Plan Review Details - Permit 01070374
Plan Review Stops For Permit 01070374
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 22:08 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 22:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 21:16 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 21:15 Sent To  
Notes
2001-09-17 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS NOW
 INCLUDE A RISER DIAGRAM WITH NEW EQUIP-
 -MENT BEING INSTALLED.
 PLEASE NOTE, NEED TO SUBMIT AIC RATINGS
 FOR ALL NEW EQUIPMENT/MAIN/PANELS.
 PER 110-9/215-5
  
 2)NOTE: PLEASE CLARIFY 10 GFI CIRCUITS
 SHOWN ON PANEL SCHEDULE. PLEASE NOTE
 THAT TWO SMALL APPLIANCE CIRCUITS ARE
 REQ`D BY 210-52-B1
  
 3)NOTE: PLEASE LABEL GFI CIRCUIT FOR
 BATH.210-11-C-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 18:59 Sent To  
Notes
2001-08-02 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 AND SHOW EXISTING SERVICE SIZE.
 220-3-C-1
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDING ISLAND.
  
 3)NOTE" PLEASE PROVIDE PANEL SCHEDULE OF
 MIN REQ`D CIRCUITS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-12-03 Cont ID  
Sent By pkrauss Date 2001-12-03 Time 09:25 Rev Time 0.40
Received By pkrauss Date 2001-12-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-10-26 Cont ID  
Sent By pkrauss Date 2001-10-26 Time 16:10 Rev Time 0.40
Received By pkrauss Date 2001-10-26 Time 16:10 Sent To  
Notes
2001-10-26 00:00:00*******************DENIED***************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING IN
 FORMATION FOR REVIEW.
  
 PROVIDE EQUIPMENT INFORMATION.
  
 DUCT SIZE, MATERIAL AND LAYOUT.
  
 GRILL SIZE AND LOCATION.
  
 CFM DISTRIBUTION.
  
 ENERGY CALCULATIONS WITH MANUAL J CALCS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-09-14 Cont ID  
Sent By pkrauss Date 2001-09-14 Time 07:50 Rev Time 0.35
Received By pkrauss Date 2001-09-14 Time 07:50 Sent To  
Notes
2001-09-14 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE ENERGY CALCULATIONS AS
 PER FLORIDA ENERGY CODE 101.2.2.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-08-07 Cont ID  
Sent By pkrauss Date 2001-08-07 Time 07:55 Rev Time 0.35
Received By pkrauss Date 2001-08-07 Time 07:54 Sent To  
Notes
2001-08-07 00:00:00*******************DENIED***************
 INSUFFICIENT INFORMATION
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION.
  
 1.MAKE, MODEL, SEER, BTU, AND KW HEAT
 STRIP FOR AHU/CONDENSER.
  
 2.PROVIDE MATERIAL AND R-VALUE FOR
 DUCT BEING INSTALLED.
  
 3.SIZE OF GRILLS AND CFM BEING
 DISTRIBUTED.
  
 4.PLEASE PROVIDE ENERGY CALCULATIONS
 TO SHOW COMPLIANCE WITH FLORIDA
 ENERGY EFFICIENCY CODE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-12 Cont ID  
Sent By kstevens Date 2001-09-12 Time 19:47 Rev Time 0.50
Received By kstevens Date 2001-09-12 Time 19:47 Sent To  
Notes
2001-09-12 00:00:00SEPARATE GAS REQUIRED
 IF ANY GAS WORK IS TO BE DONE..

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By kstevens Date 2001-08-06 Time 08:57 Rev Time 0.50
Received By kstevens Date 2001-08-06 Time 08:57 Sent To  
Notes
2001-08-06 00:00:00DENIED..
  
 1) NOT ENOUGH INFROMATION.
  
 2) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM SHOWING ALL NEW FIXTURES AND ANY
 FIXTURES RELOCATED.
  
 3) PLEASE SUBMIT DETAIL ON WATER AND
 DRAINAGE FOR DISHWASHER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 7 Status P Date 2002-01-30 Cont ID  
Sent By jgomez Date 2002-01-30 Time 16:13 Rev Time 1.50
Received By jgomez Date 2002-01-30 Time 16:13 Sent To  
Notes
2002-01-30 00:00:00APPROVED WITH PROVISO:
  
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-ELECTRICAL, PLUMBING AND MECHANICAL
 WORK UNDER SEPARATE PERMITS SINCE THEY
 DIDN'T SIGN ORIGINAL APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status F Date 2001-12-26 Cont ID  
Sent By jgomez Date 2001-12-26 Time 10:59 Rev Time 1.50
Received By jgomez Date 2001-12-26 Time 10:58 Sent To  
Notes
2001-12-26 00:00:005TH CHECKLIST:
 1-PRODUCT APPROVAL INFORMATION SUBMITTED
 STILL IS NOT ACCEPTABLE.
 A)SITE SPECIFIC FORM NEEDS TO BE SIGNED,
 SEALED & DATED BY ARCHITECT OF RECORD
 AS WELL.
 B)DESIGN PRESSURES SPECIFIED FOR THE
 SLIDING GLASS DOORS ARE INCORRECT.
 THOSE ARE THE RESULT PRESSURES, NOT
 THE DESIGN PRESSURES. THEREFORE, THIS
 PRODUCT APPROVAL IS NOT ACCEPTABLE.
 SEE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT OF RECORD.
 C)PRODUCT APPROVAL IS FOR CASEMENT
 WINDOWS.THERE ARE NOT CASEMENT WINDOWS
 IN THIS PROJECT. SEE ARCHITECT'S PLANS
 D)ENGINEER TO SEE ARCHITECT'S PLANS TO
 SEE SIZES AND TYPE OF GLASS REQUIRED
 ACCORDING TO LOCATION. (SAFETY GLASS
 REQUIRED AT HAZARDOUS LOCATIONS.
 SECTION2405.2 SBC 1997).
 E)PROVIDE COMPLETE PRODUCT APPROVAL
 INFORMATION FOR WINDOW MULLIONS.
  
 2-OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS AS REQUIRED BY
 SEC. 103.1 FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION, 1997.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2001-12-06 Cont ID  
Sent By jgomez Date 2001-12-06 Time 15:28 Rev Time 1.00
Received By jgomez Date 2001-12-06 Time 15:28 Sent To  
Notes
2001-12-06 00:00:00CHECKLIST:
 1-NEED ENERGY CALCULATIONS OF FORM
 600A-97. SEC. 101.2.2 FL. ENERGY CODE.
 -INFORMATION SUBMITTED ARE THE MANUAL
 J CALCS FOR A/C SIZING.
 2-COMMENTS FOR SITE SPECIFIC PRODUCT
 APPROVAL INFORMATION SUBMITTED:
 A)NEED TO COMPLETELY FILL OUT FORM FOR
 SITE SPECIFIC INSTALLATIONS. SEE
 ATTACHED COPY.
 NOTE: THIS FORM TO BE SEALED, SIGNED &
 DATED BY MANUFACTURER'S ENGINEER AND
 BY ARCHITECT OF RECORD.
 B)DESIGNED PRESSURES SPECIFIED FOR THE
 SLIDING GLASS DOORS ARE TEST RESULTS,
 NOT DESIGN PRESSURES. THEREFORE, THIS
 PRODUCT APPROVAL IS NOT ACCEPTABLE.
 -DESIGN PRESSURES MUST MEET OR EXCEED
 THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT FOR THIS PROJECT.
 C)THERE ARE NOT CASEMENT WINDOWS ON THIS
 PROJECT. THERE ARE SINGLE HUNG WINDOWS
 D)THERE IS NOT INFORMATION GIVEN FOR THE
 FIXED WINDOWS. ALSO, CHECK SIZES SHOWN
 ON ARCHITECT'S PLANS.
 E)ENGINEER NEEDS TO PROVIDE ORIGINAL
 SIGNATURE & DATE ON ALL DOCUMENTS
 SUBMITTED FOR PUBLIC RECORDS AS REQ'D
 BY CHAPTER 471 OF FLORIDA STATUTES.
  
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS. INFORMATION PROVIDED IS ONLY
 THE PRODUCT APPROVAL.
 -CLEARLY INDICATE ON DRAWINGS THE
 SPECIFIC INSTALLATION FOR THIS PROJECT.
 SAMPLE ATTACHED. SEE SHEET 2 OF 17.
 NOTE: PROVIDE COMPLETE PRODUCT APPROVAL
 REPORT. ONLY APPROVED DRAWINGS
 WERE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2001-11-02 Cont ID  
Sent By jgomez Date 2001-11-02 Time 14:53 Rev Time 0.00
Received By jgomez Date 2001-11-02 Time 14:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2001-11-02 Cont ID  
Sent By jgomez Date 2001-11-02 Time 14:30 Rev Time 1.50
Received By jgomez Date 2001-11-02 Time 14:30 Sent To  
Notes
2001-11-02 00:00:00CHECKLIST:
 1-NEED ENERGY CALCULATIONS ON FORM
 600A-97 AS REQUIRED BY SECTION 101.2.2
 OF FLORIDA ENERGY EFFICIENCY CODE FOR
 BUILDING CONSTRUCTION, 1997 EDITION.
 -INFORMATION SUBMITTED ARE NOT THE
 ENERGY CALCULATIONS.
 2-PROVIDE PRODUCT APPROVAL FOR:
 A)SLIDING GLASS DOORS WITH SIZE AND
 DESIGN PRESSURES AS SPECIFIED ON
 ARCHITECT'S PLANS.
 -PRODUCT APPROVAL SUBMITTED DOESN'T
 MEET EITHER ONE.
 C)FIXED WINDOWS WITH THE SIZE SHOWN IN
 ARCHITECT'S PLANS.
 -PRODUCT APPROVAL SUBMITTED IS FOR
 WINDOWS UP TO 120" IN WIDTH AND UP TO
 60" IN HEIGHT. SEE ARCHITECT'S PLAN
 FOR SIZE SPECIFIED.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS.
 -CLEARLY INDICATE ON SHUTTER DRAWINGS
 THE SPECIFIC MOUNTING CONDITIONS AND
 ALL THE SPECIFIC COMPONENTS TO BE USED
 ON THIS PROJECT.
 -IF INFORMATION IS NOT COMPLETE AT THIS
 TIME, THEN SUB-CONTRACTOR MAY APPLY
 FOR A SEPARATE PERMIT IN ORDER TO
 EXPEDITE THE BUILDING PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-09-24 Cont ID  
Sent By jgomez Date 2001-09-24 Time 19:07 Rev Time 2.50
Received By jgomez Date 2001-09-24 Time 19:07 Sent To  
Notes
2001-09-24 00:00:00CHECKLIST:
 1-NEED ENERGY CALCULATIONS AS REQUIRED
 BY SECTION 101.2.2 OF STATE OF FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 2-CLARIFY HOW IS TRUSS ANCHOR TAPR
 ANCHORED TO EXISTING TIE BEAM.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED BY
 SEC. 2405.2 SBC 1997. SEE PLANS.
 4-PROVIDE PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM TO BE USED.
 B)SLIDING GLASS DOORS WITH THE SIZES AND
 AND THE DESIGN PRESSURES AS SHOWN ON
 THE ARCHITECT'S PLANS.
 C)FIXED WINDOWS WITH THE SIZE AS SHOWN
 ON ARCHITECT'S PLANS.
  
 5-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS:KEY PLAN, INSTALLATION SCHEDULE
 AND CLEARLY INDICATE ON DRAWINGS THE
 SPECIFIC MOUNTING CONDITIONS TO BE
 USED.
 -IF COMPLETE INFORMATION IS NOT
 PROVIDE A TIME OF RESUBMITTAL, THEN A
 SEPARATE PERMIT MAY BE APPLIED FOR.
 6-OWES ADDITIONAL FEES OF $315.28 FOR
 UPDATED BUILDING VALUATION AND RADON
 FEES. PLEASE PAY ATTACHED RECEIPT.
 7-SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AS REQ'D BY SEC. 2305 SBC/97.
 SEE SHEET #6 FOR COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-31 Cont ID  
Sent By jgomez Date 2001-07-31 Time 11:01 Rev Time 3.00
Received By jgomez Date 2001-07-31 Time 11:01 Sent To  
Notes
2001-07-31 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS AND RECEIPT.
 2-NEED TO FILE NOTICE OF COMMENCEMENT.
 3-PROVIDE ENERGY CALCULATIONS.
 4-PROVIDE SOIL TEST REPORT.
 5-SPECIFY VENTILATION FOR ROOF AS REQ'D
 BY SEC. 2309.7.2 SBC 1997.
 6-TRUSS ANCHOR SCHEDULE:
 -CONNECTOR SEMCO RTPGA IS A WOOD TO
 WOOD CONNECTOR. NOT WOOD TO CONCRETE.
 REVISE AS REQUIRED.
 -CLARIFY HOW IS CONNECTOR TAPR EMBEDED
 INTO EXISTING TIE BEAM.
 7-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. SEE
 COMMENTS ON FORM.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEC 2405.2 SBC/97. SEE FLOOR PLAN.
 9-NEED PRODUCT APPROVAL FOR: (2 COPIES)
 -FLAT ROOF SYSTEM.
 -CLAY BARREL TILE.
 -SLIDING GLASS DOORS.
 -SINGLE HUNG WINDOWS.
 -FIXED WINDOWS.
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS. INSTALLATION SCHEDULE
 KEY PLAN, ETC.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-07 Cont ID  
Sent By sgraham Date 2001-08-07 Time 15:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***