| Plan Review Stops For Permit 01070987 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-08 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-06 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-02-06 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2002-02-06 00:00:00 | SUBMITTAL STATING ABOVE CEILING XFMR WAS | | | 45KVA NOT 50KVA AS PER PLANS.FILED SAME | | | IN 01070987 OPEN FILE. | | | WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-07 |
Time |
20:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-07 |
Time |
20:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
08:15 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-03 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-03 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2001-08-03 00:00:00 | 1) ALL C RATED FIRE DOOORS TO BE | | | EQUIPPED WITH SELF-CLOSING DEVICES. | | | 2) NO INTERIOR FINISH INFORMATION | | | ON PLANS. INTERIOR FINISH SHALL BE AT | | | LEAST CLASS C ON THE WALLS AND CEILINGS. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-28 |
Time |
14:08 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-08-28 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | REVISIONS ON PREVIOUS PLAN REVIEW | | | ADDRESSED.APPROVED | | | DISREGARD THIS REVIEW STOP. | | | | | | | | | | | | ` |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
07:19 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-08-09 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2001-08-09 00:00:00 | *******************PROVISO************** | | | | | | | | | PLEASE CLARIFY HP-1, EXAM ROOM #4 (P123) | | | INDICATES A 24" X 24" SUPPLY GRILL | | | COMING OFF THE RETURN LINE.IS IT | | | INTENDED FOR A RETURN OR SUPPLY?THE | | | CFM LISTED ON THE SCHEDULE FOR HP-1 IS | | | 2200, YOU ONLY HAVE 1675 CFM WITHOUT | | | COUNTING THE DROP IN QUESTION.IF YOU | | | INCLUDE THE DROP IN QUESTION IT WILL | | | BRING THE TOTAL CFM WILL BE BROUGHT UP | | | TO 1875 CFM. | | | | | | NOTE:FAN SHUTDOWN WITH NOTIFICATION TO | | | ALARM/STROBE OR BUILDING FIRE | | | ALARM SYSTEM IN SYSTEMS GREATER | | | THAN 2,000 CFM OR SERVING IN AN | | | AREA OF EGRESS.(1997 SMC 406.1 | | | AND NFPA 90A 4-4.4.3 & 4-4.4.3. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-10 |
Time |
19:43 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-01-10 |
Time |
19:43 |
Sent To |
|
|
| Notes |
| 2002-01-10 00:00:00 | REVISION OK - FLOOR SINKS - WATER HAMMER | | | ARRESTORS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-06 |
Time |
13:47 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-09-06 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2001-09-06 00:00:00 | PASSED/PROVISO | | | | | | 1) N-36 VACUUM BREAKER INSTALLED 6" | | | ABOVE FLOOD RIM LEVEL REQUIRED FOR | | | SUPPLY LINE TO (PRE FILTERS IF USED, OR | | | MILLIPORE UNIT. | | | 2) ALL INDIRECT WASTE SHALL DRAIN TO | | | A FLOOR SINK NOT FLOOR DRAIN, NOTE #1 | | | IN LABORATORY. SPC-94 SEC. 804.1/804.5. | | | 3) AIR HAMMER ARRESTORS SHALL BE INSTALL | | | ED PER MANUFACTURE'S INTSTALLATION IN- | | | STRUCTIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-08-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-24 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-24 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2001-08-24 00:00:00 | DENIED | | | | | | PLEASE SUBMIT INFORMATION ON ITEMS #4 & | | | #5 ON EQUIPMENT LIST PAGE 1-A. IF UNABLE | | | TO PRODUCE MANUFACTURE SPECS., THEN A | | | BACKFLOW WILL BE REQUIRED TO BE INSTALL- | | | ED IN THE LINES SERVING THESE PIECES OF | | | EQUIPMENT. ALSO FLOOR SINKS WILL HAVE TO | | | BE PROVIDED AND DRAIN LINES FROM BACK- | | | FLOWS TO FLOOR SINKS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-02 |
Time |
18:35 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-08-02 |
Time |
18:34 |
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | DENIED; | | | | | | 1.PAGE P-1 FLOOR SINKS ARE REQUIRED | | | WHERE BACKFLOW PREVENTORS ARE | | | INSTALLED AND MUST BE PRIMED. | | | 2.BACKFLOW TO BE READILY ACCESSIBLE | | | MOUNTED NO HIGHER THAN 4' OFF FLOOR. | | | SHOW DETAIL OF INSTALLATION AND | | | SPECIFY MODEL NUMBER AND SIZE. | | | 3.PAGE P-3 WATER HEATER DETAIL FLOOR | | | DRAIN SHALL BE FLOOR SINK. | | | 4.DRAIN FROM HEATER PAN SHALL BE 1" SPC | | | SEC. 507.7.8.2. | | | 5.WATER HAMMER ARRESTORS TO BE INSTALLED | | | PER MANUFACTORS SPECIFICATIONS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
08:15 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|