Plan Review Details - Permit 01071304
Plan Review Stops For Permit 01071304
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-10-23 Cont ID  
Sent By hpiskura Date 2001-10-23 Time 08:07 Rev Time 0.00
Received By hpiskura Date   Time   Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-09-26 Cont ID  
Sent By hpiskura Date 2001-09-26 Time 13:32 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-26 00:00:00THE PROPERTY SURVEY REQUESTED ON THE
 FIRST CHECKLIST HAS NOT BEEN PROVIDED,
 THEREFORE IT MUST BE ASSUMED THAT THIS
 IS A ZERO LOT LINE BUILDING. CREATING
 NEW OPENINGS IN THE EAST AND SOUTH
 WALLS FOR THE TWO DOORS ARE PROHIBITTED
 BY SBC TABLE600.
  
 IN THE ABSENCE OF TEST REPORTS OR NOTICE
 OF ACCEPTANCE REPORTS FROM METRO DADE,
 THE WINDOW AND DOOR SYSTEMS WILL HAVE TO
 BE PERMITTED SEPARATELY AND INFORMATION
 DEMONSTRATING CODE COMPLIANCE PROVIDED
 AT THAT TIME.THE REPORTS FOR THE PAIR
 OF ALUMINUM DOORS COVER ONLY THAT
 PORTION OF THE WORK AT THIS TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-17 Cont ID  
Sent By hpiskura Date 2001-08-17 Time 08:34 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-17 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
 SO THAT COMPLIANCE WITH TABLE 600 MAY BE
 DETERMINED.
  
 THE CHANGE IN USE MAY BE SUBJECT TO
 IMPACT FEES.CONTACT PALM BEACH COUNTY
 FOR MORE INFORMATION, 233-5025, AND
 HAVE THE PERMIT PLANS STAMPED BY THAT
 OFFICE.
  
 THE $175000 DECLARED VALUATION APPEARS
 TOO LOW FOR THIS SCOPE OF WORK.PLEASE
 PROVIDE A SIGNED CONTRACT AND A
 DETAILED TAKEOFF TO JUSTIFY THE VALUE.
  
 SHEET A1.2, IT APPEARS THE FRONT DOORS
 WILL SWING OVER THE PUBLIC SIDEWALK.
 SEE SBC 3203.
  
 PROVIDE THE TEST REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING THAT
 DEMONSTRATE THEIR ABILITY TO RESIST THE
 DESIGN WINDLOADS.
  
 IT IS THE BUILDING OFFICIAL'S
 INTERPRETATION THAT ABOVE GRADE GLAZING
 BE MISSLE IMPACT RESISTANT AND SHUTTERS
 ARE NOT AN ACCEPTABLE SUBSTITUTE.SEE
 SBC 1606.4 AMENDED.
  
 THE USE OF A LIFT IN PLACE OF AN
 ELEVATOR MUST MEET THE CRITERIA OF
 FACBC 4.1.3, (5).
  
 SBC 1006.1.1 REQUIRES EGRESS STAIRS TO
 BE ENCLOSED IN FIRE RATED CONSTRUCTION.
  
 THE STAIRS MUST PROVIDE A PROTECTED
 EXITTO A PUBLIC PLACE.SEE SBC 1010.
  
 GIVEN THE CHANGE OF USE THE STAIRS
 SHOULD BROUGHT INTO COMPLIANCE WITH SBC
 1007.6.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-03-14 Cont ID  
Sent By dpalmer Date 2002-03-14 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2002-03-14 Time 16:45 Sent To  
Notes
2002-03-14 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE PER REVIEW OF PLANS
 W/ FIELD INSPECTOR, IF OUTSIDE LTS ARE
 SHOWN ON PLANS, THEN SOME SORT OF OUT-
 -DOOR FIXTURES MUST BE INSTALLED.
  
 2)NOTE: PLEASE NOTE OUTLET SPACING TO
 MEET LOCAL AMENDMENTS 210-50 (UPSTAIRS)
  
 3)NOTE: PLEASE CORRELATE LOADS SHOWN
 ON PANEL SCHEDULES AND LOADS CARRIED
 OVER PANEL "A/C".
  
 4)NOTE: PLEASE CLARIFY LOADS SHOWN ON
 PANEL A/C., SHOWN ABOVE 600A RATING OF
 EQUIPMENT.
  
 5)NOTE: PLEASE NOTE THAT SOME CIRCUIT
 #`S ON PLANS DO NOT CORRELATE WITH
 PANEL SCHEDULES.
  
 6)NOTE:, PLEASE SHOW LOAD CALCUALTIONS,
 TO INCLUDE WATTS PER SQ FT/RECEPTS
 220-3, 220-13 ETC.
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-25 Cont ID  
Sent By dpalmer Date 2001-09-25 Time 06:59 Rev Time 0.00
Received By dpalmer Date 2001-09-25 Time 06:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-10 Cont ID  
Sent By dpalmer Date 2001-08-10 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2001-08-10 Time 08:43 Sent To  
Notes
2001-08-10 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE MISSING OUTLETS FOR
 WINDOWS PER 210-62
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR WATER HEATER. PLEASE NOTE THAT
 LOAD SHOWN AT 23.3 KW AND AMPERAGE AT
 250AMPS? PLEASE CLARIFY?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-21 Cont ID  
Sent By pkrauss Date 2001-08-21 Time 13:46 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-03-08 Cont ID  
Sent By mcarsill Date 2002-03-08 Time 15:42 Rev Time 0.00
Received By mcarsill Date 2002-03-08 Time 15:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-22 Cont ID  
Sent By mcarsill Date 2001-10-22 Time 14:14 Rev Time 0.00
Received By mcarsill Date 2001-10-22 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-27 Cont ID  
Sent By mcarsill Date 2001-09-27 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2001-09-27 Time 15:50 Sent To  
Notes
2001-09-27 00:00:00IT APPEARS THAT ALL FIRE COMMENTS HAVE
 BEEN ADDRESSED. PLEASE COMPLY WITH
 BUILDING PLAN REVIEWER COMMENTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 12:23 Sent To  
Notes
2001-08-07 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 FIRE RESCUE.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS.
 4) PANIC HARDWARE REQUIRED ON EXIT
 DOORS.
 5) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 6) PLEASE EXPLAIN OPEN STAIRWAY.
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD, DUCT, AND SUPPRESSION
 SYSTEM.
 8) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-03-20 Cont ID  
Sent By pkrauss Date 2002-03-20 Time 09:03 Rev Time 0.45
Received By pkrauss Date 2002-03-20 Time 07:43 Sent To P
Notes
2002-03-20 00:00:00AS-BUILTS

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-02-25 Cont ID  
Sent By ndenmark Date 2002-02-25 Time 13:53 Rev Time 0.33
Received By ndenmark Date 2002-02-25 Time 13:53 Sent To  
Notes
2002-02-25 00:00:00REVISION FOR RESIZE OF S/A DUCT AND
 REMOVAL OF DISH HOOD AND RELATED EXFAN

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-10-18 Cont ID  
Sent By pkrauss Date 2001-10-18 Time 12:25 Rev Time 0.40
Received By pkrauss Date 2001-10-18 Time 11:19 Sent To  
Notes
2001-10-18 00:00:00PROVISO ON PLAN - MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR THE FLOOR
 PENETRATION FIRE DAMPERS, SHALL BE WITH
 THE PLANS AT THE TIME OF INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-09-28 Cont ID  
Sent By pkrauss Date 2001-09-28 Time 12:02 Rev Time 0.45
Received By pkrauss Date 2001-09-28 Time 11:43 Sent To  
Notes
2001-09-28 00:00:00 
 PLEASE NOTE THE FIRE DAMPER DETAIL ON
 PLAN SHEET M-1, THIS DETAIL IS FOR A
 PENETRATION AT A FIRE RATED WALL NOT A
 FLOOR/CEILING ASSEMBLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By pkrauss Date 2001-08-21 Time 12:56 Rev Time 1.20
Received By pkrauss Date 2001-08-21 Time 11:35 Sent To  
Notes
2001-08-21 00:00:00********************DENIED**************
  
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.PLAN A-1.3 INDICATES AC CHASE IS
 NON-RATED AS PER 1997 SMC 610.2 &
 610.4, DUCTS EXTENDING THROUGH MORE
 THAN ONE FLOOR SHALL HAVE A SHAFT
 ENCLOSURE HAVING A FIRE FATING OF
 NOT LESS THAN 1 HOUR OR DUCTS
 PENETRATING ONLY 1 FLOOR MAY BE
 PROTECTED BY INSTALLING A LISTED
 FIRE DAMPER. ACCESS DOOR OR OTHER
 APPROVED MEANS OF ACCESS SHALL BE
 PROVIDED IN DUCTS TO PERMIT THE
 PROPER MAINTENANCE AND RESETTING OF
 EACH FIRE DAMPER.LOCATION AND
 INSTALLATION DETAILS OF EACH FIRE
 DOOR, DAMPER, CEILING DAMPER SHALL
 BE PROPERLY IDENTIFIED ON PLANS.
  
 2.GREASE DUCT SHALL HAVE ADEQUATE
 CLEARANCE FOR INSPECTION OF WELDS
 AND FIREWRAP.CLEANOUTS ARE
 REQUIRED AT EACH CHANGE OF DIRECTION
 OR ANY PORTION OF DUCT THAT IS NOT
 ACCESSIBLE FROM THE DUCT INLET OR
 DISCHARGE. PLEASE SUBMIT PRODUCT
 APPROVAL FOR THE 3M FIREMASTER DUCT
 WRAP WITH MECH HOOD PERMIT
 APPLICATION.
  
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER.PLEASE SUBMIT
 PLANS AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-03-28 Cont ID  
Sent By kstevens Date 2002-03-28 Time 11:27 Rev Time 0.00
Received By kstevens Date 2002-03-28 Time 11:26 Sent To  
Notes
2002-03-28 00:00:00DENIED
 REFERENCE: SPC-94-SGC-97- FACBC-97
  
 1) SHT P-1/P-3 DROP IN ICE BIN AND TWO
 COMP SINK SHALL BE INDIRECT WASTE TO
 FLOOR SINK. SEC 804.1
 2) SHT P-4 WATER ISOMETRIC, WATER LINES
 CHANGED TO 3/4" AT DISHWASHING AREA BUT
 NOT ON WATER ISO.
 3) SHT P-4 WATER ISOMETRIC, WATER HEATER
 SHOWN CHANGED TO ROOF ON SHT P-2 BUT NOT
 ON WATER ISO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-10-22 Cont ID  
Sent By pkrauss Date 2002-03-21 Time 14:49 Rev Time 0.25
Received By kstevens Date 2001-10-22 Time 16:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-10-19 Cont ID  
Sent By kstevens Date 2001-10-19 Time 09:27 Rev Time 1.50
Received By kstevens Date 2001-10-19 Time 09:26 Sent To  
Notes
2001-10-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT S-2, A-1.4 SHOW LOCATION OF
 SCUPPERS AND SIZE WITH CALCULATIONS SPC-
 94 SEC 1109.
  
 2) PLEASE CONTACT ROD COMPO (561) 837-
 4074 FOR SIZING AND LOCATION APPROVAL
 OF GREASE INTERCEPTOR. LETTER SHALL BE
 WITH PLANS FOR PLAN REVIEW.
  
 3) SHT A-1.5 MENS RESTROOM, DOOR CAN NOT
 OPEN INTO CLEAR FLOOR SPACE OF LAV.
  
 4) SHT P-5, FLOOR DRAIN WITH SAFE WASTE
 DETAIL NOT APPROVED. PLEASE DELETE,
 FLOOR SINKS TO BE USED FOR INDIRECT
 WASTE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-22 Cont ID  
Sent By pschmitz Date 2001-09-22 Time 17:21 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-22 00:00:00PLUMBING PLAN REVIEW,DENIED
 PREVIOUS NOTES NOT ADDRESSED, PLUS MORE.
 (1) SHT S-2,A-1.4 SHOW LOCATION OF ROOF
 DRAINS,SCUPPERS. SIZE WITH CALCULATIONS
 SPC-94 SEC 1108,1109.
 (2) SHT P-1 RM #107 SHOWS,JOSAM 6052OA?
 SHT A-1 SHOWS BIG DIPPER VAULT?
 LOCAL ORDINANCE #2938-96 REQUIRES A MIN.
 750 GAL GREASE,TANK LOCATED OUTSIDE OF
 BUILDING, SIZED BY REG SEWER TREATMENT
 PLANT, CONTACT ROD COMPO 561-837-4074.
 (3) SHT P-1 RM #107 NO DRAIN & H/C WATER
 FOR CAN WASH & JANITORS SINK.
 (4) SHT A 1.5,1ST FLR MEN & WOMEN'S REST
 RM'S, COMPLY W/FACBC-97,SEC 4.1.6 (1)(B)
 & 4.1.6.(2) PRIMARY FUNCITION, FOR NEW
 CONSTRUCTION, H/C ACCESSIBLE.
 (5) SHT SHT A-1.3 2ND FLR PRIVATE REST
 RM, TO COMPLY W/FACBC-97 SEC 4.1.3(11)
 TO BE ADAPTABLE FOR H/C.
 (6) SHT P-1,P-5,1ST & 2ND FLR (I/D) SAFE
 WASTE TO F/D OR F/S NOT APPROVED, SPC-94
 SEC 802, FLR DRAIN IS FOR SPILLS &MOP
 AREA, FLR SINKS ARE FOR INDIRECT WASTE.
 (7) SHT P-3, 3 COMP SINKS, SEC 804.1
 FOOD HANDLING, RINSE SINKS TO FLR SINKS
 (8) SHT P-1,COOLER CONDENSATE TO F/S.
 (9) SHT P-3,BAR EQUIPMENT DRAINS TO F/S.
 (10) SHT P-6,NOTE L, F REFERENCE TO AIR
 CHAMBERS, DELETE ,SEC 607.8.3 TO BE
 ACCESSIBLE & RECHARGEALE,IMPRACTICAL.
 (11) SHT P-4 WATER HAMMER ARRESTORS TO
 BE INSTALLED PER MFG INSTRUCTIONS FOR
 SIZE AND LOCATION, "NOT IN THE CEILING".
 (12) SHT P-4,P-6, GAS PERMIT APPLICATION
 REQUIRMENTS,ADDRESS PREVIOUS COMMENTS.
 (A) FPU DELIVERS .5# PSI, 12"TO 14" W/C.
 (B)TOTAL DEVELOPED LGTH IS CLOSER TO 60'
 (C) MANFACTURE SHEETS FOR ALL EQUIPMENT
 (D) EMERGENCY HOOD SOV,TO BE LOCATED
 CLOSE TO THE HOOD, W/MANUAL SOV UP
 STREAM OF THEEMERGENCY SOV, WITH A
 UNION DOWN STREAM.
 (E) TOTAL BTU'S NOT CORRECT,2 APPLIANCES
 LEFT OUT, "TOT. BTU'S 662K".
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-20 Cont ID  
Sent By jleech Date 2001-08-20 Time 16:47 Rev Time 2.50
Received By jleech Date 2001-08-20 Time 16:47 Sent To  
Notes
2001-08-20 00:00:00DENIED;
 1.PLANS TO BE REVIEW AND APPROVED BY THE
 HOTEL BUSINESS REGULATIONS.
 2.GREASE TRAP, SIZE AND LOCATION TO BE
 APPROVED BY UTILTY DEPARTMENT CONTACT
 RODNEY COMPO AT 837-4074.
 3.FLOOR SINKS ARE REQUIRED FOR ALL
 INDIRECT WASTES.
 4.PAGE P-1 WALKIN COOLER CONDENSATE TO
 DISCHARGE INTO A FLOOR SINK, NOT SAFE-
 WASTED.
 5.DISHWASHER TO DISCHARGE INTO A FLOOR
 SINK. FLOOR SINK WILL DISCHARGE TO
 SANITARY SEWER SYSTEM PER UTILITY
 ORD.
 6.3 COMPARTMENT SINK TO DISCHARGE
 INDIRECTLY INTO A FLOOR SINK. SPC SEC.
 804.1.
 7.CAN WASH, JAN. SINK TO DISCHARGE TO
 GREASY WASTE NOT SANITARY.
 8.BAR EQUIPMENT TO DISCHARGE INDIRECTLY
 INTO FLOOR SINKS.
 9.PAGE P-4. TEMPERING VALVE REQUIRED AT
 AT WATER HEATER TO REDUCE THE TEMP.
 FROM 140F TO 110F FOR HAND SINKS AND
 LAVS.
 10.WATER HEATER PAN DRAIN SHALL BE 1"
 PER.507.8.2.
 11.MECHANICAL WATER HAMMER ARRESTERS TO
 BE SIZED BY THE ENGINEER AND INSTALL
 ED PER MANUFACTORS RECOMMENDATIONS.
 SEN. 607.8.2 AND 607.8.3.
 12.AUTO. SHUTOFF FOR GAS EQUIPMENT
 SHOULD BE INSTALLED NEXT TO HOOD.
 BELOW THE CEILING WITH A MANUAL SHUT-
 OFF VALVE UP STREAM AND A UNION DOWN
 STREAM.
 13.SHOW DIRT LEG.
 14.FOLLOW ATTACHED FORM, HIGHLIGHTED
 ITEMS "GAS PERMIT APPLICATION
 REQUIREMENTS'.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 2 Status P Date 2001-10-04 Cont ID  
Sent By pkrauss Date 2002-03-20 Time 09:04 Rev Time 0.24
Received By sgraham Date   Time   Sent To  
Notes
2001-10-04 00:00:00OK'D BY URBAN DESIGN 10-4-01

Review Stop Z ZONING
Rev No 1 Status F Date 2001-08-27 Cont ID  
Sent By ydavis Date 2001-08-27 Time 14:43 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2001-08-27 00:00:00STOREFRONT GLAZING > 70% SEE JMINICOZZI
 AT 659-8031