| Plan Review Stops For Permit 01071052 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-08-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-13 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-08-13 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-08 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-08 |
Time |
07:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-08-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-14 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-09-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-04 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-04 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-25 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-25 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-07-25 00:00:00 | 1) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 2) PLEASE PROVIDE MORE DETAILS ON QVENT. | | | WHAT DOES THIS EQUIPMENT PROTECT. IF | | | SMOKE OR GREASE LADEN VAPORS ARE EMITTED | | | THEN A HOOD,DUCT, AND FIRE SUPPRESSION | | | SYSTEM WILL BE REQUIRED THAT MEETS | | | NFPA 33 AND NFPA 17. | | | | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-14 |
Time |
16:49 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-14 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
11:48 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-08-09 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2001-08-09 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFOMRATION | | | FOR REVIEW. | | | | | | | | | 1.AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE | | | AS PER 1997 SMC 406.1 AND NFPA 90A | | | 4-4.4.3. | | | | | | 3.PLEASE INDICATE AS TO WHERE THE | | | CONDENSATE IS TO TERMINATE. | | | | | | NOTE, CONDENSATE WILL FOLLOW THE | | | PITCH OF THE ROOF SO LONG AS THE | | | PITCH IS DOWN. | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION AND WALK | | | IN COOLER/FREEZER.PLEASE | | | SUBMIT PLANS AND MANUFACTURER | | | SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-28 |
Time |
17:51 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-09-28 |
Time |
17:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-10 |
Time |
08:41 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-09-07 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2001-09-10 00:00:00 | DENIED | | | | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) COMMENT #1 FROM PREVIOUS REVIEW NOT | | | ADDRESSED. PLEASE COMPLY WITH RUNNING | | | THE GREASE LINE SEPARATE FROM THE SANIT- | | | ARY LINE. PAGE P-1 | | | | | | 2) PAGE P-1, WATER RISER DIAGRAM STILL | | | SHOWS AIR CHAMBERS AT EACH FIXTURE. | | | LOCATION OF WATER HAMMER ARRESTORS SHALL | | | BE PER MANUFACTURE'S INSTALLATION IN- | | | STRUCTIONS NOT AT TOP OF DROP AS SHOWN. | | | PLEASE LOCATE ARRESTORS WHERE INSTRUCTED | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-14 |
Time |
15:33 |
Rev Time |
1.75 |
| Received By |
kstevens |
Date |
2001-08-14 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2001-08-14 00:00:00 | DENIED | | | | | | 1) GREASE LINE REQUIRED TO PICK UP FLOOR | | | DRAINS, FLOOR SINKS, HAND SINKS, AND | | | THREE COMPARTMENT SINK. MINIMUN 750 GAL | | | GREASE TRAP REQUIRED. PLEASE CONTACT | | | RODNEY COMPO AT WEST PALM BEACH UTILITY | | | (561) 837-4074 | | | | | | 2) AIR CHAMBERS TO MEET SPC-94 REQUIRE- | | | MENTS 607.8.2 & 607.8.3 - MUST BE RE- | | | CHARGEABLE AND ACCESSABLE. | | | | | | 3) PERMINATE SHIPS LADDER REQUIRED FOR | | | WATER HEATER TO MAKE IT ACCESSABLE AND | | | SERVICEABLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-07 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|