| Plan Review Stops For Permit 01070522 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-01-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-28 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-01-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-07 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-01-07 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | SAME CODE CONFLICT EXISTS. | | | ARCHITECTURAL TITLE PAGE CITES 1997 SBC | | | 1606 AND 110 MPH.STRUCTURAL PLANS | | | CALL OUT ASCE 7-95.MISING OF | | | WINDLOADS FROM DIFFERENT SOURCES IS | | | PROHIBITTED BY SBC 1606.1.2.1THERE IS | | | ALSO A CONFLICTING STATEMENT RE: ROOF | | | LIVE LOADS.40 VS 30. | | | | | | SOME OF THE PRODUCT REPORTS HAVE EXPIRED | | | | | | | | | ON MARCH 1, 2002 THE FLORIDA BUILDING | | | CODE WILL BE IN EFFECT AND PERMIT | | | APPLICATIONS RECEIVED SUBSEQUENT TO | | | THAT DATE WILL BE REVIEWED AND | | | PERMITTED TO THAT CODE.THIS SERIES OF | | | REVIEWS ARE JUST THAT REVIEWS, A PERMIT | | | APPLICATION HAS NOT BEEN RECEIVED FOR | | | THIS PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-02 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-02 00:00:00 | SHEET ST2 CITES ASCE 7-93 AND 110 MPH. | | | SBC 1997 INVOKES ASCE7-95 AND WEST PALM | | | BEACH IS IN THE 140 MPH WIND REGION. | | | | | | REVIEW SBC 1606 AND CHOOSE ONE METHOD OF | | | WIND DESIGN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-06 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-06 00:00:00 | COVER SHEET DECLARES STRUCTURAL TO BE | | | SBC CHAPTER 16 110 MPH WIND VELOCITY | | | AND 2000 PSF SOIL BEARING CAPACITY. | | | SHEET ST2 CALLS ASCE 7-95 WITH 140 MPH | | | AND 2500 PSF.SEE SBC 1606.1.2.1. AND | | | REVISE AS NECESSARY. | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.CALL 561-233-5025 FOR | | | MORE INFORMATION. | | | | | | PROVIDE TEST REPORTS FOR THE ROOF, | | | DOORSS AND WINDOWS. | | | | | | PROVIDE THE REINFORCED MASONRY | | | SPECIFICATIONS CHECKLIST IN ACCORDANCE | | | WITH ACI 530. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
23:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-01 |
Time |
23:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-02 |
Time |
20:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-02 |
Time |
20:13 |
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT SHUNT TRIPS | | | ARE NOT PERMITTED AS MAIN MEANS OF | | | DISCONNECT. MANUAL MEANS MUST BE | | | PRIMARYPER 230-76/230-79 | | | | | | 2)NOTE: PLEASE NOTE THAT "PP" SHOW 400A | | | OCP FOR PANEL"K-1" WITH 3/0 CONDUCTORS | | | AS FEED TO "K-1" 310-16 | | | | | | | | | PLEASE SUBMIT CLARIFICATION FOR THE | | | ABOVE INFORMATION. PLEASE SUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-04-30 |
Time |
08:39 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-04-30 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | PASSED: | | | 1. REVISION AS SUBMITTED TO RELOCATE THE | | | FIRE HYDRANT, APPROVED. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-12-04 |
Time |
08:41 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-12-04 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2001-12-04 00:00:00 | PASSED WITH PROVISOS : | | | 1. A SEPARATE PERMIT APPLICATION AND | | | FEES FOR THE UNDERGROUND UTILITIES/ SITE | | | WORKS IS REQUIRED PRIOR TO ANY EARTH | | | WORKS. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-07-25 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-25 |
Time |
09:41 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-07-25 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2001-07-25 00:00:00 | FAILED: | | | 1. PARKING STALLS SHOULD BE PAINTED WITH | | | DOUBLE 4" WHITE LINES, PER CITY | | | REQUIREMENT. | | | 2. PLEASE SHOW DETAILS FOR GREASE/ WATER | | | SEPARATOR, SEE ATTACHED. | | | 3. CONTRACTOR MUST CALL RODNEY COMPO FOR | | | INSPECTION/INSTALLATION OF GREASE/WATER | | | SEPARATOR 873-4051 EXT. 4074 | | | 4. LANDSCAPING, IRRIGATION, EROSION | | | CONTROL PLANS DO NOT MATCH THE CIVIL | | | PLANS, PLEASE REVISE. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8496 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-04-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-17 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-17 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2002-04-17 00:00:00 | A) RELOCATED FIRE HYDRANT MUST BE | | | PROVIDED WITH AT LEAST SEVEN FEET SIX | | | INCH CLEARANCE TO THE FRONT AND SIDES | | | OF IT. ALSO A MINIMUM OF AT LEAST FOUR | | | FEET IS TO BE PROVIDED TO THE REAR OF | | | IT. | | | B) FIRE HYDRANT VALVE IS TO BE NO | | | FARTHER THAN FOUR FEET FROM THE FIRE | | | HYDRANT. | | | C) RELOCATED FIRE HYDRANT IS TO MEET | | | CITY UTILITY AND FIRE RESCUE STANDARDS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-27 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-27 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-26 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-26 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | 1) BUILDING ADDRESS NOTE ON PAGE A-1 | | | IS INCORRECT. CITY CODE 3343-00 | | | REQUIRES ADDRESSES ON BUILDINGS TO BE | | | AT LEAST 6" HIGH, 3" WIDE ON A | | | CONTRASTING BACKGROUND VISIBLE DAY AND | | | NIGHT. | | | 2) AWNINGS IF CANVAS AND PERSONS ARE | | | EXPECTED TO TRAVEL UNDERNEATH THEM ARE | | | TO BE FIRE RETARDANT. | | | 3) EXHAUST FAN LOCATIONS FOR KITCHEN | | | EQUIPMENT ARE TO BE LOCATED A MINIMUM | | | OF AT LEAST 10 FEET FROM ANY AIR | | | INTAKES. | | | 4) PANIC HARDWARE REQUIRED ON ALL EXIT | | | DOORS SINCE SEATING AREA HOLDS 99 | | | PERSONS WITH STAFF WILL BE OVER 100 | | | PERSONS. | | | 5) PROVIDE BOLLARD PROTECTION FOR | | | GAS METER. | | | 6) PLEASE CLEARLY IDENTIFY EMERGENCY | | | LIGHTING EQUIPMENT IN DINING ROOM. | | | ADDITIONAL EXIT SIGNS ARE REQUIRED | | | ABOVE EXIT DOORS THAT ARE NOT | | | PREVENTLY MARKED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-07-13 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2001-07-13 |
Time |
10:30 |
Rev Time |
0.25 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-13 00:00:00 | HOOD AND EXTINGUISHING SYSTEM | | | INSTALLATION SHALL BE IN ACCORDANCE WITH | | | NFPA 96. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-02 |
Time |
16:21 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-01-02 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | ******************PROVISO*************** | | | | | | CONDENSER UNIT STANDS SHALL HAVE A | | | MINIMUM OF 18" BETWEEN THE ROOF SURFACE | | | AND THE BOTTOM OF THE SUPPORT RAIL. | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLERS/FREEZERS.PLEASE PROVIDE | | | PLANS AND MANUFACTURER SUBMITTAL | | | DATA WITH PERMIT APPLICATION. | | | | | | EXHAUST OUTLETS FOR DUCTS | | | CONVEYING NOXIOUS GASES,FLAMMABLE | | | OR CORROSIVE VAPORS AND DUCTS | | | SERVING COMMERCIAL FOOD COOKING | | | & PROCESSING EQUIPMENT, SHALL | | | TERMINATE OUTSIDE OF THE BUILDING | | | & SHALL BE LOCATED 10 FT. FROM | | | ANY ADJACENT BUILDING, PARKING | | | AREA, ADJACENT PROPERTY LINE, | | | DOOR, WINDOW, OR AIR INTAKE. | | | 1997 SMC 506.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-20 |
Time |
13:17 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-12-20 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | ********************DENIED************** | | | | | | AS PER COUNTYWIDE AMENDMENTS TO THE 1994 | | | SPC 804.3, AIR CONDITIONING UNITS | | | GREATER THAN 3 TON, CONDENSATE SHALL | | | TERMINATE INTO AN APPROVED DRYWELL OR | | | TO THE STORM DRAINAGE SYSTEM. | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-1989.(2ND REQUEST) | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION AND WALK-IN COOLERS AND | | | FREEZERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-08 |
Time |
11:53 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-10-08 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2001-10-08 00:00:00 | ******************DENIED**************** | | | | | | | | | 1.DUCT PENETRATING A FIRE RATED WALL | | | IN THE FOOD PREP AREA, INDICATES THE | | | DUCT PENETRATING THE WALL ON AN | | | ANGLE.FIRE DAMPER CANNOT BE | | | INSTALLED IN DUCTWORK AT THIS ANGLE. | | | DUCTWORK SHALL RUN PERPENDICULAR TO | | | THE WALL FOR PROPER INSTALLATION OF | | | THE FIRE DAMPER. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER ASHRAE 62-89. | | | | | | 3.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 4.CONDENSER UNIT STAND DOES NOT | | | INDICATE HEIGHT REQUIRMENT. 18" | | | MINIMUM FROM ROOF SURFACE TO THE | | | BOTTOM OF THE SUPPORT RAIL. | | | | | | 5.PROVIDE EQUIPMENT SCHEUDLE. | | | | | | 6.ENERGY CALCULATIONS AS PER FLORIDA | | | ENERGY CODE 101.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-02 |
Time |
12:43 |
Rev Time |
1.20 |
| Received By |
pkrauss |
Date |
2001-08-02 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.FIRE DAMPER INSTALLATION DETAIL, | | | SHALL COMPLY WITH UL 555 AND BEAR | | | THE LABLE OF AN APPROVED TESTING | | | AGENCY. | | | | | | 2.FAN SHUTDOWN REQUIRED WITH | | | NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS, AS PER | | | 1997 SMC 406.1 AND NFPA 96 4-4.4.3. | | | PLEASE INDICATE ALARM/STROBE AND | | | DUCT SMOKE DETECTORS ON PLAN. | | | | | | 3.PLEASE INDICATE CONDENSATE DRAIN | | | LINES ON PLAN AS WELL AS SUPPORT FOR | | | PIPING.CONDENSATE SHALL COMPLY | | | WITH 1997 SMC 304.8.3, UNITS LARGER | | | THAN 3 TONS SHALL DRAIN TO STORM | | | DRAIN OR AN APPROVED DRYWELL. | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION, AND WALK | | | IN COOLERS.PLEASE PROVIDE PLANS | | | WITH AND MANUFACTURER SUBMITTAL | | | DATA WITH PERMIT APPLICATION. | | | | | | CONDENSER UNIT STANDS SHALL BE | | | A MINIMUM OF 18" ABOVE THE ROOF | | | SURFACE TO THE BOTTOM OF THE | | | SUPPORT RAIL. (AMENDED 1997 SMC | | | 304.2.5) | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-08 |
Time |
10:27 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-01-08 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-10 |
Time |
19:26 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2001-10-10 |
Time |
19:26 |
Sent To |
|
|
| Notes |
| 2001-10-10 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) SHT A-1 DEPT OF HOTEL BUSINESS REG- | | | ULATION, PLAN REVIEW W/COMMENTS REQUIRED | | | BEFORE PLUMBING PLAN REVIEW. FROM PREV- | | | IOUS REVIEW, COMMENT RESPONSE ACKNOWLED- | | | GED. | | | 2) SHT C-1, IR-6, P-1, DETAIL(6), GREASE | | | TANK, COMMENT FROM PREVIOUS PLAN REVIEW, | | | NEED LETTER FROM R. COMPO FOR PLAN RE- | | | VIEW. COMMENT RESPONSE ACKNOWLEDGED. | | | 3) C-4, SITE WORK, TO COMPLY WITH CITY | | | OF WPB UTILITY STANDARDS. BACK FLOW PRE- | | | VENTERS REQD ON IRRIGATION AND FIRE. | | | PLEASE SHOW ON PLANS. COMMENT RESPONSE | | | ACKNOWLEDGED. SHOW TYPE AND LOCATION. | | | 4) GAS PERMIT APPLICATION REQUIREMENTS | | | STILL REQUIRED. PLEASE SUBMIT AN ISO- | | | METRIC THAT CLEARLY SHOWS "ALL CUT SECT- | | | IONS AND CORRESPONDING LENGTHS". PLEASE | | | SHOW TYPE OF GAS (NATURAL OR LP). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-29 |
Time |
10:01 |
Rev Time |
3.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-29 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | CODE REFERENCES,SPC-94,SGC-97,FACBC-97. | | | (1)SHT A-1 DEPT.OF HOTEL BUSINESS | | | REGULATION, PLAN REVIEW W/ COMMENTS | | | REQUIRED, BEFORE PLUMBING PLAN REVIEW. | | | CONTACT | | | 954 -958-5520. | | | (2)SHT C-1,IR-6, P-1, DETAIL(6), GREASE | | | TANK, CONTACT W PALM BCH ENVIRONMENTAL | | | COMPLIANCE, RODNEY COMPO FOR SIZE, | | | 561- 837- 4074. | | | (3)C-4,SITE WORK,TO COMPLY WITH CITY OF | | | WEST PALM BCH. UTILITY STDS, BACK FLOW | | | PREVENTERS REQ. ON DOMESTIC,IRRIGATION | | | AND FIRE WATER SUPPLY, ORD# 2853-95. | | | SHOW TYPE AND LOCATION. | | | (4)SHT A-11,NO ELV.DETAIL FOR THE URINAL | | | SEC 4.18.2 HIGHT 17" AFF. | | | SEC 4.18.3 CLEAR FLR SPACE 30"X 48". | | | (5)SHT A-11 DETAIL(9),H/C SINK, COMPLY | | | SEC 4.19.2, HEIGHT & CLEARANCE,NO | | | HIGHERTHAN 34" AFF. | | | (6)SHT A-11 DETAIL(9) H/C WATER CLOSET, | | | SEC 4.17.3,SIZE & ARRANGMENT,FIG 30(E). | | | DIMENSION OFF THE SIDE WALL 18" | | | ABSOLUTE(7A) SHT P-1,PLBG PLAN NOTES | | | #(4) A/C | | | CONDENSATE DRAINS, COMPLY WITH MCWA-94 | | | SEC 804. COMMON SYTEM TO STORM, CONNECT | | | OUTSIDE OF BLDG, WITH A RELIEF VENT. | | | (7B) ANY REFERENCE TO KITCHEN EQUIPMENT | | | CONTRACTOR,INSTALLING DRAINS. ALL | | | PIPINGTO BE INSTALLED BY A LICENSED | | | PLUMBING | | | CONTRACTOR. | | | (8) SHT P-1 NOTES #6 TO #25 COMPLY WITH | | | MCWA-94 SEC 607.7, NO MORE THAN 2 PLBG. | | | FIXTURES ON 1/2" C/W,NO MORE THAN 4 | | | PLBGFIXTURES ON 1/2" H/W. | | | (9) SHT P-1 NOTE #14 REFERENCE TO OHD, | | | OTHER REFERENCES TO ID, FUNNEL DRAINS | | | ORSAFE WASTE (ID). SEC 802. | | | ALL INDIRECT WASTE TO FLR SINKS. | | | | | | (10) SHT P-1 NOTE #19 COMPLY W ITH SEC | | | 607.8.3,REFERENCE TO AIR CHAMBERS IN | | | CEILINGS AND WALLS. NOT APPROVED. | | | USE STD PDI-WH102,INSTALLATION OF WATER | | | HAMMER ARRESTORS,COMPLY WITH MANFACTURE | | | INSTRUCTIONS FOR SIZE & PLACEMENT. | | | (11) SHT P-2 NO DETAIL# GAS ISOMETRIC, | | | SEE ATTACHED GAS PERMIT APPLICATION RE- | | | QUIRMENTS. ADDRESS EACH OF (6) ITEMS. | | | (12) SHT P-2 DETAIL#(9) IRRIATION BACK | | | FLOW PREVENTER TYPE (RPZV). | | | (13) SHT P-2 KITCHEN DWV ISOMETRIC AND | | | SHT P-3 NOTE #7,DISH WASHER TO SANITARY | | | SEWER,LOCAL ORDINANCE # 2938-96. | | | END OF COMMENTS, PAUL SCHMITZ | | | 3QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-01-23 |
Time |
11:03 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-12 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-07-12 |
Time |
10:44 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-12 00:00:00 | SENT TO BLDG FOR REVIEW |
|
|