| 2001-08-27 00:00:00 | CHECKLIST: |
| | 1-PROPOSED BUILDING DOESN'T COMPLY WITH |
| | TABLE 600 OF SBC 1997. THE 2 BUILDINGS |
| | ARE TOO CLOSE TOGETHER. THEREFORE, THE |
| | PERCENTAGE OF OPENINGS ALLOWED BY |
| | TABLE 600 IS EXCEEDED. |
| | 2-BATHROOM WINDOW DOESN'T PROVIDE THE |
| | MINIMUM REQUIRED VENTILATION BY SEC. |
| | 1203.4.2 SBC 1997. |
| | -INCREASE WINDOW SIZE TO MEET THE MIN. |
| | REQUIREMENTS OR PROVIDE MECHANICAL |
| | VENTILATION. |
| | 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY |
| | 2405.2 SBC 1997. SEE PLANS FOR |
| | COMMENTS. |
| | 4-SPECIFY THE DESIGN PRESSURES |
| | CALCULATED AT ALL EXTERIOR OPENINGS. |
| | SECTION 1606 SBC 1997. |
| | 5-GARAGE SWING DOOR TO HAVE 32" MINIMUM |
| | CLEAR OPENING AS REQUIRED BY TABLE |
| | 1004 SBC 1997. REVISE SIZE AS REQUIRED |
| | 6-PROVIDE ATTIC ACCESS AS REQUIRED BY |
| | SEC 2309.6 SBC 1997. |
| | 7-SPECIFY FASTENING OF ROOF SHEATHING. |
| | SEC. 2306 CITY AMENDMENTS TO SBC 1997. |
| | 8-SPECIFY CONSTRUCTION AT GABLE END. |
| | PROVIDE WALL/SECTION SHOWING RAKE BM |
| | OR KNEE WALL AND COMPLETE FASTENERS. |
| | 9-PROVIDE SOIL TEST REPORT. |
| | 10-PROVIDE PRODUCT APPROVAL FOR: |
| | -SINGLE HUNG WINDOWS (DWGS NOT LEGIBLE) |
| | -OUTSWING DOOR (MISSING SOME DRAWINGS) |
| | 11-STORM SHUTTERS: PROVIDE KEY PLAN AND |
| | COMPLETE INSTALLATION SCHEDULE (SEE |
| | CITY SAMPLE). |