| Plan Review Stops For Permit 01071242 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-01 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-01 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-26 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-26 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2001-07-26 00:00:00 | 1) EXHAUST FAN DOES NOT MEET MINIMUM | | | AIR FLOW REQUIREMENTS. THE MINIMUM AIR | | | FLOW SHALL NOT BE LESS THAN 1500 CFM | | | PER MINUTE. PLEASE SEE NFPA 96, SECTION | | | 5-2.1 | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-25 |
Time |
15:28 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-07-25 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2001-07-26 00:00:00 | ******************PROVISO*************** | | | | | | | | | MINIMUM SLOPE OF 1" PER FOOT TOWARD HOOD | | | OR AN APPROVED TRAP. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
|