Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-01-28 Cont ID  
Sent By hpiskura Date 2002-01-28 Time 09:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-01-08 Cont ID  
Sent By hpiskura Date 2002-01-07 Time 09:23 Rev Time 0.00
Received By hpiskura Date 2002-01-07 Time 09:09 Sent To  
Notes
2002-01-07 00:00:00SAME CODE CONFLICT EXISTS.
 ARCHITECTURAL TITLE PAGE CITES 1997 SBC
 1606 AND 110 MPH.STRUCTURAL PLANS
 CALL OUT ASCE 7-95.MISING OF
 WINDLOADS FROM DIFFERENT SOURCES IS
 PROHIBITTED BY SBC 1606.1.2.1THERE IS
 ALSO A CONFLICTING STATEMENT RE: ROOF
 LIVE LOADS.40 VS 30.
  
 SOME OF THE PRODUCT REPORTS HAVE EXPIRED
  
  
 ON MARCH 1, 2002 THE FLORIDA BUILDING
 CODE WILL BE IN EFFECT AND PERMIT
 APPLICATIONS RECEIVED SUBSEQUENT TO
 THAT DATE WILL BE REVIEWED AND
 PERMITTED TO THAT CODE.THIS SERIES OF
 REVIEWS ARE JUST THAT REVIEWS, A PERMIT
 APPLICATION HAS NOT BEEN RECEIVED FOR
 THIS PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-02 Cont ID  
Sent By hpiskura Date 2001-10-02 Time 14:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-02 00:00:00SHEET ST2 CITES ASCE 7-93 AND 110 MPH.
 SBC 1997 INVOKES ASCE7-95 AND WEST PALM
 BEACH IS IN THE 140 MPH WIND REGION.
  
 REVIEW SBC 1606 AND CHOOSE ONE METHOD OF
 WIND DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By hpiskura Date 2001-08-06 Time 07:34 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-06 00:00:00COVER SHEET DECLARES STRUCTURAL TO BE
 SBC CHAPTER 16 110 MPH WIND VELOCITY
 AND 2000 PSF SOIL BEARING CAPACITY.
 SHEET ST2 CALLS ASCE 7-95 WITH 140 MPH
 AND 2500 PSF.SEE SBC 1606.1.2.1. AND
 REVISE AS NECESSARY.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 PROVIDE TEST REPORTS FOR THE ROOF,
 DOORSS AND WINDOWS.
  
 PROVIDE THE REINFORCED MASONRY
 SPECIFICATIONS CHECKLIST IN ACCORDANCE
 WITH ACI 530.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 23:01 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 23:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 20:13 Sent To  
Notes
2001-08-02 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT SHUNT TRIPS
 ARE NOT PERMITTED AS MAIN MEANS OF
 DISCONNECT. MANUAL MEANS MUST BE
 PRIMARYPER 230-76/230-79
  
 2)NOTE: PLEASE NOTE THAT "PP" SHOW 400A
 OCP FOR PANEL"K-1" WITH 3/0 CONDUCTORS
 AS FEED TO "K-1" 310-16
  
  
 PLEASE SUBMIT CLARIFICATION FOR THE
 ABOVE INFORMATION. PLEASE SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2002-04-30 Cont ID  
Sent By mamini Date 2002-04-30 Time 08:39 Rev Time 1.00
Received By mamini Date 2002-04-30 Time 08:39 Sent To  
Notes
2002-04-30 00:00:00PASSED:
 1. REVISION AS SUBMITTED TO RELOCATE THE
 FIRE HYDRANT, APPROVED.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-12-04 Cont ID  
Sent By mamini Date 2001-12-04 Time 08:41 Rev Time 2.00
Received By mamini Date 2001-12-04 Time 08:41 Sent To  
Notes
2001-12-04 00:00:00PASSED WITH PROVISOS :
 1. A SEPARATE PERMIT APPLICATION AND
 FEES FOR THE UNDERGROUND UTILITIES/ SITE
 WORKS IS REQUIRED PRIOR TO ANY EARTH
 WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-07-25 Cont ID  
Sent By mamini Date 2001-07-25 Time 09:41 Rev Time 4.00
Received By mamini Date 2001-07-25 Time 09:40 Sent To  
Notes
2001-07-25 00:00:00FAILED:
 1. PARKING STALLS SHOULD BE PAINTED WITH
 DOUBLE 4" WHITE LINES, PER CITY
 REQUIREMENT.
 2. PLEASE SHOW DETAILS FOR GREASE/ WATER
 SEPARATOR, SEE ATTACHED.
 3. CONTRACTOR MUST CALL RODNEY COMPO FOR
 INSPECTION/INSTALLATION OF GREASE/WATER
 SEPARATOR 873-4051 EXT. 4074
 4. LANDSCAPING, IRRIGATION, EROSION
 CONTROL PLANS DO NOT MATCH THE CIVIL
 PLANS, PLEASE REVISE.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8496 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-04-17 Cont ID  
Sent By mcarsill Date 2002-04-17 Time 13:12 Rev Time 0.00
Received By mcarsill Date 2002-04-17 Time 13:12 Sent To  
Notes
2002-04-17 00:00:00A) RELOCATED FIRE HYDRANT MUST BE
 PROVIDED WITH AT LEAST SEVEN FEET SIX
 INCH CLEARANCE TO THE FRONT AND SIDES
 OF IT. ALSO A MINIMUM OF AT LEAST FOUR
 FEET IS TO BE PROVIDED TO THE REAR OF
 IT.
 B) FIRE HYDRANT VALVE IS TO BE NO
 FARTHER THAN FOUR FEET FROM THE FIRE
 HYDRANT.
 C) RELOCATED FIRE HYDRANT IS TO MEET
 CITY UTILITY AND FIRE RESCUE STANDARDS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-12-27 Cont ID  
Sent By mcarsill Date 2001-12-27 Time 09:00 Rev Time 0.00
Received By mcarsill Date 2001-12-27 Time 09:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-26 Cont ID  
Sent By mcarsill Date 2001-09-26 Time 12:30 Rev Time 0.00
Received By mcarsill Date 2001-09-26 Time 12:30 Sent To  
Notes
2001-09-26 00:00:001) BUILDING ADDRESS NOTE ON PAGE A-1
 IS INCORRECT. CITY CODE 3343-00
 REQUIRES ADDRESSES ON BUILDINGS TO BE
 AT LEAST 6" HIGH, 3" WIDE ON A
 CONTRASTING BACKGROUND VISIBLE DAY AND
 NIGHT.
 2) AWNINGS IF CANVAS AND PERSONS ARE
 EXPECTED TO TRAVEL UNDERNEATH THEM ARE
 TO BE FIRE RETARDANT.
 3) EXHAUST FAN LOCATIONS FOR KITCHEN
 EQUIPMENT ARE TO BE LOCATED A MINIMUM
 OF AT LEAST 10 FEET FROM ANY AIR
 INTAKES.
 4) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SINCE SEATING AREA HOLDS 99
 PERSONS WITH STAFF WILL BE OVER 100
 PERSONS.
 5) PROVIDE BOLLARD PROTECTION FOR
 GAS METER.
 6) PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHTING EQUIPMENT IN DINING ROOM.
 ADDITIONAL EXIT SIGNS ARE REQUIRED
 ABOVE EXIT DOORS THAT ARE NOT
 PREVENTLY MARKED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-07-13 Cont ID  
Sent By rturnque Date 2001-07-13 Time 10:30 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
2001-07-13 00:00:00HOOD AND EXTINGUISHING SYSTEM
 INSTALLATION SHALL BE IN ACCORDANCE WITH
 NFPA 96.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-01-02 Cont ID  
Sent By pkrauss Date 2002-01-02 Time 16:21 Rev Time 0.45
Received By pkrauss Date 2002-01-02 Time 16:21 Sent To  
Notes
2002-01-02 00:00:00******************PROVISO***************
  
 CONDENSER UNIT STANDS SHALL HAVE A
 MINIMUM OF 18" BETWEEN THE ROOF SURFACE
 AND THE BOTTOM OF THE SUPPORT RAIL.
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE
 PLANS AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 EXHAUST OUTLETS FOR DUCTS
 CONVEYING NOXIOUS GASES,FLAMMABLE
 OR CORROSIVE VAPORS AND DUCTS
 SERVING COMMERCIAL FOOD COOKING
 & PROCESSING EQUIPMENT, SHALL
 TERMINATE OUTSIDE OF THE BUILDING
 & SHALL BE LOCATED 10 FT. FROM
 ANY ADJACENT BUILDING, PARKING
 AREA, ADJACENT PROPERTY LINE,
 DOOR, WINDOW, OR AIR INTAKE.
 1997 SMC 506.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-12-20 Cont ID  
Sent By pkrauss Date 2001-12-20 Time 13:17 Rev Time 0.40
Received By pkrauss Date 2001-12-20 Time 13:08 Sent To  
Notes
2001-12-20 00:00:00********************DENIED**************
  
 AS PER COUNTYWIDE AMENDMENTS TO THE 1994
 SPC 804.3, AIR CONDITIONING UNITS
 GREATER THAN 3 TON, CONDENSATE SHALL
 TERMINATE INTO AN APPROVED DRYWELL OR
 TO THE STORM DRAINAGE SYSTEM.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-1989.(2ND REQUEST)
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS AND
 FREEZERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-08 Cont ID  
Sent By pkrauss Date 2001-10-08 Time 11:53 Rev Time 0.50
Received By pkrauss Date 2001-10-08 Time 11:49 Sent To  
Notes
2001-10-08 00:00:00******************DENIED****************
  
  
 1.DUCT PENETRATING A FIRE RATED WALL
 IN THE FOOD PREP AREA, INDICATES THE
 DUCT PENETRATING THE WALL ON AN
 ANGLE.FIRE DAMPER CANNOT BE
 INSTALLED IN DUCTWORK AT THIS ANGLE.
 DUCTWORK SHALL RUN PERPENDICULAR TO
 THE WALL FOR PROPER INSTALLATION OF
 THE FIRE DAMPER.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER ASHRAE 62-89.
  
 3.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 4.CONDENSER UNIT STAND DOES NOT
 INDICATE HEIGHT REQUIRMENT. 18"
 MINIMUM FROM ROOF SURFACE TO THE
 BOTTOM OF THE SUPPORT RAIL.
  
 5.PROVIDE EQUIPMENT SCHEUDLE.
  
 6.ENERGY CALCULATIONS AS PER FLORIDA
 ENERGY CODE 101.1.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By pkrauss Date 2001-08-02 Time 12:43 Rev Time 1.20
Received By pkrauss Date 2001-08-02 Time 11:03 Sent To  
Notes
2001-08-02 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.FIRE DAMPER INSTALLATION DETAIL,
 SHALL COMPLY WITH UL 555 AND BEAR
 THE LABLE OF AN APPROVED TESTING
 AGENCY.
  
 2.FAN SHUTDOWN REQUIRED WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS, AS PER
 1997 SMC 406.1 AND NFPA 96 4-4.4.3.
 PLEASE INDICATE ALARM/STROBE AND
 DUCT SMOKE DETECTORS ON PLAN.
  
 3.PLEASE INDICATE CONDENSATE DRAIN
 LINES ON PLAN AS WELL AS SUPPORT FOR
 PIPING.CONDENSATE SHALL COMPLY
 WITH 1997 SMC 304.8.3, UNITS LARGER
 THAN 3 TONS SHALL DRAIN TO STORM
 DRAIN OR AN APPROVED DRYWELL.
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION, AND WALK
 IN COOLERS.PLEASE PROVIDE PLANS
 WITH AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 CONDENSER UNIT STANDS SHALL BE
 A MINIMUM OF 18" ABOVE THE ROOF
 SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL. (AMENDED 1997 SMC
 304.2.5)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-08 Cont ID  
Sent By kstevens Date 2002-01-08 Time 10:27 Rev Time 1.25
Received By kstevens Date 2002-01-08 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-10 Cont ID  
Sent By kstevens Date 2001-10-10 Time 19:26 Rev Time 2.50
Received By kstevens Date 2001-10-10 Time 19:26 Sent To  
Notes
2001-10-10 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) SHT A-1 DEPT OF HOTEL BUSINESS REG-
 ULATION, PLAN REVIEW W/COMMENTS REQUIRED
 BEFORE PLUMBING PLAN REVIEW. FROM PREV-
 IOUS REVIEW, COMMENT RESPONSE ACKNOWLED-
 GED.
 2) SHT C-1, IR-6, P-1, DETAIL(6), GREASE
 TANK, COMMENT FROM PREVIOUS PLAN REVIEW,
 NEED LETTER FROM R. COMPO FOR PLAN RE-
 VIEW. COMMENT RESPONSE ACKNOWLEDGED.
 3) C-4, SITE WORK, TO COMPLY WITH CITY
 OF WPB UTILITY STANDARDS. BACK FLOW PRE-
 VENTERS REQD ON IRRIGATION AND FIRE.
 PLEASE SHOW ON PLANS. COMMENT RESPONSE
 ACKNOWLEDGED. SHOW TYPE AND LOCATION.
 4) GAS PERMIT APPLICATION REQUIREMENTS
 STILL REQUIRED. PLEASE SUBMIT AN ISO-
 METRIC THAT CLEARLY SHOWS "ALL CUT SECT-
 IONS AND CORRESPONDING LENGTHS". PLEASE
 SHOW TYPE OF GAS (NATURAL OR LP).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-29 Cont ID  
Sent By pschmitz Date 2001-07-29 Time 10:01 Rev Time 3.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-29 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCES,SPC-94,SGC-97,FACBC-97.
 (1)SHT A-1 DEPT.OF HOTEL BUSINESS
 REGULATION, PLAN REVIEW W/ COMMENTS
 REQUIRED, BEFORE PLUMBING PLAN REVIEW.
 CONTACT
 954 -958-5520.
 (2)SHT C-1,IR-6, P-1, DETAIL(6), GREASE
 TANK, CONTACT W PALM BCH ENVIRONMENTAL
 COMPLIANCE, RODNEY COMPO FOR SIZE,
 561- 837- 4074.
 (3)C-4,SITE WORK,TO COMPLY WITH CITY OF
 WEST PALM BCH. UTILITY STDS, BACK FLOW
 PREVENTERS REQ. ON DOMESTIC,IRRIGATION
 AND FIRE WATER SUPPLY, ORD# 2853-95.
 SHOW TYPE AND LOCATION.
 (4)SHT A-11,NO ELV.DETAIL FOR THE URINAL
 SEC 4.18.2 HIGHT 17" AFF.
 SEC 4.18.3 CLEAR FLR SPACE 30"X 48".
 (5)SHT A-11 DETAIL(9),H/C SINK, COMPLY
 SEC 4.19.2, HEIGHT & CLEARANCE,NO
 HIGHERTHAN 34" AFF.
 (6)SHT A-11 DETAIL(9) H/C WATER CLOSET,
 SEC 4.17.3,SIZE & ARRANGMENT,FIG 30(E).
 DIMENSION OFF THE SIDE WALL 18"
 ABSOLUTE(7A) SHT P-1,PLBG PLAN NOTES
 #(4) A/C
 CONDENSATE DRAINS, COMPLY WITH MCWA-94
 SEC 804. COMMON SYTEM TO STORM, CONNECT
 OUTSIDE OF BLDG, WITH A RELIEF VENT.
 (7B) ANY REFERENCE TO KITCHEN EQUIPMENT
 CONTRACTOR,INSTALLING DRAINS. ALL
 PIPINGTO BE INSTALLED BY A LICENSED
 PLUMBING
 CONTRACTOR.
 (8) SHT P-1 NOTES #6 TO #25 COMPLY WITH
 MCWA-94 SEC 607.7, NO MORE THAN 2 PLBG.
 FIXTURES ON 1/2" C/W,NO MORE THAN 4
 PLBGFIXTURES ON 1/2" H/W.
 (9) SHT P-1 NOTE #14 REFERENCE TO OHD,
 OTHER REFERENCES TO ID, FUNNEL DRAINS
 ORSAFE WASTE (ID). SEC 802.
 ALL INDIRECT WASTE TO FLR SINKS.
  
 (10) SHT P-1 NOTE #19 COMPLY W ITH SEC
 607.8.3,REFERENCE TO AIR CHAMBERS IN
 CEILINGS AND WALLS. NOT APPROVED.
 USE STD PDI-WH102,INSTALLATION OF WATER
 HAMMER ARRESTORS,COMPLY WITH MANFACTURE
 INSTRUCTIONS FOR SIZE & PLACEMENT.
 (11) SHT P-2 NO DETAIL# GAS ISOMETRIC,
 SEE ATTACHED GAS PERMIT APPLICATION RE-
 QUIRMENTS. ADDRESS EACH OF (6) ITEMS.
 (12) SHT P-2 DETAIL#(9) IRRIATION BACK
 FLOW PREVENTER TYPE (RPZV).
 (13) SHT P-2 KITCHEN DWV ISOMETRIC AND
 SHT P-3 NOTE #7,DISH WASHER TO SANITARY
 SEWER,LOCAL ORDINANCE # 2938-96.
 END OF COMMENTS, PAUL SCHMITZ
 3QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 2 Status P Date 2002-01-23 Cont ID  
Sent By sgraham Date 2002-01-23 Time 11:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-07-12 Cont ID  
Sent By sgraham Date 2001-07-12 Time 10:44 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-07-12 00:00:00SENT TO BLDG FOR REVIEW