Plan Review Details - Permit 01070537
Plan Review Stops For Permit 01070537
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By hpiskura Date 2001-08-07 Time 13:07 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-07 00:00:00PLEASE PROVIDE SPECIFIC CONNECTION
 DETAILS IN ACCORDANCE WITH GOOD
 ENGINEERING PRACTICE.SHOW THE ROOF
 COVERING CONNECTION AND ALL WELD
 DETAILS.
  
 PROVIDE AN ANALYSIS OF THE ROOF BEAMS
 AND COLUMNS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 20:58 Sent To  
Notes
2001-08-07 00:00:00*************** UNSAT ****************
  
 1)NOTE: NEED TO SUBMIT ELECTRICAL DETAIL
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 13:31 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 13:31 Sent To  
Notes
2001-08-06 00:00:001) THE BUILDING APPEARS TO BE LOCATED
 WITHIN THE CITY FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY WITHIN THE LIMITS
 WITH REGARDS TO CONSTRUCTION MATERIALS.
 PLEASE SEE APPENDIX F OF THE STANDARD
 BUILDING CODE.
 2) PLEASE PROVIDE MORE DETAILS ON VENT
 STACK.
 3) DISTANCES FROM COMBUSTIBLES ARE TO
 NOTED ON THE PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-10 Cont ID  
Sent By pkrauss Date 2001-08-10 Time 08:42 Rev Time 0.30
Received By pkrauss Date 2001-08-10 Time 08:42 Sent To  
Notes
2001-08-10 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.MAKE AND MODEL OF EXHAUST FANS.
  
 2.PLEASE INDICATE WHAT "B.B.Q." IS
 MADE OF.IS IT OPEN OR HAVE A LID?
 IS MADE OF BRICK, STEEL?
  
 3.PLEASE INDICATE CLEARANCES TO
 COMBUSTIBLES.
  
 4.WHAT TYPE OF FUEL BURNING WILL BE
 USED, WOOD, CHARCOAL, OR GAS?
  
 5.DOES THE COOKER COME WITH A FLUE?
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-12 Cont ID  
Sent By sgraham Date 2001-07-12 Time 08:42 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***