Plan Review Details - Permit 01070988
Plan Review Stops For Permit 01070988
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-10-15 Cont ID  
Sent By jwitmer Date 2001-10-15 Time 15:02 Rev Time 1.00
Received By jwitmer Date 2001-10-15 Time 15:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-09-24 Cont ID  
Sent By jwitmer Date 2001-09-24 Time 13:32 Rev Time 2.00
Received By jwitmer Date 2001-09-24 Time 13:32 Sent To  
Notes
2001-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070988
 1515 N FLAGLER DRIVE # 130
 CONT: CATALFUMO
 LORI: 307- 4836
  
 1)- PLANS SHEET A-3 DETAIL 6-A, INDICATE
 THE USE OF A WATER CURTAIN WITH THE
 REFRENCE NER # 516 REPORT. IN THIS RE-
 PORT ARE INSTALLATION INSTRUCTIONS
 (4.1 SPRINKLER ORIENTATION) THE REPORT
 MAKES IT CLEAR THAT AT LEAST A 36" PONY
 WALL SHALL BE REQUIRED ABOVE THE FINISH
 FLOOR, AS INSTUCTED BY THE MANUFACTURERS
 INSTALLATION MANUAL.
 CONDITIONS OF USE (7.8) GLAZING ASS-
 EMBLIES ARE REQUIRED TO BE EQUIPPED WITH
 A SOLID PARTIAL WALL AT LEAST 36" ABOVE
 THE FINISH FLOOR, AS INSTRUCTED BY THE
 MANUFACTURERS INSTALLATION MANUAL OR BY
 APPROVED ALTERNATE PROTECTION MEASURES.
 A COPY OF THE REPORT WILL BE ATTACHED.
  
 2)- SHEET A-3 DETAIL 9 MAKES REFRENCE TO
 ATTACHMENT OF A SOFFIT TO THE DECK ABOVE
 BUT DOESN'T GIVE THE SPACING OR TYPE OF
 FASTENER?
  
 3)- SHEET A-1 FINISH SCHEDULE PUBLIC
 RESTROOMS SBC 1204.2 THE WALLS & FLOORS
 OF PUBLIC RESTROOMS SHALL BE LINED WITH
 AN NONABSORBANT MATERIAL TO THE HEIGTH
 OF 4'-0".
  
 4)- FL ACCESS CODE 1997 4.5 FLOOR SUR-
 FACES ALONG ACCESSIBLE ROUTES AND IN ACC
 ESSIBLE ROOMS & SPACES INCLUDING FLOORS
 WALKS, RAMPS STAIRS, SHALL BE STABLE,
 FIRM& SLIP-RESISTANT. ADDAGG A STATIC
 COEFFICIENT OF FRICTION OF 6.0 IS
 RECOMMENDED FOR ACCESSIBLE ROUTES AND
 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-23 Cont ID  
Sent By hpiskura Date 2001-08-23 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2001-10-15 Time 14:58 Sent To  
Notes
2001-08-23 00:00:00THE NER 516 REPORT IS FOR FIXED GLAZING
 NOT DOORS.SEE SBC 705.1.3.1 AND REVISE
 AS NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By hpiskura Date 2001-08-02 Time 15:44 Rev Time 0.00
Received By jwitmer Date 2001-10-15 Time 14:58 Sent To  
Notes
2001-08-02 00:00:00PLEASE PROVIDE THE DATA FOR THE GLASS
 STORE FRONT DOORS DEMONSTRATING
 COMPLIANCE WITH NFPA 80 AS PROVIDED FOR
 IN SBC 705.1.3.1.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-25 Cont ID  
Sent By dpalmer Date 2001-09-25 Time 07:18 Rev Time 0.00
Received By dpalmer Date 2001-09-25 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 20:46 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 20:46 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-08 Cont ID  
Sent By pkrauss Date 2001-08-08 Time 16:18 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 14:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-22 Cont ID  
Sent By mcarsill Date 2001-08-22 Time 15:13 Rev Time 0.00
Received By mcarsill Date 2001-08-22 Time 15:13 Sent To  
Notes
2001-08-22 00:00:001) THE NATIONAL EVALUATION REPORT
 SUBMITTED WAS DIFFICULT TO READ. AFTER
 LOCATING THIS EXACT TEST REPORT IN THE
 CONSTRUCTION SERVICES DEPARTMENT LIBRARY
 IT WAS DETERMINED THAT THIS ARRANGEMENT
 IS FOR WINDOWS NOT DOORS. PLEASE
 SUBMIT THE PROPER TEST REPORT FOR
 THE DOORS OR PROVIDE RATED FIRE DOORS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 09:48 Sent To  
Notes
2001-08-07 00:00:001) NO FIRE SPRINKLER HEAD SHOWN IN
 CLOSET 102.
 2) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS
 PROVIDED WITH PLANS.
 3) PLEASE INDICATE FIRE RATING ON
 3070 STOREFRONT DOORS.
 4) SECURITY FEATURES PLANNED FOR EXIT
 DOORS TO COMPLY WITH "SPECIAL LOCKING
 ARRANGEMENTS" OF THE 1985 EDITION OF
 THE LIFE SAFETY CODE, SECTION 5-2.1.6.1
 PLEASE SHOW COMPLIANCE ON PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-08 Cont ID  
Sent By pkrauss Date 2001-08-08 Time 16:17 Rev Time 0.50
Received By pkrauss Date 2001-08-08 Time 16:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2001-11-06 Cont ID  
Sent By kstevens Date 2001-11-06 Time 18:06 Rev Time 0.75
Received By kstevens Date 2001-11-06 Time 18:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2001-10-27 Cont ID  
Sent By kstevens Date 2001-10-27 Time 09:03 Rev Time 0.50
Received By kstevens Date 2001-10-27 Time 09:03 Sent To  
Notes
2001-10-27 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) LOUNGE SINK DETAILS ASKED FOR NOT
 ADDRESSED. PER FACBC-97 SEC 2.24 PLEASE
 SHOW CLEAR FLOOR SPACE, KNEE CLEARANCE,
 DEPTH, ECT FOR FRONTAL APPROACH.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-10-16 Cont ID  
Sent By kstevens Date 2001-10-16 Time 14:48 Rev Time 0.50
Received By kstevens Date 2001-10-16 Time 14:47 Sent To  
Notes
2001-10-16 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) THIRD NOTICE. PAGE A-4 DETAIL 4,
 SINK TO COMPLY WITH FACBC-97 SEC 4.24.
 SECTION 4.24.2 HEIGHT, 4.24.3 KNEE
 CLEARANCE, 4.24.4 DEPTH, 4.24.5 CLEAR
 FLOOR SPACE, 4.24.6 EXPOSED PIPES AND
 4.24.7 FAUCETS. PLEASE SHOW COMPLIANCE
 WITH SECTION 4.24 ON DETAIL 4.
  
 2) THIRD NOTICE. PAGES P1 & P2, FLAT
 DRAWING ROOM 102, SHOW FLOOR SINK NOT
 FUNNEL DRAIN. SANITARY RISER DIAGRAM,
 SHOW FLOOR SINK NOT FUNNEL FLOOR DRAIN
 FOR PAN DRAIN/RELIEF VALVE DISCHARGE.
  
 3) THIRD NOTICE. PAGE P-2 WATER RISER
 ISOMETRIC. SHOW PROPER PLACEMENT FOR
 WATER HAMMER ARRESTORS. THEY SHALL BE
 INSTALLED NEAR SOURCE OF VALVE NOT AT
 TOP OF DROP AS SHOWN. INSTALL PER MANU-
 FACTURE'S INSTRUCTIONS AND WH-PDI 201.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-26 Cont ID  
Sent By kstevens Date 2001-09-26 Time 18:16 Rev Time 0.50
Received By kstevens Date 2001-09-26 Time 18:16 Sent To  
Notes
2001-09-26 00:00:00DENIED
 REFERENCE SPC-94-FACBC-97
  
 1) PAGE A-4 PREVIOUS 2 PLAN REVIEW
 COMMENTS NOT ADDRESSED. ( 8-6 & 8-31)
 PLEASE SHOW COMPLIANCE WITH FACBC-97 SEC
 4.24 AT LOUNGE SINK DETAIL.
  
 2) PAGE P-2 PREVIOUS PLAN REVIEW COMMENT
 NOT ADDRESSED (8-31). SANITARY RISER DIA
 GRAM TO SHOW FLOOR SING, NOT FUNNEL
 FLOOR DRAIN FOR PAN DRAIN - RELIEF LINE
 DISCHARGE.
  
 3) PAGE P-2 PLUMBING SPECIFICATIONS #18.
 WATER HAMMER ARRESTORS TO COMPLY WITH
 MANUFACTURES INSTALLATION INSTRUCTIONS
 AND WH-PDI 201. SHOW PROPER INSTALLATION
 NOT AT TOP OF DROP AS SHOWN ON WATER
 RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-08-31 Cont ID  
Sent By kstevens Date 2001-08-31 Time 16:49 Rev Time 0.50
Received By kstevens Date 2001-08-31 Time 16:49 Sent To  
Notes
2001-08-31 00:00:00DENIED
 REFERENCES: SPC-94 - FACBC-97
  
 1) PAGE A-4, PREVIOUS PLAN REVIEW (8-6)
 COMMENT #1 NOTADDRESSED. SINK TO COMPLY
 WITH FACBC-97 SECTION 4.24.
  
 2) PAGE P-2, SANITARY RISER DIAGRAM TO
 SHOW FLOOR SINK, NOT FUNNEL FLOOR DRAIN.
 FOR PAN DRAIN/RELIEF VALVE DISCHARGE.
  
 3) PAGE P-2, PLUMBING SPECIFICATIONS,
 #18, WATER HAMMER ARRESTORS SHALL COMPLY
 WITH MANUFACTURE'S INSTALLATION INSTRUC-
 TIONS FOR SIZE AND LOCATION. ALSO PER
 WH-PDI 201.
  
 REVIEW BY KEN STEVENS
 (561) 650-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By jleech Date 2001-08-06 Time 16:49 Rev Time 1.50
Received By jleech Date 2001-08-06 Time 16:48 Sent To  
Notes
2001-08-06 00:00:00DENIED;
  
 1.PAGE A-4 LOUNGE ROOM #112. SHALL MEET
 FACBC REQUIREMENTS SEC. 4.24 THRU
 4.24.7.
  
 2.EXTEND RELIEF AND PAN DRAIN TO THE
 OUTSIDE OR INTO A FLOOR SINK WITH A
 TRAP PRIMER SEC. 507.8.4.
  
 3.WATER HEATER DETAIL (NOTE) 2" HIGH
 DRAIN PAN PROVIDE (1") DRAIN NOT 3/4".
  
  
 4.PAGE P-2 (WATERRISER) PLEASE SIZE
 ALL PIPES TO WATER HEATER.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-08 Cont ID  
Sent By pkrauss Date 2001-08-08 Time 16:18 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***