Plan Review Details - Permit 01070556
Plan Review Stops For Permit 01070556
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-22 Cont ID  
Sent By dpalmer Date 2001-08-22 Time 09:25 Rev Time 0.00
Received By dpalmer Date 2001-08-22 Time 09:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-24 Cont ID  
Sent By lsmith Date 2001-07-24 Time 15:03 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-07-24 00:00:00NOTES FROM 7/16/01 STILL NOT ADDRESSED:
 COPY OF NOTES FROM 7/16/01 ATTACHED.
 REVIEWED BY PHIL PETTY 7/24/01

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-07-16 Cont ID  
Sent By dpalmer Date 2001-07-16 Time 13:44 Rev Time 0.00
Received By dpalmer Date 2001-07-16 Time 13:44 Sent To  
Notes
2001-07-16 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PERMIT
 APPLICATION WAS SUBMITTED FOR SERVICE
 CHANGE, BUT A PLANWAS SUBMITTED SHOW-
 -ING A HOUSE BEING WIRED?
 PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT IF HOUSE IS
 BEING WIRED, MISSING SD`S AND COND UNIT
 SHOWN FOR A/C. NFPA-72 2-2.1.1.1,440-11
  
 3)NOTE: PLEASE NOTE THAT SERVICE RISER
 DIAGRAM SHOWS SERVICE BEING 3-PHASE??
 NO WIRE SIZES SHOWN.
  
 4) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TOAND COLD WATER ALSO.
 PER 250-50.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372