| 2001-08-31 00:00:00 | BUILDING PLAN REVIEW |
| | 6215 S. FLAGLER DRIVE |
| | PERMIT # 01071037 |
| | ARCH: SMITH & MOORE |
| | TEL: (561) 835- 1888 |
| | FAX: (561) 832- 7015 |
| | |
| | SBC= STANDARD BUILDING CODE 1997 ED. |
| | SBC*=AMENDMENTS /STANDARD BUILDING CODE |
| | FBC= FLORIDA BUILDING CODE (WILL BE |
| | ADOPTED JAN.1, 2002). |
| | |
| | 1)- SBC* 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, A CURRENT SURVEY. |
| | |
| | 2)- NOTE: SITE IS LOCATED IN A A-5 FLOOD |
| | ZONE. BFE IS TO BE 7'-6", CITY CODE. |
| | |
| | 3)- SBC* 1804.2.7.2(3) REQUIRES SOILS |
| | TEST REPORT W/ MINIMUM BEARING VALUE. |
| | |
| | 4)-FL. ENERGY CODE 600.1 ENERGY CODE |
| | CALCULATIONS INCLUDING MANUAL "J". |
| | |
| | 5)- SBC 104.2.2*(2) SETS OF PLANS ARE |
| | REQUIRED FOR PERMIT APPLICATION. |
| | |
| | 6)- (PCN) PROPERTY CONTROL NUMBER INDICA |
| | TES THAT THERE IS A EXISTING TWO STORY |
| | STRUCTURE, IS THIS TO STAY ON THIS LOT? |
| | |
| | 7)- SHEET A-2 STRUCTURAL NOTES: |
| | SBC 1606.2.2. DESIGN CRITERIA ? |
| | CHAPTER 1606. |
| | ASCE 7-95 145 MPH BY INTERPERLATION |
| | |
| | 8)- SBC 411.4.2: THE GARAGE DOESN'T MEET |
| | THE EXCEPTION, OVER 850 SQ. FT. REQUIRES |
| | (6) EXCHANGES OF AIR AN HOUR. |
| | |
| | 9)- EXIT DOOR #120 REQUIRES A LANDING |
| | SEE SBC 1012.1.6. |
| | |
| | 10)- SBC TABLE 600 NORTH ELEVATION TYPE |
| | V CONSTRUCTION ALLOWABLE OPEN AREA 40% |
| | THIS IS EXCEEDED. TYPE V CONSTRUCTION |
| | SEE SBC 411.2.9. |
| | |
| | 11)- SHEET A-9AT THE GARAGE ELEVATION |
| | THERE IS A HASHED LINE, WHAT IS THIS |
| | INDICATION FOR? |
| | |
| | 12)- SBC BY DEFINITION OF PENTHOUSE |
| | (1517.1.1.3.)IS A THREE STORY BUILDING. |
| | SBC TABLE 500 FOR TYPE V CONSTRUCTION RE |
| | QUIRES EITHER FIRESPRINKLERS OR 1 HOUR |
| | PROTECTION. THIS WILL ALLOW FOR A THREE |
| | STORY BUILDING. |
| | |
| | 13)- SBC 705.6 WILL ALSO REQUIRE FLOOR |
| | CEILING ASSEMBLIES TO BE RATED, SHOW |
| | COMPLIANCE WITH PENETTRATIONS OF HORIZON |
| | TAL ASSEMBLIES. |
| | |
| | 14)- ELEVATOR PLEASE PROVIDE THE MANUFAC |
| | TURERS SPECIFICATIONS.SHOW COMPLIANCE |
| | WITH SBC SECTION 3003. |
| | |
| | 15)- MANUFACTUREED FIREPLACES SBC 2806 |
| | FALSE FIREPLACES 2807. MANUFACTURES |
| | SPECIFICATION, FRESH AIR INTAKES RE- |
| | QUIRED & SHOW COMPLIANCE WITH THE ENERGY |
| | CODE. |
| | |
| | 16)- ADDITIONAL INFOFRMATION REQUIRED |
| | SBC 2114 INFORMATION REGARDING THE SIZ- |
| | ING OF THE FIREPLACE FIREBOX NOT GIVEN, |
| | WIDTH & DEPTH OF FIREBOX. FLUE SIZING OF |
| | THE CHIMNEY ( FIGURE 2114.3.4) |
| | |
| | 17)- SBC 1606.2.6.2COMPONENTS & CLADDING |
| | ALL GLAZED OPENINGS WILL REQUIRE WINDOW |
| | & DOOR BUCK ATTACHMENT DETAILS, ALSO FOR |
| | THE GARAGE DOORS. |
| | |
| | 18)- SBC 1606.4.1/ 1707.4.1. ALL GLAZED |
| | OPENINGS WILL REQUIRE TESTING FOR WIND |
| | BORNE DERIS, LARGE MISSLE IMPACT RESIS- |
| | TANCE TESTING. OPENINGS THAT DONOT HAVE |
| | THIS APPROVAL WILL REQUIRE APPROVED |
| | STORM SHUTTERS EITHER SBCCI REPORT OR |
| | DADE COUNTY TESTING REPORTS ARE ACCEPTED |
| | (2) COPIES OF SAID REPORT WILL BE |
| | REQUIRED. A INSTALLATION SCHEDULE & KEY |
| | PLAN WILL ALSO BE REQUIRED, SEE ATTACH- |
| | MENT. |
| | |
| | 19)- ROOF COVERINGS: SBC 1707.5 CLAY / |
| | CONCRETE ROOF TILE TESTING FOR 110 HPH |
| | WIND ZONE. |
| | |
| | 20)- SBC 2405.2 SAFETY GLASS REQUIREMENT |
| | SEE MASTER BATH TUB, SHOWER DOORS, SWING |
| | DOORS,& SIDELIGHTS. |
| | |
| | 21)- FL S.S.515 -TO TIE TO POOL PERMIT: |
| | RESIDENTIALSWIMMING POOL SAFETY ACT. |
| | |
| | 22)- COUNTY IMPACT FEES DO AT TIME OF |
| | PERMIT ISSUANCE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X8412 |