Plan Review Details - Permit 01071207
Plan Review Stops For Permit 01071207
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-16 Cont ID  
Sent By rbrown Date 2002-01-16 Time 18:58 Rev Time 0.00
Received By rbrown Date 2002-01-16 Time 18:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By lmartine Date 2001-10-03 Time 14:09 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-28 Cont ID  
Sent By lmartine Date 2001-08-28 Time 10:40 Rev Time 3.00
Received By lmartine Date   Time   Sent To  
Notes
2001-08-28 00:00:00BUILDING COMMENTS
 -----------------
  
 PROVISO
 -------
  
 PROVIDE SIGNED AND SEALED
 CERTIFICATION FROM A STRUCTURAL
 ENGINEER VERIFING EXISTING ROOF
 STRUCTURE WILL SUPPORT ADDITIONAL LOADS
 IMPOSED BY NEW INSTALLATION.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-01-04 Cont ID  
Sent By dpalmer Date 2002-01-04 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2002-01-04 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 18:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 14:37 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 22:55 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 22:55 Sent To  
Notes
2001-08-07 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT THE NEW SERVICE
 SHOWN IS NOT PERMITTED UNDER 230-2,
  
 2)NOTE: PLEASE NOTE GROUPING OF MAINS
 PER 230-72. PLEASE NOTE THAT A SHUNT
 TRIP AT EXSITING SERVICE LOCATION DOES
 NOT MEET 230-76 AND 230-79 FOR MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
 PER 215-2 AND 230-42.
  
 PLEASE SUBMIT CLARIFICATION ON LOCATION
 OF SERVICES.
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-01-07 Cont ID  
Sent By mcarsill Date 2002-01-07 Time 15:33 Rev Time 0.00
Received By mcarsill Date 2002-01-07 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-30 Cont ID  
Sent By mcarsill Date 2001-10-30 Time 13:45 Rev Time 0.00
Received By mcarsill Date 2001-10-30 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-18 Cont ID  
Sent By mcarsill Date 2001-09-18 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2001-09-18 Time 14:18 Sent To  
Notes
2001-09-18 00:00:001) CONDUITS IN STAIR TOWER BEING SHOWN
 AS BEING BOXED OUT WITH 2 HOUR RATED
 DRY WALL ENCLOSURE. AGAIN, NOTHING IS
 PERMITTED TO BE LOCATED WITHIN THE STAIR
 TOWER EXCEPT FOR FIRE PROTECTION PIPING
 AND ELECTRICAL EQUIPMENT USED FOR
 EMERGENCY LIGHTING. PLEASE REFER TO LIFE
 SAFETY CODE, CHAPTER 5-1.3.2
 2)NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. THE NEXTEL ROOM MUST BE FIRE
 SPRINKLER PROTECTED EVEN WITH THE
 INSTALLATION OF THE FM 200 SYSTEM.
 PLEASE SUBMIT FIRE SPRINKLER DRAWINGS.
  
 MIKE CARSILLO, CAPTAIN
 832-2910 OR 659-8096 EXT. 8497

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By mcarsill Date 2001-08-09 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2001-08-09 Time 16:00 Sent To  
Notes
2001-08-09 00:00:001) THE NEW CONDUIT TO SAME PATH AS
 EXISTING 3" PIPE SHOWN ON E-1 CANNOT
 RUN THRU STAIRTOWER. NOTHING IS
 PERMITTED TO ENTER THE STAIR EXCEPT
 FIRE PROTECTION PIPING AND ELECTRICAL
 EQUIPMENT USED FOR EMERGENCY LIGHTING.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF THE FM 200
 SYSTEM. THE FM 200 SYSTEM CANNOT
 BE USED IN LIEU OF REQUIRED FIRE
 SPRINKLER PROTECTION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-09 Cont ID  
Sent By pkrauss Date 2002-01-09 Time 14:18 Rev Time 0.45
Received By pkrauss Date 2002-01-09 Time 14:18 Sent To  
Notes
2002-01-09 00:00:00MECH PERMIT 01071243
  
 PROVISO:
  
 AS PER 1997 SMC 304.6.3, EVERY APPLIANCE
 ON AN EXTERIOR WALL OF A BUILDING, WHICH
 IS SO DESIGNED THAT THE COMPONENTS ARE
 SERVICABLE ONLY FROM OUTSIDE THE
 BUILDING, SHALL BE ACCESSIBLE.SHOULD
 EQUIPMENT HEIGHT BE GREATER THAN 20'
 ABOVE THE LOW ROOF A PERMENENT MEANS OF
 ACCESS IS REQUIRED.
  
 A MINIMUM OF 30" OF CLEAR SPACE ON THE
 SERVICE SIDE FOR INSPECTION AND
 SERVICING OF CONDENSING UNITS OR
 COMPRESSOR UNITS WITH ENCLOSURES SHALL
 BE ACCESSIBLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-13 Cont ID  
Sent By pkrauss Date 2001-11-13 Time 09:13 Rev Time 0.45
Received By pkrauss Date 2001-11-13 Time 09:13 Sent To  
Notes
2001-11-13 00:00:00******************PROVISO***************
  
  
 MECHANICAL PERMIT 01071243
  
 1.DUCT SMOKE DETECTORS ARE REQUIRED
 IF MORE THAN ONE AIR HANDLING UNIT
 ARE TO BE RUN AT ANY GIVEN TIME.
 (CFM WOULD BE GREATER THAN 2000 CFM)
  
  
 2.DUCT SMOKE DETECTORS SHALL BE TIED
 BUILD BUILDING ALARM SYSTEMS AS PER
 NFPA 90A 4-4.4.2.
  
 NOTE, CONDENSERS MOUNTED ON WALL SHALL
 BE ACCESSIBLE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-21 Cont ID  
Sent By ndenmark Date 2001-08-21 Time 08:54 Rev Time 0.50
Received By ndenmark Date 2001-08-21 Time 08:54 Sent To  
Notes
2001-08-21 00:00:00PROVISO:
 DUCT SMOKE DETECTORS SHALL BE REQUIRED
 IF MORE THAN ONE AIR HANDLING UNIT ARE
 TO RUN AT ANY GIVEN TIME. CFM WOULD BE
 GREATER THAN 2000CFM FOR THE AGGREGATE
 AREA. TIE TO BLDG ALARM.
 SEPARATE PERMIT AND PLANS WILL BE
 REQUIRED FOR THE FM200 SUPPRESSION
 SYSTEM.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-06 Cont ID  
Sent By sjohnson Date 2001-08-06 Time 09:21 Rev Time 0.25
Received By sjohnson Date   Time   Sent To  
Notes
2001-08-06 00:00:00APPROVED PER SHIRLEY GRAHAM