Plan Review Details - Permit 01070604
Plan Review Stops For Permit 01070604
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 21:59 Rev Time 0.00
Received By dpalmer Date 2001-07-31 Time 21:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-07-28 Cont ID  
Sent By hmoser Date 2001-07-28 Time 11:26 Rev Time 0.33
Received By hmoser Date 2001-07-28 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-10 Cont ID  
Sent By kstevens Date 2001-08-10 Time 10:17 Rev Time 0.33
Received By kstevens Date 2001-08-10 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-28 Cont ID  
Sent By jleech Date 2001-07-28 Time 07:46 Rev Time 0.25
Received By jleech Date 2001-07-28 Time 07:46 Sent To  
Notes
2001-07-28 00:00:00DENIED;
 SUBMIT SANITARY RISER DIAGRAM SIZE ALL
 PIPE.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2002-01-14 Cont ID  
Sent By rmcdouga Date 2002-01-14 Time 09:58 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-01-14 00:00:00TRUSSES OK W/LETTER FROM ENGINEER

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-12-05 Cont ID  
Sent By rmcdouga Date 2001-12-05 Time 11:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-05 00:00:00TRUSSES
 DENIED
  
 1) LETTER FROM ENGINEER MUST HAVE THE
 EMBOSSED SEAL OF THE ENGINEER.
  
 2) CONNECTOR HETAL 20 (EMBEDDED ANCHOR)
 REQUIRES (20) 10D X 1 1/2" NAILS FOR
 UPLIFT CAPACITY OF 1890#. LETTER STATES
 (15) NAILS.
  
 3) THE INTERIOR BEARING OF SG2 IS AT
 JOINT #15 NOT #21. THE TRUSS WEBS VEE AT
 THIS POINT(SEE TRUSS DRAWING), WHICH
 WILL NOT PROVIDE ADEQUATE NAILING FOR
 MST136 STRAP. PLEASE ADVISE AS TO HOW
 THESE WILL ATTACH TO TRUSS.
  
 PLEASE MAKE CORRECTIONS TO LETTER AND
 RESUBMIT.
  
 SAME NOTES APPLY TO 01071616 AND
 01070611.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-10-30 Cont ID  
Sent By rmcdouga Date 2001-10-30 Time 09:08 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-30 00:00:00TRUSSES
 UNSAT
  
 1) FOR TRUSS S13 THE TRUSS DRAWINGS
 INDICATE AN UPLIFT OF 1600# AT JOINT 13.
 SHEET A-3 OF THE PLANS INDICATE AN HC10
 CONNECTOR RATED FOR 1325# OF UPLIFT.
  
 2) FOR TRUSS S14 THE TRUSS DRAWINGS
 INDICATE AN UPLIFT OF 1650# AT JOINT 13.
 SHEET A-3 OF THE PLANS INDICATE AN HC10
 CONNECTOR RATED FOR 1325# OF UPLIFT.
  
 3) FOR TRUSS SG2 THE TRUSS DRAWINGS
 INDICATE 1860# OF UPLIFT AT JOINT 21 AND
 THE PLANS INDICATE A HETAL-16 RATED FOR
 1365# OF UPLIFT.
 THE TRUSS DRAWINGS INDICATE 4200# UPLIFT
 AT JOINT 15 AND PLANS HAVE LSTA-24 RATED
 FOR 1295# OF UPLIFT.
  
 PLEASE REVIEW AND CORRECT.
  
 THESE COMMENTS APPLY TO THE TRUSSES FOR
 PERMIT NUMBERS 01070611, 01070616 AND
 01071305.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-10 Cont ID  
Sent By rmcdouga Date 2001-08-10 Time 17:40 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-08-04 Cont ID  
Sent By rmcdouga Date 2001-08-04 Time 08:42 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-08-04 00:00:00*************BUILDING UNSAT*************
  
 1) STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 2) THE PERCENTAGE OF WALL AREA ALLOWED
 AS OPENINGS PER THE 97 SBC TABLE 600 IS
 EXCEEDED AT REAR OF STRUCTURE. BASED ON
 THE DISTANCE TO THE PROPERTY LINE 40% OF
 THE WALL AREA IS ALLOWED AS OPENINGS.
  
 3) THE FOOTINGS FOR THE 10" COLUMNS AT
 THE ENTRY ARE DESIGNATED AS F-8 WHICH
 ARE MONOLITHIC PADS BUT APPEAR TO BE
 F-8A CONCRETE PADS. PLEASE REVIEW AND
 CORRECT.
  
 4) WALL SECTION ON SHEET A-2 SHOWS A
 FOOTER WITH A DEPTH OF 20" AND FOOTER
 SCHEDULE ON SHEET A-1 INDICATES AN 18"
 FOOTER DEPTH AT F-1. PLEASE REVISE SO
 THAT SHEETS ARE CONSISTENT.
  
 5) ADVISE TRUSS ENGINEER THAT A/C
 EQUIPMENT WILL BE SUPPORTED BY TRUSSES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-25 Cont ID  
Sent By sgraham Date 2001-07-25 Time 11:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***