Plan Review Details - Permit 01070987
Plan Review Stops For Permit 01070987
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-08 Cont ID  
Sent By hpiskura Date 2001-08-08 Time 07:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-06 Cont ID  
Sent By btrobaug Date 2002-02-06 Time 15:09 Rev Time 0.00
Received By btrobaug Date 2002-02-06 Time 14:48 Sent To  
Notes
2002-02-06 00:00:00SUBMITTAL STATING ABOVE CEILING XFMR WAS
 45KVA NOT 50KVA AS PER PLANS.FILED SAME
 IN 01070987 OPEN FILE.
 WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 20:06 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 08:15 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-03 Cont ID  
Sent By mcarsill Date 2001-08-03 Time 08:01 Rev Time 0.00
Received By mcarsill Date 2001-08-03 Time 08:01 Sent To  
Notes
2001-08-03 00:00:001) ALL C RATED FIRE DOOORS TO BE
 EQUIPPED WITH SELF-CLOSING DEVICES.
 2) NO INTERIOR FINISH INFORMATION
 ON PLANS. INTERIOR FINISH SHALL BE AT
 LEAST CLASS C ON THE WALLS AND CEILINGS.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-28 Time 14:08 Rev Time 0.35
Received By pkrauss Date 2001-08-28 Time 14:06 Sent To  
Notes
2001-08-28 00:00:00REVISIONS ON PREVIOUS PLAN REVIEW
 ADDRESSED.APPROVED
 DISREGARD THIS REVIEW STOP.
  
  
  
 `

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 07:19 Rev Time 0.45
Received By pkrauss Date 2001-08-09 Time 07:15 Sent To  
Notes
2001-08-09 00:00:00*******************PROVISO**************
  
  
 PLEASE CLARIFY HP-1, EXAM ROOM #4 (P123)
 INDICATES A 24" X 24" SUPPLY GRILL
 COMING OFF THE RETURN LINE.IS IT
 INTENDED FOR A RETURN OR SUPPLY?THE
 CFM LISTED ON THE SCHEDULE FOR HP-1 IS
 2200, YOU ONLY HAVE 1675 CFM WITHOUT
 COUNTING THE DROP IN QUESTION.IF YOU
 INCLUDE THE DROP IN QUESTION IT WILL
 BRING THE TOTAL CFM WILL BE BROUGHT UP
 TO 1875 CFM.
  
 NOTE:FAN SHUTDOWN WITH NOTIFICATION TO
 ALARM/STROBE OR BUILDING FIRE
 ALARM SYSTEM IN SYSTEMS GREATER
 THAN 2,000 CFM OR SERVING IN AN
 AREA OF EGRESS.(1997 SMC 406.1
 AND NFPA 90A 4-4.4.3 & 4-4.4.3.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-01-10 Cont ID  
Sent By kstevens Date 2002-01-10 Time 19:43 Rev Time 0.50
Received By kstevens Date 2002-01-10 Time 19:43 Sent To  
Notes
2002-01-10 00:00:00REVISION OK - FLOOR SINKS - WATER HAMMER
 ARRESTORS

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-09-06 Cont ID  
Sent By kstevens Date 2001-09-06 Time 13:47 Rev Time 1.25
Received By kstevens Date 2001-09-06 Time 13:47 Sent To  
Notes
2001-09-06 00:00:00PASSED/PROVISO
  
 1) N-36 VACUUM BREAKER INSTALLED 6"
 ABOVE FLOOD RIM LEVEL REQUIRED FOR
 SUPPLY LINE TO (PRE FILTERS IF USED, OR
 MILLIPORE UNIT.
 2) ALL INDIRECT WASTE SHALL DRAIN TO
 A FLOOR SINK NOT FLOOR DRAIN, NOTE #1
 IN LABORATORY. SPC-94 SEC. 804.1/804.5.
 3) AIR HAMMER ARRESTORS SHALL BE INSTALL
 ED PER MANUFACTURE'S INTSTALLATION IN-
 STRUCTIONS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-08-24 Cont ID  
Sent By kstevens Date 2001-08-24 Time 17:49 Rev Time 0.00
Received By kstevens Date 2001-08-24 Time 17:49 Sent To  
Notes
2001-08-24 00:00:00DENIED
  
 PLEASE SUBMIT INFORMATION ON ITEMS #4 &
 #5 ON EQUIPMENT LIST PAGE 1-A. IF UNABLE
 TO PRODUCE MANUFACTURE SPECS., THEN A
 BACKFLOW WILL BE REQUIRED TO BE INSTALL-
 ED IN THE LINES SERVING THESE PIECES OF
 EQUIPMENT. ALSO FLOOR SINKS WILL HAVE TO
 BE PROVIDED AND DRAIN LINES FROM BACK-
 FLOWS TO FLOOR SINKS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By jleech Date 2001-08-02 Time 18:35 Rev Time 2.00
Received By jleech Date 2001-08-02 Time 18:34 Sent To  
Notes
2001-08-02 00:00:00DENIED;
  
 1.PAGE P-1 FLOOR SINKS ARE REQUIRED
 WHERE BACKFLOW PREVENTORS ARE
 INSTALLED AND MUST BE PRIMED.
 2.BACKFLOW TO BE READILY ACCESSIBLE
 MOUNTED NO HIGHER THAN 4' OFF FLOOR.
 SHOW DETAIL OF INSTALLATION AND
 SPECIFY MODEL NUMBER AND SIZE.
 3.PAGE P-3 WATER HEATER DETAIL FLOOR
 DRAIN SHALL BE FLOOR SINK.
 4.DRAIN FROM HEATER PAN SHALL BE 1" SPC
 SEC. 507.7.8.2.
 5.WATER HAMMER ARRESTORS TO BE INSTALLED
 PER MANUFACTORS SPECIFICATIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 08:15 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***