| Plan Review Stops For Permit 01071304 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-10-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-23 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-26 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | THE PROPERTY SURVEY REQUESTED ON THE | | | FIRST CHECKLIST HAS NOT BEEN PROVIDED, | | | THEREFORE IT MUST BE ASSUMED THAT THIS | | | IS A ZERO LOT LINE BUILDING. CREATING | | | NEW OPENINGS IN THE EAST AND SOUTH | | | WALLS FOR THE TWO DOORS ARE PROHIBITTED | | | BY SBC TABLE600. | | | | | | IN THE ABSENCE OF TEST REPORTS OR NOTICE | | | OF ACCEPTANCE REPORTS FROM METRO DADE, | | | THE WINDOW AND DOOR SYSTEMS WILL HAVE TO | | | BE PERMITTED SEPARATELY AND INFORMATION | | | DEMONSTRATING CODE COMPLIANCE PROVIDED | | | AT THAT TIME.THE REPORTS FOR THE PAIR | | | OF ALUMINUM DOORS COVER ONLY THAT | | | PORTION OF THE WORK AT THIS TIME. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-17 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-17 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY | | | SO THAT COMPLIANCE WITH TABLE 600 MAY BE | | | DETERMINED. | | | | | | THE CHANGE IN USE MAY BE SUBJECT TO | | | IMPACT FEES.CONTACT PALM BEACH COUNTY | | | FOR MORE INFORMATION, 233-5025, AND | | | HAVE THE PERMIT PLANS STAMPED BY THAT | | | OFFICE. | | | | | | THE $175000 DECLARED VALUATION APPEARS | | | TOO LOW FOR THIS SCOPE OF WORK.PLEASE | | | PROVIDE A SIGNED CONTRACT AND A | | | DETAILED TAKEOFF TO JUSTIFY THE VALUE. | | | | | | SHEET A1.2, IT APPEARS THE FRONT DOORS | | | WILL SWING OVER THE PUBLIC SIDEWALK. | | | SEE SBC 3203. | | | | | | PROVIDE THE TEST REPORTS FOR THE DOORS, | | | WINDOWS AND ROOF COVERING THAT | | | DEMONSTRATE THEIR ABILITY TO RESIST THE | | | DESIGN WINDLOADS. | | | | | | IT IS THE BUILDING OFFICIAL'S | | | INTERPRETATION THAT ABOVE GRADE GLAZING | | | BE MISSLE IMPACT RESISTANT AND SHUTTERS | | | ARE NOT AN ACCEPTABLE SUBSTITUTE.SEE | | | SBC 1606.4 AMENDED. | | | | | | THE USE OF A LIFT IN PLACE OF AN | | | ELEVATOR MUST MEET THE CRITERIA OF | | | FACBC 4.1.3, (5). | | | | | | SBC 1006.1.1 REQUIRES EGRESS STAIRS TO | | | BE ENCLOSED IN FIRE RATED CONSTRUCTION. | | | | | | THE STAIRS MUST PROVIDE A PROTECTED | | | EXITTO A PUBLIC PLACE.SEE SBC 1010. | | | | | | GIVEN THE CHANGE OF USE THE STAIRS | | | SHOULD BROUGHT INTO COMPLIANCE WITH SBC | | | 1007.6. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-14 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-14 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2002-03-14 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE PER REVIEW OF PLANS | | | W/ FIELD INSPECTOR, IF OUTSIDE LTS ARE | | | SHOWN ON PLANS, THEN SOME SORT OF OUT- | | | -DOOR FIXTURES MUST BE INSTALLED. | | | | | | 2)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET LOCAL AMENDMENTS 210-50 (UPSTAIRS) | | | | | | 3)NOTE: PLEASE CORRELATE LOADS SHOWN | | | ON PANEL SCHEDULES AND LOADS CARRIED | | | OVER PANEL "A/C". | | | | | | 4)NOTE: PLEASE CLARIFY LOADS SHOWN ON | | | PANEL A/C., SHOWN ABOVE 600A RATING OF | | | EQUIPMENT. | | | | | | 5)NOTE: PLEASE NOTE THAT SOME CIRCUIT | | | #`S ON PLANS DO NOT CORRELATE WITH | | | PANEL SCHEDULES. | | | | | | 6)NOTE:, PLEASE SHOW LOAD CALCUALTIONS, | | | TO INCLUDE WATTS PER SQ FT/RECEPTS | | | 220-3, 220-13 ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-25 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-25 |
Time |
06:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-10 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-10 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-08-10 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE MISSING OUTLETS FOR | | | WINDOWS PER 210-62 | | | | | | 2)NOTE: PLEASE PROVIDE CLARIFICATION | | | FOR WATER HEATER. PLEASE NOTE THAT | | | LOAD SHOWN AT 23.3 KW AND AMPERAGE AT | | | 250AMPS? PLEASE CLARIFY? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-21 |
Time |
13:46 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-08 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-08 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-22 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-22 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-27 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-27 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | IT APPEARS THAT ALL FIRE COMMENTS HAVE | | | BEEN ADDRESSED. PLEASE COMPLY WITH | | | BUILDING PLAN REVIEWER COMMENTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-07 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-07 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | FIRE RESCUE. | | | 2) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 3) ANY CHANGES IN ELEVATION LESS THAN | | | 21 INCHES SHALL BE BY RAMPS. | | | 4) PANIC HARDWARE REQUIRED ON EXIT | | | DOORS. | | | 5) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 6) PLEASE EXPLAIN OPEN STAIRWAY. | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD, DUCT, AND SUPPRESSION | | | SYSTEM. | | | 8) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-03-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-20 |
Time |
09:03 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-03-20 |
Time |
07:43 |
Sent To |
P |
|
| Notes |
| 2002-03-20 00:00:00 | AS-BUILTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-02-25 |
Time |
13:53 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2002-02-25 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2002-02-25 00:00:00 | REVISION FOR RESIZE OF S/A DUCT AND | | | REMOVAL OF DISH HOOD AND RELATED EXFAN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-10-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-18 |
Time |
12:25 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-10-18 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2001-10-18 00:00:00 | PROVISO ON PLAN - MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS FOR THE FLOOR | | | PENETRATION FIRE DAMPERS, SHALL BE WITH | | | THE PLANS AT THE TIME OF INSPECTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-28 |
Time |
12:02 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-09-28 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | | | | PLEASE NOTE THE FIRE DAMPER DETAIL ON | | | PLAN SHEET M-1, THIS DETAIL IS FOR A | | | PENETRATION AT A FIRE RATED WALL NOT A | | | FLOOR/CEILING ASSEMBLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-21 |
Time |
12:56 |
Rev Time |
1.20 |
| Received By |
pkrauss |
Date |
2001-08-21 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | | | | 1.PLAN A-1.3 INDICATES AC CHASE IS | | | NON-RATED AS PER 1997 SMC 610.2 & | | | 610.4, DUCTS EXTENDING THROUGH MORE | | | THAN ONE FLOOR SHALL HAVE A SHAFT | | | ENCLOSURE HAVING A FIRE FATING OF | | | NOT LESS THAN 1 HOUR OR DUCTS | | | PENETRATING ONLY 1 FLOOR MAY BE | | | PROTECTED BY INSTALLING A LISTED | | | FIRE DAMPER. ACCESS DOOR OR OTHER | | | APPROVED MEANS OF ACCESS SHALL BE | | | PROVIDED IN DUCTS TO PERMIT THE | | | PROPER MAINTENANCE AND RESETTING OF | | | EACH FIRE DAMPER.LOCATION AND | | | INSTALLATION DETAILS OF EACH FIRE | | | DOOR, DAMPER, CEILING DAMPER SHALL | | | BE PROPERLY IDENTIFIED ON PLANS. | | | | | | 2.GREASE DUCT SHALL HAVE ADEQUATE | | | CLEARANCE FOR INSPECTION OF WELDS | | | AND FIREWRAP.CLEANOUTS ARE | | | REQUIRED AT EACH CHANGE OF DIRECTION | | | OR ANY PORTION OF DUCT THAT IS NOT | | | ACCESSIBLE FROM THE DUCT INLET OR | | | DISCHARGE. PLEASE SUBMIT PRODUCT | | | APPROVAL FOR THE 3M FIREMASTER DUCT | | | WRAP WITH MECH HOOD PERMIT | | | APPLICATION. | | | | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLER/FREEZER.PLEASE SUBMIT | | | PLANS AND MANUFACTURER SUBMITTAL | | | DATA WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-28 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-28 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2002-03-28 00:00:00 | DENIED | | | REFERENCE: SPC-94-SGC-97- FACBC-97 | | | | | | 1) SHT P-1/P-3 DROP IN ICE BIN AND TWO | | | COMP SINK SHALL BE INDIRECT WASTE TO | | | FLOOR SINK. SEC 804.1 | | | 2) SHT P-4 WATER ISOMETRIC, WATER LINES | | | CHANGED TO 3/4" AT DISHWASHING AREA BUT | | | NOT ON WATER ISO. | | | 3) SHT P-4 WATER ISOMETRIC, WATER HEATER | | | SHOWN CHANGED TO ROOF ON SHT P-2 BUT NOT | | | ON WATER ISO. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-21 |
Time |
14:49 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2001-10-22 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-19 |
Time |
09:27 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-10-19 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2001-10-19 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SHT S-2, A-1.4 SHOW LOCATION OF | | | SCUPPERS AND SIZE WITH CALCULATIONS SPC- | | | 94 SEC 1109. | | | | | | 2) PLEASE CONTACT ROD COMPO (561) 837- | | | 4074 FOR SIZING AND LOCATION APPROVAL | | | OF GREASE INTERCEPTOR. LETTER SHALL BE | | | WITH PLANS FOR PLAN REVIEW. | | | | | | 3) SHT A-1.5 MENS RESTROOM, DOOR CAN NOT | | | OPEN INTO CLEAR FLOOR SPACE OF LAV. | | | | | | 4) SHT P-5, FLOOR DRAIN WITH SAFE WASTE | | | DETAIL NOT APPROVED. PLEASE DELETE, | | | FLOOR SINKS TO BE USED FOR INDIRECT | | | WASTE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-22 |
Time |
17:21 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | PREVIOUS NOTES NOT ADDRESSED, PLUS MORE. | | | (1) SHT S-2,A-1.4 SHOW LOCATION OF ROOF | | | DRAINS,SCUPPERS. SIZE WITH CALCULATIONS | | | SPC-94 SEC 1108,1109. | | | (2) SHT P-1 RM #107 SHOWS,JOSAM 6052OA? | | | SHT A-1 SHOWS BIG DIPPER VAULT? | | | LOCAL ORDINANCE #2938-96 REQUIRES A MIN. | | | 750 GAL GREASE,TANK LOCATED OUTSIDE OF | | | BUILDING, SIZED BY REG SEWER TREATMENT | | | PLANT, CONTACT ROD COMPO 561-837-4074. | | | (3) SHT P-1 RM #107 NO DRAIN & H/C WATER | | | FOR CAN WASH & JANITORS SINK. | | | (4) SHT A 1.5,1ST FLR MEN & WOMEN'S REST | | | RM'S, COMPLY W/FACBC-97,SEC 4.1.6 (1)(B) | | | & 4.1.6.(2) PRIMARY FUNCITION, FOR NEW | | | CONSTRUCTION, H/C ACCESSIBLE. | | | (5) SHT SHT A-1.3 2ND FLR PRIVATE REST | | | RM, TO COMPLY W/FACBC-97 SEC 4.1.3(11) | | | TO BE ADAPTABLE FOR H/C. | | | (6) SHT P-1,P-5,1ST & 2ND FLR (I/D) SAFE | | | WASTE TO F/D OR F/S NOT APPROVED, SPC-94 | | | SEC 802, FLR DRAIN IS FOR SPILLS &MOP | | | AREA, FLR SINKS ARE FOR INDIRECT WASTE. | | | (7) SHT P-3, 3 COMP SINKS, SEC 804.1 | | | FOOD HANDLING, RINSE SINKS TO FLR SINKS | | | (8) SHT P-1,COOLER CONDENSATE TO F/S. | | | (9) SHT P-3,BAR EQUIPMENT DRAINS TO F/S. | | | (10) SHT P-6,NOTE L, F REFERENCE TO AIR | | | CHAMBERS, DELETE ,SEC 607.8.3 TO BE | | | ACCESSIBLE & RECHARGEALE,IMPRACTICAL. | | | (11) SHT P-4 WATER HAMMER ARRESTORS TO | | | BE INSTALLED PER MFG INSTRUCTIONS FOR | | | SIZE AND LOCATION, "NOT IN THE CEILING". | | | (12) SHT P-4,P-6, GAS PERMIT APPLICATION | | | REQUIRMENTS,ADDRESS PREVIOUS COMMENTS. | | | (A) FPU DELIVERS .5# PSI, 12"TO 14" W/C. | | | (B)TOTAL DEVELOPED LGTH IS CLOSER TO 60' | | | (C) MANFACTURE SHEETS FOR ALL EQUIPMENT | | | (D) EMERGENCY HOOD SOV,TO BE LOCATED | | | CLOSE TO THE HOOD, W/MANUAL SOV UP | | | STREAM OF THEEMERGENCY SOV, WITH A | | | UNION DOWN STREAM. | | | (E) TOTAL BTU'S NOT CORRECT,2 APPLIANCES | | | LEFT OUT, "TOT. BTU'S 662K". | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-20 |
Time |
16:47 |
Rev Time |
2.50 |
| Received By |
jleech |
Date |
2001-08-20 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2001-08-20 00:00:00 | DENIED; | | | 1.PLANS TO BE REVIEW AND APPROVED BY THE | | | HOTEL BUSINESS REGULATIONS. | | | 2.GREASE TRAP, SIZE AND LOCATION TO BE | | | APPROVED BY UTILTY DEPARTMENT CONTACT | | | RODNEY COMPO AT 837-4074. | | | 3.FLOOR SINKS ARE REQUIRED FOR ALL | | | INDIRECT WASTES. | | | 4.PAGE P-1 WALKIN COOLER CONDENSATE TO | | | DISCHARGE INTO A FLOOR SINK, NOT SAFE- | | | WASTED. | | | 5.DISHWASHER TO DISCHARGE INTO A FLOOR | | | SINK. FLOOR SINK WILL DISCHARGE TO | | | SANITARY SEWER SYSTEM PER UTILITY | | | ORD. | | | 6.3 COMPARTMENT SINK TO DISCHARGE | | | INDIRECTLY INTO A FLOOR SINK. SPC SEC. | | | 804.1. | | | 7.CAN WASH, JAN. SINK TO DISCHARGE TO | | | GREASY WASTE NOT SANITARY. | | | 8.BAR EQUIPMENT TO DISCHARGE INDIRECTLY | | | INTO FLOOR SINKS. | | | 9.PAGE P-4. TEMPERING VALVE REQUIRED AT | | | AT WATER HEATER TO REDUCE THE TEMP. | | | FROM 140F TO 110F FOR HAND SINKS AND | | | LAVS. | | | 10.WATER HEATER PAN DRAIN SHALL BE 1" | | | PER.507.8.2. | | | 11.MECHANICAL WATER HAMMER ARRESTERS TO | | | BE SIZED BY THE ENGINEER AND INSTALL | | | ED PER MANUFACTORS RECOMMENDATIONS. | | | SEN. 607.8.2 AND 607.8.3. | | | 12.AUTO. SHUTOFF FOR GAS EQUIPMENT | | | SHOULD BE INSTALLED NEXT TO HOOD. | | | BELOW THE CEILING WITH A MANUAL SHUT- | | | OFF VALVE UP STREAM AND A UNION DOWN | | | STREAM. | | | 13.SHOW DIRT LEG. | | | 14.FOLLOW ATTACHED FORM, HIGHLIGHTED | | | ITEMS "GAS PERMIT APPLICATION | | | REQUIREMENTS'. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-10-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-20 |
Time |
09:04 |
Rev Time |
0.24 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-04 00:00:00 | OK'D BY URBAN DESIGN 10-4-01 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-27 |
|
|
Cont ID |
|
| Sent By |
ydavis |
Date |
2001-08-27 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-27 00:00:00 | STOREFRONT GLAZING > 70% SEE JMINICOZZI | | | AT 659-8031 |
|
|