Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-10-18 Cont ID  
Sent By dpalmer Date 2001-10-18 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2001-10-18 Time 15:43 Sent To  
Notes
2001-10-18 00:00:00**************** UNSAT *************
  
 1)NOTE: PLANS STILL NEED TO BE
 SUBMITTEDFOR CHANGE OF USE, TO INCLUDE
 APPLICATION BY A CONTRACTOR SO THAT MAY
 CAN BE
 REVIEW FOR BLDG/PLUMB/HANDICAP CODE
 ISSUES.104.1.1
  
 2)NOTE: AS NOTED ON PREVIOUS REVIEWS
 COUNTY IMPACT FEES WILL NEED TO BE
 ADDRESSED.
  
 3)NOTE: PLEASE NOTE AND GIVE ALL INFOR-
 -MATION FOR FAIR HOUSING ACT REG,
 24 CFR 100.205
  
 4)NOTE: PLEASE NOTE ROOMS BEING ACCESS-
 -IBLE BY OTHER ROOMS AND YET PERMIT IS
 FOR MAKING NEW APTS???????
  
 5)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW ALL BRANCH CIRCUIT #`S ON PLANS
 AND NEED TO CORRELATE WITH SUBMITTED
 PANEL
 SCHEDULES FOR NEW CIRCUITS AND
 SEPARATION BETWEEN UNITS???
  
 6)NOTE: PLEASE NOTE ONE KITCHEN SERVING
 MORETHAN ONE UNIT.????
  
 7)NOTE: MIN OF TWO SMALL APPLIANCE
 CIRCUITS PER 210-52.210-11-C-1
  
 8)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW HOW/WHERE A/C CIRCUITS ARE ???
 UNITS TO BE CALCULATED PER NAME PLATE
 RATINGS.
  
 9) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 10)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 11)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 FOR HOUSE LIGHTING.
  
 12)NOTE: PLEASE NOTE THAT NO GROUNDING
 IS SHOWN FOR ANYTHING. 250
  
 13)NOTE: PLEASE SUBMIT A ONE-LINE
 DIAGRAM SHOWING ALL PANELS/NEW AND OLD
 AND HOW THEY ARE FED? CONDUITS/FEEDERS
 ETC>
  
 14)NOTE: PLEASE NOTE THAT SOME BATHS
 DON'T SHOW ANY GFI OUTLETS. 210-52D
  
 15)NOTE: PLEASE NOTE THAT OCCUPANTS
 ARE REQ`D TO HAVE ACCESS TO PANELS
 FEEDING THEIR UNITS.
  
 16)NOTE:PLEASE NOTE PLANS NEED TO
 CLARIFY WASHING MACHINES AND OR DRYERS
 UNITS? GAS ? ELECTRIC??
  
 17)NOTE: PLEASE NOTE THAT LOAD EXCEEDS
 SERVICE ENTRANCE CONDUCTORS SIZE. PER
 310-16
  
 PERMIT APPLICATION NEEDS TO CLEARLY
 STATE WHAT IS BEING APPIED FOR AND
 OTHER REVIEW WILL NEED TO BE DONE.
 I SUGGEST ANOTHER MEETING BE SCHEDULED
 WITH ALL THAT MAY BE INVOLVED.
  
 PLEASE NOTE THAT THERE ARE PROBABLY
 MORE ELECTRICAL COMMENTS BUT PLANS
 ARE NOT COMPLETE ENOUGH TO MEET NEC
 REQUIREMENTS FOR COMMERCIAL APTS.
  
 PLEASE SUBMIT ALL OF THE ABOVE FOR
 REVIEW AND ADDRESS OTHER ISSUES.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
  
  
 ***** PLEASE NOTE****
 THAT COMPLETE VALUE OF TOTAL SCOPE OF
 WORK NEEDS TO BE SUBMITTED WITH PERMIT
 APPLICATION AND FEES AJUSTED.
 PER 104.7.5
 VALUE ON APPLICATION WAS CHANGED FROM
 ORIG SUBMITTAL AND FEES WERE NOT AJUSTED
 OWES FEES FOR RESUBMITTALS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-08-09 Cont ID  
Sent By dpalmer Date 2001-08-09 Time 12:37 Rev Time 0.00
Received By dpalmer Date 2001-08-09 Time 12:37 Sent To  
Notes
2001-08-09 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT WE NEED A
 COMPLETE PLAN SHOWING ALL UNITS FOR
 ADDING FRIG AND STOVE TOP OUTLET
 LOCATIONS. PLEASE NOTE THAT PLANS WILL
 HAVE TO BE APPROVED BY ZONING FOR USEAGE
 PLEASE ALSO NOTE THAT IMPACT FEES MAY
 BE REQ`D DEPENDING ON ZOING AND CHANGE
 OF USE.
 PLEASE SUBMIT COMPLETE SET OF DRAWINGS
 FOR REVIEW. SHOWING PANEL LOCATIONS FOR
 OCCUPANCY USE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BY ZONING, ELECTRICAL AND BLDG.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-07-24 Cont ID  
Sent By lsmith Date 2001-07-24 Time 15:21 Rev Time 0.50
Received By dpalmer Date   Time   Sent To  
Notes
2001-07-24 00:00:00FAILED: PER PHIL PETTY 7/24/01
  
 1. PROVIDE WIRE SIZE, PANEL SCHEDULE AND
 LOAD CALCULATIONS FOR EACH UNIT.
 2. PROVIDE COPY OF CONTRACT TO VERIFY VA
 LUE OF WORK ( PERMIT FEES ARE PASED ON
 TOTAL LABOR & MATERIALS PER SBC 104.7.5