH SHRUB.
 6. A SEPARATE IRRIGATION METER IS
 SUGGESTED.A PROPER BACKFLOW PREVENTER
 WILL NEED TO BE INSTALLED ON THIS LINE.
 7. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM CITY
 ENGINEER'S OFFICE , 659-8040.
 ANY NEW CONNECTION TO CITY SERVICES WILL
 REQUIRE A SEPARATE PERMIT FROM PUBLIC
 UTILITIES ENGINEERING SERVICES
 DEPARTMENT, 659-8040.
 8. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE,
 IT SHOULD BE SIGNED AND SEALED BY THE
 DESIGN ENGINEER.THIS DATA WILL BE USED
 TO CALCULATE THE STORM CHARGES TO THE
 PROPERTY.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-12-06 Cont ID  
Sent By mcarsill Date 2002-12-06 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2002-12-06 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-03-06 Cont ID  
Sent By mcarsill Date 2002-03-06 Time 13:43 Rev Time 0.00
Received By mcarsill Date 2002-03-06 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-12-31 Cont ID  
Sent By mcarsill Date 2001-12-31 Time 10:35 Rev Time 0.00
Received By mcarsill Date 2001-12-31 Time 10:35 Sent To  
Notes
2001-12-31 00:00:001) ATRIUM NOTES SECTION A1.1 INDICATES
 THAT THE ATRIUM SMOKE EXHAUST WILL
 BE TESTED BY A THIRD PARTY PRIOR TO
 ISSUANCE OF FINAL CERTIFICATE. PLEASE
 BE ADVISED THAT THE ATRIUM SYSTEM WILL
 BE TESTED WITH CITY OFFICIALS AFTER
 BEING NOTIFIED BY THE CONTRACTOR. PLEASE
 PROVIDE TESTING REQUIREMENTS FOR THE
 ATRIUM SYSTEM ON THE PLANS.
 2) ALSO NO DETAILS PROVIDED ON THE
 LOCATION, TYPE, OR IDENTITY OF THE
 FIREFIGHTER SMOKE EXHAUST PANEL
 REQUIRED PER NFPA 101, THE LIFE SAFETY
 CODE, SECTION 6-2.2.3.5, SECTION (G)
 3) THE NOTES REGARDING THE STOVE AND
 ASSOCIATED EQUIPMENT WILL PROBABLY NOT
 BE ALLOWED. ALL OF THE REQUIREMENTS OF
 NFPA 96 MUST BE MET SINCE THE
 RESIDENTIAL STOVE WILL BE LOCATED IN
 A COMMERCIAL BUILDING.
 4) HOW DOES THE ATRIUM SMOKE EXHAUST
 WORK SHOULD LOSS OF POWER OCCURS.
 5) THE FIRE DEPARTMENT CONNECTION FOR
 THE SPRINKLER SYSTEM MUST FACE TOWARDS
 THE FIRE HYDRANT AND NOT AWAY FROM IT.
 6) PLEASE INDCIATE NUMBER OF AIR
 CHANGES FOR ATRIUM SMOKE EXHAUST SYSTEM
 AND ANY ALL DEVICES THAT WILL ACTIVATE
 IT.
 7) SINCE DOORS OPEN FOR MAKE-UP AIR
 ARE THERE ANY PROBLEMS WITH SECURITY
 ASSOCIATED WHEN THESE DOORS OPEN.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-11-29 Cont ID  
Sent By mcarsill Date 2001-11-29 Time 15:49 Rev Time 0.00
Received By mcarsill Date 2001-11-29 Time 15:49 Sent To  
Notes
2001-11-29 00:00:001) BUILDING ADDRESS REQUIRED ON THE
 BUILDING NOT THE PLANS.
 2) A KNOX-BOX WILL BE REQUIRED FOR
 FIRE RESCUE ACCESS.
 3) ALL OUTSIDE STEPS AND SURFACES ARE
 TO BE SLIP RESISTANT.
 4) A STOVE IS NOTED IN THE PANTRY.
 PLEASE INDICATE WHAT THE STOVE WILL BE
 USED FOR. ANY COOKING THAT PRODUCES
 SMOKE OR GREASE LADEN VAPORS MUST BE
 PROTECTED BY A HOOD,DUCT, AND
 EXTINGUISHING SYSTEM. PLEASE EXPLAIN.
 5) PLEASE EXPLAIN NOTES ON DOOR NOTES
 "EXIT DOORS CONNECTED TO SECURITY
 SYSTEM".
 6) STORAGE # 1, 107 IS LOCATED ADJACENT
 TO AN EXIT. THIS AREA CANNOT INTERFERE
 WITH ACCESS TO THE EXIT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 08:47 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 08:47 Sent To  
Notes
2001-08-06 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER SYSTEM DRAWINGS.
 3) THE SIAMESE CONNECTION SHOWN ON
 THE DRAWINGS IS NOT IN AN ACCEPTABLE
 LOCATION. THE HOSE WILL KINK AND
 WILL REDUCE PRESSURE. THIS CONNECTION
 IS TO BE WITHIN 150 FEET OF A FIRE
 HYDRANT.
 4) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 5) PLEASE EXPLAIN USE OF OPEN STAIRS
 AND WHAT FIRE PROTECTION FEATURES ARE
 PLANNED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-14 Cont ID  
Sent By shernand Date 2003-04-14 Time 10:44 Rev Time 0.00
Received By shernand Date 2003-04-14 Time 10:44 Sent To E
Notes
2003-04-14 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-02 Time 15:20 Rev Time 0.00
Received By shernand Date 2003-04-02 Time 15:19 Sent To B
Notes
2003-04-02 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 16:13 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 16:13 Sent To B
Notes
2003-03-24 00:00:00TO HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 09:34 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 09:34 Sent To  
Notes
2003-03-13 00:00:00COMM BOARD #25

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-11-27 Cont ID  
Sent By pkrauss Date 2002-11-27 Time 08:43 Rev Time 0.40
Received By pkrauss Date 2002-11-27 Time 08:27 Sent To  
Notes
2002-11-27 00:00:00MECH REV PERMIT 02101629

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-10-25 Cont ID  
Sent By pkrauss Date 2002-10-25 Time 08:28 Rev Time 0.35
Received By pkrauss Date 2002-10-25 Time 08:28 Sent To  
Notes
2002-10-25 00:00:00MECH REV PERMIT 02101629

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-03-11 Cont ID  
Sent By pkrauss Date 2002-03-11 Time 09:41 Rev Time 0.45
Received By pkrauss Date 2002-03-11 Time 09:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 08:43 Rev Time 1.00
Received By pkrauss Date 2002-01-05 Time 08:43 Sent To  
Notes
2002-01-05 00:00:00*******************DENIED***************
  
 CLARIFY SMOKE SYSTEM SEQUENCE OF
 OPERATION FOR THE ATRIUM.PLAN
 INDICATES AHU 1, 9 & 15 WILL SHUT DOWN.
 PLAN SHEET M.01 SHOWS AHU 3 ALSO
 SUPPLIES AIR AND TRANSFERS AIR TO THE
 ATRIUM.WHY IS THIS UNIT NOT INCLUDED
 IN THE SHUTDOWN?
  
 INDICATE ON PLAN RATING OF "SHAFT"
 ENCLOSING DUCTS AND REFRIGERANT LINES.
 CLARIFY SEPARATION ON THE SOUTH SHAFT,
 PLAN SHEET M.02 & M.03 DO NOT INDICATE
 ANY SEPARATION BETWEEN THE REFRIGRANT
 LINES AND DUCTWORK.AS PER NFPA 90A
 3-3.4.3, SHAFTS THAT CONSITITUE AIR
 DUCTS OR THAT ENCLOSE AIR DUCTS USED
 FOR THE MOVEMENT OF ENVIRONMENTAL AIR
 SHALL NOT ENCLOSE:(F) PIPING.
  
 INDICATE CALCULATION FOR ATRUIM ON PLAN
 SHOWING COMPLIANCE WITH 414.4.2.
  
 SEE FIRE DEPT COMMENTS ON KITCHEN HOOD.
  
 PLEASE PROVIDE TEST CRITERIA FOR SMOKE
 EVACUATION PRIOR TO FINAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 09:09 Rev Time 1.30
Received By pkrauss Date 2001-12-08 Time 08:51 Sent To  
Notes
2001-12-08 00:00:00 
 PROVISO:
  
 AIR BALANCE SCHEDULE DOES NOT INCLUDE
 CALCULATIONS FOR "EMERGENCY EXHAUST"
 FOR EXHAUST FAN #12, FOR OPEN STAIRWAY.
  
  
 CONDENSER UNIT RACK SHALL BE A MINIMUM
 OF 18" BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL. (COUNTY
 WIDE AMENDMENTS 1997 SMC 304.2.5)
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 AND FIRE SUPRESSION, SUBMIT PLANS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-16 Cont ID  
Sent By pkrauss Date 2001-08-16 Time 14:07 Rev Time 2.00
Received By pkrauss Date 2001-08-16 Time 12:50 Sent To  
Notes
2001-08-16 00:00:00*******************DENIED***************
  
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.PLEASE CLARFIY PLAN SHEET NOTES ON
 THE REFRIGERANT SHAFTS, ARE THEY
 BOTH VENTED?ON PLAN SHEETS M.02
 AND M.03 THE NOTES CHANGE AS DO THE
 SHAFTS.PLEASE PROVIDE DETAIL OF
 VENTED SHAFT ENCLOSURES AND ACCESS
 DOORS PENETRATING FIRE RATED WALLS.
  
 2.PROVIDE AIR BALANCE SCHEDULETO
 SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
  
 NOTE:PLAN SHEET M.06 DETAIL 8, 18"
 MINIMUM FROM ROOF SURFACE TO THE
 BOTTOM OF THE SUPPORT RAIL AS
 PER AMENDED 1997 304.2.5.
  
 FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS (NFPA 90A 4-4.4.3).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-03-18 Cont ID  
Sent By kstevens Date 2002-03-18 Time 08:26 Rev Time 1.25
Received By kstevens Date 2002-03-18 Time 08:26 Sent To  
Notes
2002-03-18 00:00:00PASSED/PROVISO
  
 SERVICE PLATFORM REQUIRED FOR W/HEATER
 MINIMUM 30"X30".

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-01-18 Cont ID  
Sent By kstevens Date 2002-01-18 Time 11:44 Rev Time 0.75
Received By kstevens Date 2002-01-18 Time 11:43 Sent To  
Notes
2002-01-18 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEWS: SHT-5.1 EN-
 LARGED TOILET PLAN 1ST FLOOR. INSIDE
 DEPTH OF STALL TO BE 5'9". SHOWN IS 5'9"
 TO OUTSIDE OF STALL. PLEASE SHOW CORRECT
 MEASUREMENTS INSIDE STALLS.
 2) SHT-5.1 STALL DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF HDCP FIX-
 TURES. FACBC SEC 4.22.2
 3) FROM PREVIOUS REVIEW, WATER HEATER #2
 SHOW COMPLIANCE WITH PERMINATE SHIPS
 LADDER & WORKING PLATFORM FOR HEATER
 ABOVE DROP CEILING.
 4) SHT P.08 SHOW DETAIL ON HOW AIR
 CHAMBERS SHALL BE RECHARGEABLE. FROM
 PREVIOUS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-08 Cont ID  
Sent By kstevens Date 2001-12-08 Time 10:57 Rev Time 1.25
Received By kstevens Date 2001-12-08 Time 10:57 Sent To  
Notes
2001-12-08 00:00:00DENIED
 REFERENCE: SPC-94 - SMC-97 - FACBC-97
  
 1) SHT A-5.1, ENLARGED TOILET PLAN 1ST
 FLOOR. INSIDE DEPTH OF STALL TO BE 5'9"
 BUT IT SHOWS 5'9" TO OUTSIDE OF STALL.
 2) WATER HEATER #2. RESPONSE ACKNOWLEDG-
 ED BUT A PERMINATE SHIPS LADDER IS STILL
 REQUIRED. ALSO PER SMC-97 SEC 304.4.1,
 A LEVEL WORKING PLATFORM EXTENDING 30"
 FROM BASE OF EQUIPMENT AND A 36" HIGH
 WORKING SPACE IS REQUIRED AT THE CONTROL
 SIDE OF EQUIPMENT. ACCESS PANEL SHALL
 COMPLY WITH SMC SEC 304.4.1
 3) WATER HEATER #2. PER MODEL COUNTYWIDE
 AMENDMENTS TO THE STANDARD MECHANICAL
 CODE SEC 304.4.2, A DISCONNECT SWITCH, A
 SERVICE OUTLET CONVIENT TO EQUIPMENT, &
 A LIGHT LOCATED ON THE SERVICE SIDE OF
 THE EQUIPMENT WHICH IS CONTROLLED AT THE
 ACCESS.
 4) SHT P.08 NOTE #16 AIR CHAMBERS SHALL
 COMPLY WITH PDI-WH 201, SEE ATTACHED
 SHEET FOR APPROVED METHOD OF RECHARGING.
 EITHER REMOVE ALL AIR CHAMBERS OR COMPLY
 WITH ACCESS AND RECHARGEABILITY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By jleech Date 2001-08-08 Time 18:55 Rev Time 3.00
Received By jleech Date 2001-08-08 Time 18:54 Sent To  
Notes
2001-08-08 00:00:00DENIED;
  
 1.PAGE C-5 BACKFLOW PREVENTER REQUIRED
 ON WATER SERVICE TO BUILDING. ALSO IF
 IRRIGATION SYSTEM IS TO USE CITY WATER
 PROTECTION IS REQUIRED AND SHALL BE
 INSTALLED BY THE PLUMBING CONTRACTOR.
 2.PAGE A-5.1 (ENLARGED TOILET PLAN 1 FL)
 HANDICAP STALLS, DOOR CANNOT SWING
 INTO CLEAR FLOOR SPACE OF THE LAV.
 FACBC 4.22.2. INSIDE DEPTH SHALL BE
 5' 9" FOR THE STALLS SEC.4.17.3.
 3.ELEVATION 1 HANDICAP TOILET
 MESSUREMENTS OFF WALLS IS 18" NOT 19"
 SEE FIG.30.
 4.GENERAL NOTE #1 "ALL WALLS IN REST-
 ROOMS TO BE DRYWALL AND PAINT".
 ELEVATIONS SHOW TILE. PLEASE CLARIFY.
 5.PAGE A-5.2 ELEVATION 3 SAME AS PLAN
 REVIEW NOTE #3.
 6.HANDICAP URINAL SHALL COMPLY WITH
 FACBC 4.18.3. NO MEASUREMENT GIVEN
 FOR URINALS.
 7.2ND AND 3RD FLOOR HANDICAP STALLS MEN
 AND WEMANS INSIDE DIAMENTION SHALL BE
 5'-9" SEC.4.17.3.
 8.PAGEA-5.2.1 SHOWER SHALL COMPLY WITH
 SEC.4.21.3 AND FIG. 36.
 9.PAGE A-5.4.1 LOUNGE SINK SHALL COMPLY
 WITH 4.24.2 34" HIGH.
 10.SHOW COMPLIANCE WITH 94 SPC TABLE 407
 FOR MINIMUM PLUMBING FIXTURES SHOW
 CALKULATIONS DRINKING FOUNTAIN
 REQUIRED ON FIRST FLOOR.
 11.P-6 CONDENSATE ISOMETRIC DRAINS
 SHOULD BE VENTED THOUGH THE ROOF.
 12.WATER HEATER # 2 SHALL BE READILY
 ACCESSIBLE. INSTALL ON FINISH FLOOR
 OR INSTALL A FIXED SHIPS LADDER NEXT
 TO HEATER. SPC 501.7 AND READILY
 ACCESSIBLE DEFINITION CHAPTER 2.
 13.PAGE P.08 NOTE 16 AIR CHAMBERS SHALL
 BE APPROVED ENGINEERED WATER HAMMER
 ARRESTERS AND SHALL COMPLY WITH SEC.
 607.8.2 AND 607.8.3 AND INSTALLED PER
 MANUFACTOR'S RECOMENDATIONS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 2 Status P Date 2001-08-29 Cont ID  
Sent By sgraham Date 2001-08-29 Time 09:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-29 00:00:00LANDSCAPE PLAN APPROVED JM LAND/ARCH
 8-28-01

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-01 Cont ID  
Sent By sgraham Date 2001-08-01 Time 13:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***