Plan Review Details - Permit 01070546
Plan Review Stops For Permit 01070546
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-12 Cont ID  
Sent By dpalmer Date 2001-12-12 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2001-12-12 Time 12:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-05 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2001-12-05 Time 19:32 Sent To P
Notes
2001-12-05 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE CLARIFY PLANS, POOL PANEL
 IS SHOWN COMING FROM METER. IS THIS A
 METER/MAIN COMBO, LIKE SHOWN ON PLANS?
  
 2)NOTE: PLEASE SHOW LOCATION OF POOL
 PANEL. PLEASE NOTE IF POOL PANEL HAS THE
 SECOND MEANS OF DISC AND IS COMING
 DIRECTLY FROM METER, THEN MAINS ARE
 REQ`D TO BE GROUPED. 230-72
  
 3)NOTE:PLEASE CLARFI IF POOL PANEL IS
 BEING FED FROM METER/MAIN?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-22 Cont ID  
Sent By dpalmer Date 2001-07-22 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2001-07-22 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-07-19 Cont ID  
Sent By hmoser Date 2001-07-19 Time 19:23 Rev Time 0.33
Received By hmoser Date 2001-07-19 Time 19:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.50
Received By kstevens Date 2001-12-08 Time 08:46 Sent To  
Notes
2001-12-08 00:00:00REVISED SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-07-18 Cont ID  
Sent By dpalmer Date 2001-12-05 Time 19:32 Rev Time 0.25
Received By jleech Date 2001-07-18 Time 16:58 Sent To  
Notes
2001-07-18 00:00:00PROVISO; REVISED SANITARY RISER REQUIRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-07-30 Cont ID  
Sent By lsmith Date 2001-07-30 Time 16:38 Rev Time 3.00
Received By lsmith Date   Time   Sent To  
Notes
2001-07-30 00:00:00************BUILDING PROVISO************
  
 1. PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 SBC 104.2.2
  
 2. PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUCTION WITH
 BFE BEFORE C/O.
  
 3. PROVIDE ENGINEERED TRUSS DRAWINGS
 WITH APPROVAL FROM ARCHITECT AND CORRECT
 MEAN ROOF HEIGHT NOTED ON SHEETS.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH: BLDG. PLANS EXAMINER
 659-8096 EXT 8394

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-18 Cont ID  
Sent By sgraham Date 2001-07-18 Time 08:32 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***