Plan Review Details - Permit 01071195
Plan Review Stops For Permit 01071195
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-10-15 Cont ID  
Sent By lmartine Date 2001-10-15 Time 12:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-09-11 Cont ID  
Sent By jwitmer Date 2001-09-11 Time 09:56 Rev Time 1.00
Received By jwitmer Date 2001-09-11 Time 09:56 Sent To  
Notes
2001-09-11 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01071195
 101 N CLEMATIS ST
  
 SBC= STANDARD BUILDING CODE
  
 1)- SHEET A-9 DOOR SCHEDULE DOORS
 200-A / 229-A ARE TO COMPLY WITH SBC
 1012.7 ACCESS-CONTROLED EGRESS DOORS
 (4) ACTIVATION OF THE BUILDING FIRE
 ALARM SYSTEMS,IF PROVIDED SHALL AUTOMAT-
 ICALLY UNLOCK THE DOORS. THE DOORS SHALL
 REMAIN UNLOCKED UNTIL THE SIGNALING SYS-
 TEMS HAVE HAVE BEEN RESSET.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By hpiskura Date 2001-08-14 Time 07:32 Rev Time 0.00
Received By hpiskura Date 2001-08-13 Time 15:47 Sent To  
Notes
2001-08-14 00:00:00THE DOOR SHOWN AS 200A AT THE LOBBY IS
 REQUIRED TO BE FIRE RATED AND LABELED
 3/4 HOUR.SEE SBC 705.1.2.1 AND TABLE
 705.1.2 FOR TENANT SEPARATION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-14 Cont ID  
Sent By dpalmer Date 2001-11-14 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2001-11-14 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 23:34 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 23:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 18:23 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 18:23 Sent To  
Notes
2001-09-10 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT CLARIFICATION
 FOR GROUND OF TRANSFORMER PER 250-30
 CLARIFY POINT OF ATTACHMENT TO BLDG
 STEEL. AS IT IS NOT KNOWN IF THERE ARE\\
 ANY BREAKS IN COLD WATER LINE OF PVC.
  
 2)NOTE: PLEASE NOTE THAT AIC RATING WERE
 SUBMITTED FOR ALL PANELS. BUT PLEASE
 NOTE THAT THE AVAILABLE FAULT CURRENT IS
 SHOWN FOR MAIN BUT PLEASE SHOW WHAT THE
 ACTUAL RATING OF EQUIPMENT NEEDS TO BE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 15:45 Sent To  
Notes
2001-08-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY METHOD OF GROUND-
 ING FOR TRANSFORMER PER 250-30.
  
 2)NOTE: PLEASE NOTE THAT PANEL "MLA" IS
 SHOWN W/OUT MAIN.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE SHOWN
 FOR PANELS BUT NEEDED FOR MAIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-15 Cont ID  
Sent By lsmith Date 2001-08-15 Time 13:06 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-03 Cont ID  
Sent By mcarsill Date 2001-10-03 Time 13:28 Rev Time 0.00
Received By mcarsill Date 2001-10-03 Time 13:28 Sent To  
Notes
2001-10-03 00:00:00APPROVED PROVISO:
  
 LOCKING DEVICES INSTALLED ON ANY
 EXIT DOORS ARE TO MEET CODE AND FIRE
 RESCUE APPROVAL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-05 Cont ID  
Sent By mcarsill Date 2001-09-05 Time 13:42 Rev Time 0.00
Received By mcarsill Date 2001-09-05 Time 13:41 Sent To  
Notes
2001-09-05 00:00:001) ADDITIONAL EXIT SIGNS REQUESTED BY
 THIS OFFICE NOT SHOWN ON REVISED
 DRAWINGS.
 2) REVISED PLANS INDICATE THE CARD
 READER WILL FAIL SAFE OPEN. PLEASE
 PROVIDE MORE DETAILS ON THE SECURITY
 FEATURES PLANNED FOR THE SPACE. PLEASE
 BE ADVISED THAT LOCKING DEVICES
 INSTALLED ON EXIT DOORS TO COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS PER THE
 LIFE SAFETY CODE.
  
 MIKE CARSILLO, CAPTAIN
 835-2910
 659 8096 X-8497

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By mcarsill Date 2001-08-15 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2001-08-15 Time 14:22 Sent To  
Notes
2001-08-15 00:00:001) DOOR SCHEDULE INDICATES DOORS 200A
 ARE ABSENT OF A FIRE RATING. DOORS
 200A ARE REQUIRED TO HAVE A FIRE RATING.
 2) PLEASE EXPLAIN CARD KEY ACCESS. HOW
 DOES THESE DEVICES AFFECT EXITING. HOW
 DOES THE CARD READER AFFECT FIRE RESCUE
 ACCESS INTO THE SPACE VIA THE EXIT
 STAIR NEAR CORRIDOR 229.
 3) ADDITIONAL EXIT SIGNS MAY BE NEEDED
 TO DIRECT PERSONS TO EXIT LOCATIONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2002-01-28 Cont ID  
Sent By pkrauss Date 2002-01-28 Time 14:56 Rev Time 0.40
Received By pkrauss Date   Time   Sent To  
Notes
2002-01-28 00:00:00MECH REV 01101056

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-12-19 Cont ID  
Sent By pkrauss Date 2001-12-19 Time 11:24 Rev Time 0.45
Received By pkrauss Date 2001-12-19 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-11-02 Cont ID  
Sent By pkrauss Date 2001-11-02 Time 10:20 Rev Time 0.30
Received By pkrauss Date 2001-11-02 Time 10:20 Sent To  
Notes
2001-11-02 00:00:00REVISION TO DUCTWORK (NOTES)

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-27 Cont ID  
Sent By pkrauss Date 2001-09-27 Time 12:56 Rev Time 1.00
Received By pkrauss Date 2001-09-27 Time 12:27 Sent To  
Notes
2001-09-27 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-09-10 Cont ID  
Sent By pkrauss Date 2001-09-10 Time 09:42 Rev Time 4.00
Received By pkrauss Date 2001-09-07 Time 16:23 Sent To  
Notes
2001-09-10 00:00:00*******************DENIED***************
  
  
 1.PLAN SHEET A-1 ELECTRIC ROOM (241)
 INDICATES A FIRE RATING OF 1 HOUR,
 THERE IS NO FIRE DAMPER INICATED FOR
 THE SUPPLY AIR TO THAT SPACE.THIS
 ELECTRIC ROOM IS NOT IDENTIFIED ON
 MECHANICAL PLAN TH-24, ROOM 241 ON
 TH-24 IS THE STORAGE ROOM.ALSO,
 SHOULD THE STORAGE ROOM HAVE A FIRE
 RATING OF 1 HOUR AS THE ELEC. RM.,
 IT TOO WILL REQUIRE A FIRE DAMPER
 ON THE SUPPLY AIR TO THAT SPACE.
  
 2.WITH REGARD TO THE CARBON DIOXIDE
 SENSOR IN THE CONFERENCE ROOM, AT
 ANY GIVEN TIME OUTSIDE AIR REQUIRE-
 MENTS SHALL NOT BE LESS THAN THAT
 SPECIFIED IN ASHRAE 62-89.
  
 NOTE:FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR FOR UNITS LESS THAN
 2,000 CFM THAT SERVE AN AREA OF
 EGRESS OR UNITS WITH AGGREGAGE
 AIR TOTALING 2,000 CFM OR
 GREATER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By ndenmark Date 2001-08-14 Time 11:19 Rev Time 0.50
Received By ndenmark Date 2001-08-14 Time 11:19 Sent To  
Notes
2001-08-14 00:00:00**************DENIED*******************
  
 PROVIDE OUTSIDE AIR SCHEDULE PER ASHRAE
 62-89.
  
 PROVIDE AIR BALANCE SHOWING COMPLIANCE
 WITH SMC 501.2
  
 VENTILATION REQUIRED FOR ELECTRIC ROOM
  
 OUTSIDE AIR REQUIRED FOR EQUIPMENT ROOM
 (269)
  
 PROVIDE INFORMATION ON (EXISTING?)
 RETURN AIR FROM THE SPACE TO THE A/C
 UNIT.
  
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR TO
 BE TESTED.

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-10-31 Cont ID  
Sent By kstevens Date 2001-10-31 Time 17:02 Rev Time 0.50
Received By kstevens Date 2001-10-31 Time 17:02 Sent To  
Notes
2001-10-31 00:00:00PASSED/PROVISO
  
 FLOOR SINK TO HAVE TRAP PRIMER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-10-12 Cont ID  
Sent By kstevens Date 2001-10-12 Time 13:59 Rev Time 0.25
Received By kstevens Date 2001-10-12 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-27 Cont ID  
Sent By kstevens Date 2001-09-27 Time 17:53 Rev Time 0.33
Received By kstevens Date 2001-09-27 Time 17:53 Sent To  
Notes
2001-09-27 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) PREVIOUS COMMENTS, (9-6-1), NOT
 ADDRESSED. ALL INDIRECT WASTE SHALL
 DRAIN TO A FLOOR SINK. HUB DRAINS ARE
 NOT APPROVED. PLEASE DRAIN BACKFLOW INTO
 A FLOOR SINK.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-06 Cont ID  
Sent By kstevens Date 2001-09-06 Time 18:13 Rev Time 0.33
Received By kstevens Date 2001-09-06 Time 18:13 Sent To  
Notes
2001-09-06 00:00:00DENIED
  
 PER SPC-94 ALL INDIRECT WASTE SHALL
 DRAIN TO A FLOOR SINK. HUB DRAINS ARE
 NOT ALLOWED. PLEASE DRAIN BACKFLOW INTO
 A FLOOR DRAIN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By jleech Date 2001-08-08 Time 13:37 Rev Time 1.25
Received By jleech Date 2001-08-08 Time 13:36 Sent To  
Notes
2001-08-08 00:00:00DENIED;
  
 1.A REDUCED PRESSURE BACKFLOW PREVENTOR
 MUST BE INSTALLED ON WATER LINE TO
 HUMIDIFIER. BACKFLOW PREVENTOR MUST
 BE INSTALLED IN AN READILY ACCESSIBLE
 AREA NOT MORE THAN 4' ABOVE FINISH
 FLOOR. A FLOOR DRAIN WITH A TRAP
 PRIMER IS REQUIRED.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-15 Cont ID  
Sent By lsmith Date 2001-08-15 Time 13:06 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***