Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-04-26 Cont ID  
Sent By pkrauss Date 2002-04-26 Time 08:05 Rev Time 0.35
Received By pkrauss Date 2002-04-26 Time 08:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-01-08 Cont ID  
Sent By ndenmark Date 2002-01-08 Time 07:52 Rev Time 0.33
Received By ndenmark Date 2002-01-08 Time 07:52 Sent To  
Notes
2002-01-08 00:00:00NOTE:
 1. SUB DUCT MUST BE MINIMUM OF 26 GA AND
 RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE PER LOCAL AMENDMENTS TO THE
 SMC 610.1.3
 2. DRYER DUCT SHAFT SHALL TERMINATE TO
 THE OUTSIDE OF THE BUILDING WITH A FAN
 RATED FOR THE SHAFT SIZE AND HAVE A
 BACKDRAFT DAMPER AND NO BIRDSCREEN OR
 EACH DRYER DUCT SHALL BE RUN SEPARATELY
 TO PREVENT POSITIVE PRESSURE ON
 NONRUNNING DRYERS APARTMENTS
 3. BATHROOM EXHAUST DUCT TO TERMINATE
 OUTSIDE OF BUILDING TO REMOVE MOISTURE
 LADEN AIR AND PREVENT INTRODUCTION OF
 AIR FROM SHAFT INTO APTS. FAN TO BE
 SIZED FOR SIZE OF SHAFT AND HAVE
 BIRDSCREEN.
 THIS APPLIES TO ALL MECHANICAL PERMITS
 FOR PINNACLE PALMS PROJECT.
 PROVIDE ENGINEER'S DESIGN SHOWING
 COMPLIANCE WITH ABOVE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-07-20 Cont ID  
Sent By sjohnson Date 2001-07-20 Time 13:29 Rev Time 0.00
Received By sjohnson Date   Time   Sent To  
Notes
2001-07-20 00:00:00APPROVED PER PATTY KRAUSS