| 2001-10-18 00:00:00 | **************** UNSAT ************* |
| | |
| | 1)NOTE: PLANS STILL NEED TO BE |
| | SUBMITTEDFOR CHANGE OF USE, TO INCLUDE |
| | APPLICATION BY A CONTRACTOR SO THAT MAY |
| | CAN BE |
| | REVIEW FOR BLDG/PLUMB/HANDICAP CODE |
| | ISSUES.104.1.1 |
| | |
| | 2)NOTE: AS NOTED ON PREVIOUS REVIEWS |
| | COUNTY IMPACT FEES WILL NEED TO BE |
| | ADDRESSED. |
| | |
| | 3)NOTE: PLEASE NOTE AND GIVE ALL INFOR- |
| | -MATION FOR FAIR HOUSING ACT REG, |
| | 24 CFR 100.205 |
| | |
| | 4)NOTE: PLEASE NOTE ROOMS BEING ACCESS- |
| | -IBLE BY OTHER ROOMS AND YET PERMIT IS |
| | FOR MAKING NEW APTS??????? |
| | |
| | 5)NOTE: PLEASE NOTE THAT PLANS NEED TO |
| | SHOW ALL BRANCH CIRCUIT #`S ON PLANS |
| | AND NEED TO CORRELATE WITH SUBMITTED |
| | PANEL |
| | SCHEDULES FOR NEW CIRCUITS AND |
| | SEPARATION BETWEEN UNITS??? |
| | |
| | 6)NOTE: PLEASE NOTE ONE KITCHEN SERVING |
| | MORETHAN ONE UNIT.???? |
| | |
| | 7)NOTE: MIN OF TWO SMALL APPLIANCE |
| | CIRCUITS PER 210-52.210-11-C-1 |
| | |
| | 8)NOTE: PLEASE NOTE THAT PLANS DO NOT |
| | SHOW HOW/WHERE A/C CIRCUITS ARE ??? |
| | UNITS TO BE CALCULATED PER NAME PLATE |
| | RATINGS. |
| | |
| | 9) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S) PER 210-11-C-3. |
| | MUST BE 20A AND #12AWG. |
| | |
| | 10)NOTE:PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 11)NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| | 125%. (LIGHTING ETC) |
| | FOR HOUSE LIGHTING. |
| | |
| | 12)NOTE: PLEASE NOTE THAT NO GROUNDING |
| | IS SHOWN FOR ANYTHING. 250 |
| | |
| | 13)NOTE: PLEASE SUBMIT A ONE-LINE |
| | DIAGRAM SHOWING ALL PANELS/NEW AND OLD |
| | AND HOW THEY ARE FED? CONDUITS/FEEDERS |
| | ETC> |
| | |
| | 14)NOTE: PLEASE NOTE THAT SOME BATHS |
| | DON'T SHOW ANY GFI OUTLETS. 210-52D |
| | |
| | 15)NOTE: PLEASE NOTE THAT OCCUPANTS |
| | ARE REQ`D TO HAVE ACCESS TO PANELS |
| | FEEDING THEIR UNITS. |
| | |
| | 16)NOTE:PLEASE NOTE PLANS NEED TO |
| | CLARIFY WASHING MACHINES AND OR DRYERS |
| | UNITS? GAS ? ELECTRIC?? |
| | |
| | 17)NOTE: PLEASE NOTE THAT LOAD EXCEEDS |
| | SERVICE ENTRANCE CONDUCTORS SIZE. PER |
| | 310-16 |
| | |
| | PERMIT APPLICATION NEEDS TO CLEARLY |
| | STATE WHAT IS BEING APPIED FOR AND |
| | OTHER REVIEW WILL NEED TO BE DONE. |
| | I SUGGEST ANOTHER MEETING BE SCHEDULED |
| | WITH ALL THAT MAY BE INVOLVED. |
| | |
| | PLEASE NOTE THAT THERE ARE PROBABLY |
| | MORE ELECTRICAL COMMENTS BUT PLANS |
| | ARE NOT COMPLETE ENOUGH TO MEET NEC |
| | REQUIREMENTS FOR COMMERCIAL APTS. |
| | |
| | PLEASE SUBMIT ALL OF THE ABOVE FOR |
| | REVIEW AND ADDRESS OTHER ISSUES. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | |
| | |
| | |
| | ***** PLEASE NOTE**** |
| | THAT COMPLETE VALUE OF TOTAL SCOPE OF |
| | WORK NEEDS TO BE SUBMITTED WITH PERMIT |
| | APPLICATION AND FEES AJUSTED. |
| | PER 104.7.5 |
| | VALUE ON APPLICATION WAS CHANGED FROM |
| | ORIG SUBMITTAL AND FEES WERE NOT AJUSTED |
| | OWES FEES FOR RESUBMITTALS. |