Plan Review Details - Permit 01070966
Plan Review Stops For Permit 01070966
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-07 Cont ID  
Sent By hpiskura Date 2001-08-07 Time 14:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 22:40 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 22:37 Sent To  
Notes
2001-08-07 00:00:00************* HOLD ****************
  
 1)NOTE: PLEASE NOTE THAT DUE TO COMMENTS
 FROM FIRE PLAN REVIEW. IT SEEMS THAT
 THERE WILL BE SOME ELECTRICAL CHANGES
 MADE TO THE ELECTRICAL DRAWINGS.
 ELECTRICAL WILL BE REVIEWED AND STAMPED
 AT TIME OF FIRE SIGN OFF.
  
 PLEASE RE-SUBMIT FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-14 Cont ID  
Sent By lsmith Date 2001-08-14 Time 07:03 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-10 Cont ID  
Sent By hpiskura Date 2001-09-10 Time 08:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 18:59 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 18:59 Sent To  
Notes
2001-08-02 00:00:001) OCCUPANT LOAD TO BE DETERMINED BY
 THE FIRE PREVENTION BUREAU.
 2) THERE ARE APPROXIMATELY 130 SEATS
 SHOWN ON THE DRAWINGS.
 3) PANIC HARDWARE REQUIRED ON ALL
 REQUIRED EXIT DOORS.
 4) ITEM 8 NOTED ON THE PLANS INDICATES
 A "SKYFOLD" MOTORIZED PARTITION WALL.
 IT APPEARS THAT WHEN THIS ITEM IS
 POSITIONED IT CUTS THE AREAS IN HALF.
 ACCORDING TO THE ELECTRICAL PLANS,
 PROPER NUMBER OF EXITS ARE NOT PRESENT
 WHEN THESE DEVICES ARE IN PLACE.
 PLEASE PROVIDE FLAMESPREAD ON THESE
 ITEMS.
 5) TWO EXITS PER AREA ARE NEEDED SINCE
 THIS SKYFOLD DEVICE LIMITS ACCESS TO
 EXITS ALREADY IDENTIFIED ON THE PLANS.
 6) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 7) PLEASE IDENTIFY AISLE LOCATIONS.
 8) EXITS SHOULD BE REMOTE AS POSSIBLE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-15 Cont ID  
Sent By pkrauss Date 2001-08-15 Time 14:11 Rev Time 0.50
Received By pkrauss Date 2001-08-15 Time 13:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-08-14 Cont ID  
Sent By lsmith Date 2001-08-14 Time 07:04 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-14 Cont ID  
Sent By lsmith Date 2001-08-14 Time 07:02 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***