Plan Review Details - Permit 01071119
Plan Review Stops For Permit 01071119
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-12-06 Cont ID  
Sent By jwitmer Date 2001-12-06 Time 06:37 Rev Time 3.00
Received By jwitmer Date 2001-12-06 Time 06:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-11-14 Cont ID  
Sent By jwitmer Date 2001-11-14 Time 17:11 Rev Time 3.50
Received By jwitmer Date 2001-11-14 Time 17:11 Sent To  
Notes
2001-11-14 00:00:00BUILDING PLAN REVIEW
 700 S ROSEMARY # 204
 PLAN REVIEW " 01071119
 ARCH: CRAIG MOSSEY
 TEL: (561) 416-9059
 FAX: (561) 416-9058
 BOCA RATON, FL 33486
 SBC=1997 STANDARD BUILDING CODE
 SBC* AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SBC 903.5 (1) FIRE SPRINKLER PLANS
 ARE REQUIRED FOR TYPE II CONSTRUCTION,
 TOBE SUBMITTED AS PART OF THE BUIULDING
 PERMIT PACKAGE. A SEPERATE PERMIT PLANS
 AND FEES SHALL BE REQUIRED.
  
 2)-NORTH WALL FIXED SEATING AT RAMP # 3
 SHALL BE A MINIMUM OF 3'-8", A REDDUC-
 TION OF 1'-0" FOR THE FIXED SEATING
 AGAINST THE NORTH WALL,(SEE SBC1019.10.3
 .3) THE EGRESS ISLE THEN HAS 2'-8".
  
 3)- SHEET A2.0 WEST TENANT SEPERATION
 WALL IS INDICATED AS A 1 HR.WALL, SBC
 704.1 ASSEMBLY REQUIRES A 2 HR SEPERA-
 TION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-09-17 Cont ID  
Sent By jwitmer Date 2001-09-17 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2001-10-25 Time 11:32 Sent To  
Notes
2001-09-17 00:00:00BUILDING PLAN REVIEW
 700 S ROSEMARY AVE
 PERMIT # 01071119
 "NV LONGE"
 ARCHITECT: CRAIG MOSSEY
 TEL: (561) 416-9059
 FAX: (561) 416-9058
 BOCA RATON, FL 33486
 SBC= 1997 STANDARD BUILDING CODE
 FL ACC CODE= 1997 FLORIDA ACCESSIBILITY
 CODE
  
 1)_ FROM PREVIOUS REVIEW: SBC 1204.2
 RESTROOMS SHALL HAVE NONABSORBANT FLOORS
 AND WALLS TO A HEIGTH OF 4'-0".
  
 2)- FROM PREVIOUS REVIEW: FL ACC CODE
 4.5.1. FLOOR SURFACES ALONG ACCESSIBILE
 ROUTES AND IN ACCESSIBLE ROOMS AND
 SPACESINCLUDING FLOORS, WALKS,STAIRS
 CURBS AND RAMPS SHALL BE FIRM, STABLE
 AND SLIP RESISTANT. A STATIC COEFFICIENT
 OF FRICTION OF 0.6 IS RECOMMENDED FOR
 FLOORS AND 0.8 FOR RAMPS.
  
 3)- DOORS E-1, E-2 PROVIDE PRODUCT INFOR
 MATION FOR 2 HR. FIRE RATING FOR DOORS
 AND THE TRANSOMS ABOVE.WINDOWS 1-4 AL-
 SO WILL REQUIRE 2 HR. FIRE RATING. DOOR
 X-1 INDICATES FLUSH SHOW DETAIL FOR 1HR
 RATING AND THE HARDWARE FOR THE DOOR,
 SBC 1012.1.2 (1-3).
  
 4)- FROM PRREVIOUS REVIEW ; ADDITIONAL
 INFORMATION REQUIRED, SHEET A7.1 DETAIL
 #4, 3" MEDIUM DENSE FOAM, FLAME & SMOKE
 DEVELOPMENT.
  
 5)- REVOLVING DOORS SBC 1012.3(1-6)
 ENTRANCE DOORS AT LOUNGE #2 ARE TO COM-
 PLY. THERE IS ALAO A DISCREPANCY FROM
 SHEET A.2 AND AC.1, P1 & E.1. THE SUB
 TRADE SHEETS SHOW A AWING DOOR WHWEREAS
 A.2 DOESN'T?
  
 6)- FROM PREVIOUS REVIEW, SBC 403.2.4.
 PLATFORM CONSTRUCTION, FOR RAISED PLAT-
 FORMS & RAMPS. FLOORS ARE TO BE BUILT AS
 A TYPE II BUILDING CONSTRUCTION. LIVE
 LOADS AS PER CHAPTER 16. 100 LBS/ SQ FT.
 TABLE 600 TYPE II CON. FLOORS (2HR. RAT-
 ING) NONCOMBUSTIBLE 604,609.2.1,
 FLOOR FINISH 803.7.1, SEE SBC SEC 706,
 707.
 AC-1 INDICATES A/C DUCTS BENEATH PLAT-
 FORM, E.2 (D) INDICATES THAT THERE ARE
 TO BE RECESSED LIGHTS IN FLOORING PLEASE
 DETAIL.
  
 7)- DISCREPANCY, AREA 21 DANCE AREA VIP
 2'-4" ELEVATION VS. DETAIL 6/A9.2.
  
 8)- SBC 903.5 (1) FIRE SPRINKLER PLANS
 ARE REQUIRED FOR TYPE II CONSTRUCTION.
  
 9)- SHEET A.9.1 SEC 8 2X4 BLOCKING.
 SBC 609.2.1 NONCOMBUSTIBLE MATERIALS
 FRAMING & BACKING IN WALLS, FIRE RESIS-
 TANT TREATED WOOD MAY BE USED.
  
 10)- FROM PREVIOUS REVIEW, SHEET A9.3
 HANGING CEILING DETAILS, EXPANSION BOLTS
 INTO EXISTING SLAB? TYPE OF ANCHOR?DEPTH
 OF ANCHOR?
  
 11)- LETTER FROM ENGINEER FOR THE ADDITI
 ONAL LOADING OF BAR JOIST, THAT THE BAR
 JOIST WILL TAKE THE ADDITIONAL LOADING.
 AC.2 ROOF CURB DETAILS : NOTE #4 SEE
 STRUCTURAL DETAILS, THERE ARE NONE?
 THE ADDITIONAL LOADS FOR THE AIR HAND-
 LERS DOESN,T INDICATE IF THE LOADS ARE
 BEING TRANSFERED TO THE TOP OR BOTTOM
 CORD OF THE BAR JOIST, PLEASE HAVE THE
 ENGINEER OF RECORD INDICATE?
  
 12)- A9.3 SECTION #2 FINISH INFORMATION
 ON THE SUSPENDED DOME. SMOKE DEVELOPMENT
 AND FLAME SPREAD.
  
 13)- ROOF /CEILING ASSEMBLY: TABLE 600
 1 HR PROTECTED FOR TYPE II STRUCTURE
 (BAR JOIST) SHOW COMPLIANCE.
  
 14)- A1.0 NORTH WALL FIXED SEATING AT
 RAMP # 3 3'-8" REQUIRED, MINIMUM.
 SBC 1019.10.3.3 SUBTRACT 12" FOR THE
 FIXED SEATING AGAINST THE NORTH WALL.
 ACCESS ISLE NOW ONLY HAS 2'-8" NOT LEGAL
  
  
 15)- A 1.0 AT THE FOOT OF RAMP #1 AND AT
 THE END OF RAMP #2 "HATCHED MARKS"
 INDICATING WHAT?

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-17 Cont ID  
Sent By jwitmer Date 2001-08-17 Time 14:29 Rev Time 6.00
Received By jwitmer Date 2001-08-17 Time 14:29 Sent To  
Notes
2001-08-17 00:00:00BUILDING PLAN REVIEW
 700 S ROSEMARY AVE # 204
 PERMIT # 01071119
 "N V LOUNGE"
 ARCHITECT:
 GUILLERMO GOMEZ
 TEL : (212) 628-7276
 FAX : (212) 585-2251
 119 E 64 STREET
 NW YORK NY 10021
  
 1)- MISSING : COMMON ENTRY AREA( NOT
 TENANT SPACE) EXIT ACCESS DOOR MISSING
 SBC 1005.3
  
 2)-SBC 1204.2 RESTROOMS SHALL HAVE
 NONABSORBEANT FLOORS & WALLS TO A HEIGHT
 OF 4'-0".
  
 3)- FLORIDA ACCESSIBILITY CODE 4.5.1.
 FLOOR SURFACES ALONG ACCESSIBLE ROUTES
 AND IN ACCESSIBLE ROOMSAND SPACES IN-
 CLUDING FLOORS, WALKS,STAIRS AND CURB
 RAMPS SHALL BE FIRM, STABLE AND SLIP RE-
 SISTANT. A STATIC COEFFICIENT OF FRIC-
 TION OF 0.6 IS RECCOMMENDED FOR FLOORS
 AND 0.8 FOR RAMPS.
  
 4)- SHEET 5.1 DOOR SCHEDULE HASN'T ANY
 CORRESPONDING NUMBERS ON FLOOR PLAN NOR
 THE LIFE SAFETY?
 COMMENT: THERE SHOULD BE 5 RATED DOORS
 FROM THE TENANT SPACE DOOR SCHEDULE DOES
 NOT INDICATE THIS. RATE THE EXIT ACCESS
 DOOR OUTSIDE OF THE TENANT SPACE.
  
 5)- SBC 104.2.2. ADDITIONAL INFORMATION
 REQUIRED ON SHEET A7.1 DETAIL #4, 3"
 MEDIUM DENSE FOAM, FLAME & SMOKE DEVELOP
 MENT
  
 6)- SBC 104.2.2. SHEET A 7.1 DETAIL #3
 STEEL LAADDER? USAGE? IT LOOKS LIKE IT
 MAY INTERFERE WITH THE EGRESS. IF THE
 USAGE IS LIGHT STORAGE THE SBC 1606.4
 FOR LIGHT STORAGE IS 125 LBS/ SQ FT.
 HOW IS THIS FLOOR AREA HELD UP? IF THIS
 AREA IS A DANCE FLOOR, VERTICAL ACCESS-
 IBILITY REQUIREMENTS ARE TO BE MET.
  
 7)- DOOR OPENING JUST LEFT OF BAR # 1.
 THE DOOR SWING DOES NOT MEET THE EGRESS
 REQUIREMENTS, SBC 1012.1.2. SWING IN THE
 DIRECTION OF EGRESS (1) WHICH SSERVE
 AN OCCUPANT LOAD OF 50 OR MORE PEOPLE. T
 HE SAME CONCERNS ARE RAISED WHERE (2)
 SETS OF DOORS PIVOT!
  
 8)- SBC 403.2.4 PLATFORM CONSTRUCTION
 FOR RAISED PLATFORMS & RAMPS. FLOORS ARE
 TO BE BUILT AS TYPE II CONSTRUCTION,
 LIVE LOADS AS PER CHAPTER 16 / 100 LBS/
 SQ. FT.
  
 9)- SBC 903.5.(1) FIRE SPRINKLER PLANS
 ARE REQUIRED TYPE II CONSTRUCTION.
  
 10)- SHEET A9.1 SBC 609.2.1. NONCOMBUST-
 IBLE MATERIAL FRAMING & BACKING IN WALLS
 FIRE RESISTANT TREATED PLYWOOD MAY BE
 USED.
  
 11)- SHEET A 9-3 HANGING CEILING DETAILS
 EXP BOLT W/ BOLT HANGERS INTO EXISTING
 SLAB? TYPE OF HANGER? DEPTH OF ANCHOR,
 WIDTH OF ANCHORNOT GIVEN, NOR THE
 ATTACHMENT TO 1/4" STEEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-24 Cont ID  
Sent By lmartine Date 2001-07-24 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2001-08-17 Time 14:29 Sent To  
Notes
2001-07-24 00:00:00BUILDING COMMENTS
 -----------------
  
 PLANS ARE INCOMPLETE.
 PLEASE PROVIDE COMPLETE SET OF
 DRAWINGS,DETAILS AND SPECIFICATIONS.
  
  
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-12-05 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2001-12-05 Time 20:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 20:07 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 20:07 Sent To  
Notes
2001-11-07 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY WHERE THE LOAD
 CALCULATIONS ARE SHOWN AND WHERE THE
 CONTINUOUS LOADS AT 125%.EVERYTHING IS
 SHOWN AT CONNECTED LOAD.
 2)NOTE: PLEASE SHOW WHERE LOADS CALCS
 ARE SHOWN FOR TRACK LIGHTING PER 220-12B
  
 3)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 PLANS SHOW TRANSFORMER AND ASSC EQUIP-
 -MENT ABOVE WALK-IN COOLER, BUT ARCH
 DETAILS ON A3.0 SHOW A DIFFERENT LOCAT-
 -ION? PLEASE SUBMIT A DETAIL ON THE
 OPEN MOUNTING/PLATFORM FOR TRANSFORMER.
 PLEASE NOTE THAT ALL MUST MEET 110-26
 AND 450-13 ECT
  
 4)NOTE: PLEASE NOTE THAT NOTE ON PLANS
 MENTION GC TO SUBMIT DETAILS FOR THE
 TRANSFORMER PLATFORM/MOUNTING ETC.
 THIS IS REQ`D TO BE SUBMITTED FOR
 PLAN REVIEW.PLEASE SUBMIT BOTH ELECTRICA
 L AND STRUCTURAL DETAILS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 22:01 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 22:00 Sent To  
Notes
2001-09-18 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT DETAIL ON GROUND-
 -ING OF TRANSFORMER PER 250-30
  
 2)NOTE: PLEASE NOTE THAT TRANSFORMER
 SHOWN ON E.1 AND E.4 ARE TWO DIFFERENT
 SIZES, PLEASE CLARIFY.
 PLEASE PROVIDE STRUCTUAL MOUNTING
 DETAIL ON E.4 FOR TRANSFORMER.
 PLEASEKEEP IN MIND 450-9 AND 450-13
  
 3)NOTE: PLEASE NOTE AS PER LOCAL AMEND-
 -MENTS:210-50 OUTLET SPACING IS EVERY
 20' OF UNENCUMBERED WALL SPACE.
 PLEASE REVISE OUTLET LAYOUT.
  
 4)NOTE: PLEASE NOTE ALL TRACK LIGHTING
 CALCULATIONS TO BE SHOWN PER 220-12B
  
 5)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. PLEASE
 NOTE 230-42 AND 215-2/3.
  
 6)NOTE: PLEASE NOTE EQUIPMENT(DISCONNECT
 -S FOR TRANSFORMER DO NOT MEET DEDICATED
 ELECTRICAL SPACE PER 110-26. FLOOR TO
 CEILING. PLEASE NOTE THAT THE TOP OF
 WALK-IN COOLERS ARE ALOMOST ALWAYS USED
 FOR STORAGE. PLEASE FIND A DEDICATED
 SPACE PER. 110-26 AND 384-7.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 21:15 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 21:15 Sent To  
Notes
2001-08-21 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NO ELECTRICAL
 PLANS WERE SUBMITTED FOR REVIEW.??
  
 PLEASE SUBMITPLANS FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-30 Cont ID  
Sent By kstevens Date 2001-08-30 Time 09:53 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-12-10 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 09:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-11-15 Cont ID  
Sent By mcarsill Date 2001-11-15 Time 12:07 Rev Time 0.00
Received By mcarsill Date 2001-11-15 Time 12:07 Sent To  
Notes
2001-11-15 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
 2) TENANT DEMISING WALL ON PAGE A2.0
 INDICATES A ONE-HOUR FIRE RATING.
 BUILDING CODE REQUIRES A TWO-HOUR
 RATING.
 3) A PROBLEM SEEMS TO BE PRESENT WITH
 THE BENCH SEATING AND AISLE REQUIREMENTS
 NEAR CALL OUT 6A9.2.
 4) HOW WILL THE FOG MACHINE BE USED
 AND HOW WILL IT AFFECT EXITING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-14 Cont ID  
Sent By mcarsill Date 2001-08-14 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2001-08-14 Time 12:53 Sent To  
Notes
2001-08-14 00:00:001) PLATFORMS IF PERMANANT, ARE TO BE
 CONSTRUCTED OF MATERIALS FO THE TYPE
 OF CONSTRUCTION IN WHICH THE PLATFORMS
 ARE LOCATED.
 2) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 3) THE SHARED FOYER MUST BE AT LEAST
 7'- 6" HIGH. ANY PROJECTIONS FROM THE
 CEILING MUST BE AT LEAST 7'- 0 FROM THE
 FINISHED FLOOR.
 4) PLEASE PROVIDE PRODUCT APPROVALS FOR
 2 HOUR FIRE PROOF TEMPERED GLASS AND
 DOORS SHOWN ON THE DRAWINGS.
 5) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTS SHOWN.
 6) NO FIRE ALARM EQUIPMENT SHOWN ON THE
 DRAWINGS.
 7) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-25 Cont ID  
Sent By mcarsill Date 2001-07-25 Time 10:09 Rev Time 0.00
Received By mcarsill Date 2001-07-25 Time 10:09 Sent To  
Notes
2001-07-25 00:00:001) PLEASE INDICATE LOCATIONS OF ALL
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING EQUIPMENT.
 2) NO INTERIOR FINISH PROVIDED WITH
 PLANS.
 3) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF
 100 OR MORE PERSONS.
 4) PLEASE PROVIDE MORE DETAILS FOR RAMP.
 5) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 6) NO FIRE SPRINKLER DRAWINGS PROVIDED.
 7) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS.
 8) HOW IS SMOKE REMOVED FROM THIS
 INTERIOR SPACE SHOULD A FIRE DEVELOP.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 11:28 Rev Time 0.35
Received By pkrauss Date 2001-12-08 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-16 Cont ID  
Sent By pkrauss Date 2001-11-16 Time 09:41 Rev Time 0.45
Received By pkrauss Date 2001-11-16 Time 09:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-09-21 Cont ID  
Sent By pkrauss Date 2001-09-21 Time 14:21 Rev Time 2.00
Received By pkrauss Date 2001-09-21 Time 12:07 Sent To  
Notes
2001-09-21 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 2.PROVIDE PLAN INDICATING TERMINATION
 OF EXHAUST FANS.
  
 3.INDICATE MATERIAL AND R-VALUE OF
 DUCTWORK.
  
 4.CLARIFY VENTILATION FOR RESTROOMS.
 NO EXHAUST FANS ARE INDICATED ON
 PLAN.AIR SHALL NOT BE RECIRCULATED
 FROM THE RESTROOMS AS PER 1997 SMC
 503.3.1.
  
 5.DO NOT SEE EXHAUST FANS F-5 AND F-6
 LOCATION ON PLAN.
  
 6.ACCESS FOR AHU SHALL BE ADAQUATE FOR
 SERVICE AND REPLACEMENT OF THE
 LARGEST PIECE TO THE EQUIPMENT.
  
 7.AUXILIARY DRAIN PAN SHALL HAVE OVER-
 FLOW PROTECTION BY MEANS OF A FLOAT
 SWITCH OR A DRAIN LINE TERMINATING
 AT A CONSPICUOUS POINT TO SERVE AS
 AN ALARM THAT THE REGULAR DRAIN IS
 RESTRICTED.
  
 8.PROVIDE DETAIL OF THE CONDENSER TO
 WALK-IN COOLER.IF CONDENSER IS
 LOCATED ON THE ROOF, PROVIDE A
 DETAIL OF STAND AND HOW IT WILL BE
 ATTACHED TO THE ROOF.18" MINIMUM
 BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL.
  
 NOTE:ADDITIONAL PERMIT REQUIRED FOR
 WALK-IN COOLER.PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status R Date 2001-08-23 Cont ID  
Sent By ndenmark Date 2001-08-23 Time 09:18 Rev Time 0.33
Received By ndenmark Date 2001-08-23 Time 09:18 Sent To  
Notes
2001-08-23 00:00:00NO MECHANICAL INFORMATION SUBMITTED FOR
 REVIEW, INCLUDING CODE REQUIRED MINIMUM
 OUTSIDE AIR AND EXHAUST FOR BATHROOMS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-04 Cont ID  
Sent By pschmitz Date 2001-11-04 Time 13:34 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-04 00:00:00PLUMBING PLAN REVIEW, APPROVED WITH
 PREVIOUS COMMENTS ADDRESSED.PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-12 Cont ID  
Sent By kstevens Date 2001-09-12 Time 09:20 Rev Time 1.50
Received By kstevens Date 2001-09-12 Time 09:20 Sent To  
Notes
2001-09-12 00:00:00DENIED
 REFERENCE SPC-94 - FACBC-97
 1) COMMENT #1 FROM PLAN REVIEW 8-30 NOT
 ADDRESSED. PLANS TO BE ROUTED TO THE
 PALM BEACH COUNTY HEALTH UNIT, DIVISION
 OF ENVIRONMENTAL HEALTH, (901 EVERNIA ST
 WPB FLA 33401), (561) 355-3018 FOR PLAN
 REVIEW BEFORE CITY OF WPB PLAN REVIEW.
 2) PAGE A4.1 FINISH SCHEDULE, PLEASE SUB
 MIT MANUFACTURE INFORMATION ON THE PRO-
 DUCT USED TO KEEP WALLS AND FLOORS NON-
 ABSORBANT. (CARMINAR)
 3) PAGES P.1, P.2 & P.4 FD-2 SHOULD READ
 FS-2 FOR FLOOR SINK.
 4) PAGE P.2 WATER HAMMER ARRESTORS TO BE
 SIZED AND LOCATED PER MANUFACTURS INSTAL
 LATION INSTRUCTIONS AND WH-PDI 201. NOT
 ON TOP OF DROP AS SHOWN ON WATER RISER
 DIAGRAM.
 5) PAGE P.2 WATER RISER DIAGRAM & WATER
 RISER NOTES, PAGE P.5 PLUMBING SPECIFIC-
 ATIONS #'S 7 & 8. AIR CHAMBERS SHALL
 COMPLY WITH SPC-94 SECT'S. 607.8.2 &
 607.8.3 SHALL BE ACCESSABLE AND RECHARG-
 ABLE.
 6) PAGE P.2 SANITARY RISER DIAGRAM. LAVS
 NOT VENTED PROPERLY. SHOW VENT THRU ROOF
 OR OTHER VENT DETAIL.
 7) PAGE P.2 SANITARY RISER DIAGRAM.
 FUNNEL DRAINS NOT APPROVED, ALL INDIRECT
 WASTE TO DRAIN TO FLOOR SINKS. SPC 804.5
 8) PAGE P.3 WATER HEATER DETAIL. SHUT
 OFF VALVE ON SUPPLY SIDE (COLD) TO BE
 ACCESSABLE. PUT VALVE CLOSE TO HEATER.
 9) PAGE P.5 PLUMBING SPECIFICATIONS. #5
 HUB DRAINS NOT APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-30 Cont ID  
Sent By kstevens Date 2001-08-30 Time 09:18 Rev Time 1.00
Received By kstevens Date 2001-08-30 Time 09:18 Sent To  
Notes
2001-08-30 00:00:00DENIED
  
 REFERENCES - SPC-94 - FACBC-97
  
 1) PLANS TO BE ROUTED TO THE PALM BEACH
 COUNTY HEALTH UNIT, DIVISION OF ENVIRON-
 MENTAL HEALTH (901 EVERNIA STREET WPB
 FL 33401 - 561 355-3018 - FOR PLAN RE-
 VIEW BEFORE CITY OF WPB PLAN REVIEW.
 2) NOT ENOUGH INFORMATION SUBMITTED.
 PLEASE SUBMIT A SANITARY AND WATER RISER
 DIAGRAM, CALCULATIONS FOR MINIMUM FAC-
 ILITIES, (TABLE 407 SPC-94), SHOW LOCAT-
 ION OF ALL BAR EQUIPMENT, AND SHOW LOC-
 ATION OF ALL FLOOR DRAINS, AND FOR IN-
 DIRECT WASTE ALL FLOOR SINKS.
 3) PAGE A10.1 BATHROOM STALL ELEVATION
 SECTION 2. WATER CLOSET SHOWS 1'7" TO
 CENTER AND IT SHOULD BE 1'6".
 4) PAGE A10.1 BATHROOM STALL ELEVATION
 SECTION 3. 1 URNAL SHALL MEET FACBC-97
 4.18 - 4.18.2 HEIGHT REQUIREMENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***