Plan Review Details - Permit 01070805
Plan Review Stops For Permit 01070805
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-08-27 Cont ID  
Sent By dpalmer Date 2001-08-27 Time 18:24 Rev Time 0.00
Received By dpalmer Date 2001-08-27 Time 18:24 Sent To  
Notes
2001-08-27 00:00:00************* PLEASE NOTE *************
  
 1)NOTE: PLEASE NOTE THAT NO ELECTRICAL
 WAS SHOWN ON PLANS. PLEASE NOTE THAT IF
 PORCH IS TO BE CLOSED IN THEN OUTLETS
 AND LIGHT IS REQ`D BY CODE(NEC)..

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 20:31 Sent To  
Notes
2001-08-02 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS AND
 PERMIT APPLICATION DO NOT MATCH>
 PLANS SHOW OPEN PORCH AND CLOSED PORCH??
 AND APPLICATION SAYS FAMILT ROOM??
 PLEASE NOTE THAT IF THIS ROOM IS CLOSED
 IN OR FAMILY ROOM, THEN IT MUST CONTAIN
 ELECTRICAL OUTLETS AND LIGHTING IN ROOM.
  
  
 PLEASE SUBMIT CALRIFICATION ON PLANS AND
 /OR APPLICATION. PLEASE RESUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 20:35 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 20:35 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-28 Cont ID  
Sent By jgomez Date 2001-08-28 Time 10:24 Rev Time 1.50
Received By jgomez Date 2001-08-28 Time 10:24 Sent To  
Notes
2001-08-28 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE TWO COPIES OF PRODUCT APPROVAL
 FOR FLAT ROOF SYSTEM TO BE USED.
 NOTE: ONLY NEED THE PAGES THAT APPLY
 TO THE SPECIFIC INSTALLATION FOR THIS
 PROJECT.(INCLUDE THE LIMITATIONS
 SHEET)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-31 Cont ID  
Sent By jgomez Date 2001-07-31 Time 17:55 Rev Time 2.00
Received By jgomez Date 2001-07-31 Time 17:31 Sent To  
Notes
2001-07-31 00:00:00CHECKLIST:
 1-OPEN STRUCTURE NEEDS TO BE DESIGNED
 USING SECTION 308 OF SSTD 10-97, WHICH
 IS THE PRESCRIPTIVE STANDARD ADOPTED
 WHEN THE DESIGNER IS NOT A REGISTERED
 ARCHITECT OR ENGINEER. SEC. 104.2.3 OF
 CITY AMENDMENTS TO SBC 1997.
 2-CLARIFY IF EXISTING WINDOWS ARE GOING
 TO BE ENCLOSED OR NOT. SEE NOTES ON
 PLAN VIEW & ELECTRICAL LAYOUT. IF SO,
 WHAT'S GOING TO HAPPEN TO THE EXISTING
 BATH VENTILATION AND EXISTING BEDROOM
 EMERGENCY EGRESS.
 3-SPECIFY VENTILATION FOR FLAT ROOF AS
 REQUIRED BY SEC. 2309.7.2 SBC 1997.
 4-SEE PLANS FOR ADDITIONAL COMMENTS.
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 5-OWES $188.55 FOR LOW VALUATION
 DECLARED ON APPLICATION AND RADON FEES
 6-PROVIDE PRODUCT APPROVAL FOR:
 -FLAT ROOF SYSTEM.
 -DOORS AND WINDOWS IF THEY ARE GOING
 TO BE REMOVED.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By sgraham Date 2001-07-17 Time 09:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***