Plan Review Details - Permit 01070273
Plan Review Stops For Permit 01070273
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-01-17 Cont ID  
Sent By lsmith Date 2003-01-17 Time 10:17 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2003-01-17 00:00:00APPROVED 1/16/03 BY LUIS MARTINEZ & MIKE
 CARSILLO (FIRE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-09-06 Cont ID  
Sent By pkrauss Date 2002-09-04 Time 13:38 Rev Time 2.00
Received By lmartine Date 2002-08-30 Time 09:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-08-02 Cont ID  
Sent By lmartine Date 2002-07-02 Time 12:30 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-08-02 00:00:00 
 REVISION COMMENTS
 -------- --------
  
 COMMENT FROM 4/20/02 REVIEW IS STILL
 AN ISSUE, 13R VERSUS STRAIGHT 13
 SPRINLER SYSTEM AND FOOTNOTE [D] TABLE
 500.
  
 COMPLIANCE WITH 1006.2 IS NOT FOUND ON
 SHEET A9.01
  
  
  
 L. MARTINEZ
 659-8096
 #8456
2002-07-02 00:00:00JOIST REPAIR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-04-30 Cont ID  
Sent By hpiskura Date 2002-04-30 Time 10:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-30 00:00:00THE PLANS DECLARE AN NFPA 13R DESIGN
 FIRE SPRINKLER SYSTEM.SEE FOOTNOTE
 {D} TO SBC TABLE 500.THERE FORE THE
 BUILDING IS REQUIRED TO BE ONE HOUR
 PROTECTED ORA COMPLETE 13 SYSTEM FOR
 THE THREE STORY REQUIREMENT.
  
 FURTHER, EGRESS WINDOWS, FIRE RATED
 CORRIDORS, AND ANY OTHER REDUCTIONS
 TAKEN FOR FIRE SPRINKLER SYSTEM ARE NOT
 APPLICABLE TO THIS BUILDING.SEE ALSO
 SBC 903.2.
  
 WHERE THE ROOF IS USED FOR EXIT ACCESS
 IT MUST COMPLY WITH SBC 1006.2 FOR
 SEPARATION FROM THE INTERIOR OF THE
 BUILDING.
  
 SHOW THE DETAILS FOR THE THIRD FLOOR
 EXTERIOR STAIR WITH REGARDS TO
 DIMENSIONS, DESIGN LOADS, HAND AND
 GUARD RAILS.SEE SBC 1007.
  
 THE PLANS DO NOT CLEARLY INDICATE THE
 FIRE RATED TENANT SEPARATION REQUIRED
 BY SBC 704.3.INCLUDING AT THE
 "CORRIDOR SIDE".
  
 DOES THE EXIT DISCHARGE ON THE WEST
 SIDECOMPLY WITH SBC 1010?
  
 SHEET A9.01.SHOW A SPECIFIC FRAMING
 DETAIL FOR THE SOFFIT CONSTRUCTION.
 HOW IS THE FIRE RATED SEPARATION
 BETWEEN FLOORS MAINTAINED?HOW IS THE
 MECHANICAL EQUIPMENT SUPPORTED AND
 ACCESSED?SEE SBC 104.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-01-31 Cont ID  
Sent By lmartine Date 2002-01-31 Time 14:22 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-01-31 00:00:00 
 BUILDING COMMENTS
 -------- --------
  
 SCOPE OF WORK FOR THIS PERMIT DOES NOT
 INCLUDE STOREFRONT INSTALLATION,
 SEPERATE PERMIT IS REQUIRED.
  
 SUBMIT TEST REPORTS FOR FIXED GLASS AS
 WELL AS THE DOORS.
  
 PROVIDE ENGINEERS DESIGN PRESSURES ON
 THE EXISTING OPENINGS.
  
 IMPACT PROTECTION WILL BE REQUIRED FOR
 NEW INSTALLATION.
  
  
 L. MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:52 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-09-03 Cont ID  
Sent By btrobaug Date 2002-09-03 Time 12:07 Rev Time 1.50
Received By btrobaug Date 2002-09-03 Time 09:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-07-02 Cont ID  
Sent By btrobaug Date 2002-07-02 Time 11:13 Rev Time 0.00
Received By btrobaug Date 2002-06-28 Time 17:12 Sent To  
Notes
2002-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES IN
 THE PLANS,AND RESUBMIT FOR REVIEW;
  
 1} THE UNITS LABELED "F,D"AND"C,F" ON
 THE ARCHITECTURAL SHEETS A2.02 AND
 A3.03 STILL ARE INCONSISTENT AND DO NOT
 CORRELATE WITH THE SHEETS IN THE
 ELECTRICAL PLAN THAT CONSISTENTLY LIST
 THEM AS TYPES "D" AND "F".PLEASE CLARIFY
  
 2} THE HALL LIGHTING ON SHEET E2.1 NEEDS
 A 4-WAY SWITCH.
  
 3} SHEET M-1 LISTS THE AHU AS #6,SHEET
 SHEET E3.1 LISTS IT AS AHU #4,WHICH
 AGREES WITH PANEL SCHEDULE"LHP"AND
 THE EQUIPMENT SCHEDULE ON SHEET
 M-8.PLEASE CORRECT.
  
 4} AHU'S #5 AND #6 DO NOT APPEAR ON THE
 ELECTRICAL PLANS,EXCEPT ON PANEL
 SCHEDULE "LHP",PLEASE INDICATE THEIR
 LOCATIONS AND SHOW DISCONNECTS.
  
 5} SHEET M-2 SHOWS THE WASHERS,DRYERS
 AND WATER HEATER IN A DIFFERENT
 LOCATION THAN SHEETS E3.2 AND
 A2.02,PLEASE CORRELATE THESE DRAWINGS
 TO SHOW THE CORRECT LOCATIONS.
  
 6} WATER HEATER DISCONNECT LOCATION
 SHOWN ON SHEET E3.2 WOULD NOT COMPLY
 WITH 110-26.(NOTE:THE HEATER IS IN
 SIGHT OF PANEL "L2".)
  
 7} PLEASE NOTE THAT THE DISCONNECTS FOR
 THE WATER HEATERS LOCATED IN THE CLOSETS
 OF THE UNITS MUST COMPLY WITH 110-26.
  
 8} PLEASE NOTE THAT THE CIRCUIT NUMBERS
 ON SHEET E3.4 MUST CORRELATE WITH THE
 PANEL SCHEDULES FOR THE CONDENSERS.
  
 9} PLEASE INDICATE THE TYPE AND SIZE OF
 THE CONDUIT AND CONDUCTORS FEEDING "L2"
 ON SHEET E5.6.
  
 10} PLEASE INDICATE FEEDER CONDUCTOR AND
 CONDUIT TYPE AND SIZE FOR THE "FUTURE"
 METERS AND DISCONNECTS IF THEY ARE BEING
 INSTALLED UNDER THIS PERMIT.
  
 11} PANEL"LHP" ON SHEET E5.1 IS SHOWN
 BEING FED WITH A 3"PVC CONDUIT,IF IT IS
 SHOWN AS THAT ON THE STAMPED PLANS IT
 MUST BE INSTALLED.
  
 12} THE LOCATION OF THE CATV BOARD SHOWN
 ON RISER SHEET E5.1,IS NOT SHOWN ON THE
 PLAN. PLEASE VERIFY THE SIZE AND NUMBER
 OF THE FEEDERS FOR THIS SYSTEM.ONE 4"
 IS SHOWN,SAME AS THE TELEPHONE RISER.
  
 13} PLEASE VERIFY THE DIMENSIONS OF THE
 ELECTRIC ROOM ON SHEET A2.01 AND E2.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-18 Cont ID  
Sent By btrobaug Date 2002-04-18 Time 18:09 Rev Time 0.00
Received By btrobaug Date 2002-04-19 Time 09:38 Sent To  
Notes
2002-04-19 00:00:00***************** UNSAT!****************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND MAKE NECESSARY CORRECTIONS AND
 RESUBMIT FOR REVIEW:
  
 1} THERE ARE DISCREPANCIES IN THE TYPES
 OF UNITS LOCATED ON THE NORTH-WEST SIDE
 OF THE BUILDING.SHEET A2.02 INDICATES
 THE UNITS ARE TYPE"F"&"D",SHEET A2.03
 INDICATES THEY ARE TYPES"C"&"F" AND
 E3.3 THEM AS"C"&"D".ALSO ON E3.3 THE"E"
 UNITS AREN'T LABELED.
  
 2} THE METER CENTER MAIN #1 LOAD
 SUMMARY ON SHEET E6.1 LISTS ONLY 17
 UNITS.PLEASE CLARIFY WHICH UNITS ARE
 NOT INCLUDED,LIST THEM AND PROVIDE LOAD
 CALCULATIONS ON THE SUMMARY SHEET FOR
 SAME.
  
 3} ON SHEET E6.1,PANEL"LHP",CIRCUIT #'S
 12-14,28-30,38-40 THE OCP IS INCORRECT
 FOR THE CONDUCTOR SIZE.THE"A"UNITS
 PANELS CIRCUIT#13-15 IS ALSO INCORRECT.
  
 4} PANEL "LHP" CIRCUIT #36 DOES NOT
 CORRELATE TO SHEET E3.1 WHERE IT IS
 SHOWN SERVING THE HALL RECEPTACLE
 CIRCUIT.
  
 5} THE HALL LIGHTING ON SHEET E2.1 NEEDS
 A 4-WAY SWITCH.
  
 6} THE TYPE"B"UNITS ON SHEETS E2.2 & E2.
 3 NEED A SMOKE DETECTOR IN BOTH BEDROOMS
 PER 2-2.1.1.1 NFPA-72 (1996).
  
 7} CIRCUIT L2-14 IN THE LAUNDRY ROOM
 SHEET E3.2 IS MISMARKED.
  
 8} SHEET E2.2 UNIT"D"HAS NO SMOKE
 DETECTRS IN THE STUDY,IF IT IS INTENDED
 AS A SLEEPING ROOM IT MUST COMPLY WITH
 2-2.1.1.1 AS THE 3RD FLOOR UNIT DOES.
  
 9} PLEASE NOTE THE LOCATION OF THE SMOKE
 DETECTORS IN UNIT TYPES"A","C"&"E" WITH
 RESPECT TO THE KITCHENS IN THESE UNITS.
 IF THESE WERE MOVED FURTHER FROM THE
 KITCHEN, ESPECIALLY GIVEN THE FACT OF
 THE DROPPED SOFFITS,IT COULD HELP
 REDUCE THE THE PROBABILITY OF NUISANCE
 ALARMS.
  
 10} PLEASE VERIFY THE DIMENSIONS OF THE
 MECHANICAL ROOM.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659/8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:54 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-01-17 Cont ID  
Sent By lsmith Date 2003-01-17 Time 10:18 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2003-01-17 00:00:00PER MEC 1/16/03 LS

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-09-03 Cont ID  
Sent By btrobaug Date 2003-01-02 Time 12:18 Rev Time 0.00
Received By mcarsill Date 2002-09-03 Time 09:05 Sent To  
Notes
2002-09-03 00:00:001) EXISTING FIRE EXIT STAIR IS NOT
 TO BE REMOVED. IT CAN BE REPLACED
 WITH ANOTHER ONE SO LONG AS IT
 COMPLIES WITH ALL APPROPRIATE
 BUILDING AND FIRE CODE REQUIREMENTS.
 THIS EXISTING DEVICE CANNOT BE REMOVED
 AS A DEAD-END CORRIDOR WOULD EXIST
 THAT EXCEEDS CODE REQUIREMENTS.
  
 2) ENSURE ALL DEVICES ARE PLACED
 ON THE BUILDING'S PROPERTY NOT
 SOMEONE ELSE'S.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-07-02 Cont ID  
Sent By mcarsill Date 2002-07-02 Time 15:07 Rev Time 0.00
Received By mcarsill Date 2002-07-02 Time 15:07 Sent To  
Notes
2002-07-02 00:00:001. PLEASE PROVIDE A COPY OF A SURVEY TO
 THIS OFFICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-04-30 Cont ID  
Sent By mcarsill Date 2002-04-30 Time 17:15 Rev Time 0.00
Received By mcarsill Date 2002-04-30 Time 17:14 Sent To  
Notes
2002-04-30 00:00:001) MERCANTILE TENANT SPACES ARE TO BE
 PROPERLY FIRE RATED FROM ONE ANOTHER BY
 AT LEAST ONE HOUR.
 2) NOTES INDICATE ON PAGE A2.01
 INDICATES A 13R FIRE SPRINKLER SYSTEM.
 THE MERCANTILE OCCUPANCIES MUST BE
 PROTECTED IN ACCORDANCE WITH NFPA 13.
 3) THE EXISTING FIRE EXIT STAIR "TO BE
 REMOVED OR REPLACED WITH COMPLYING
 STAIRS". THE EXISTING STAIRWAY MUST
 BE COMPLIANT WITH ALL OF THE
 REQUIREMENTS FOR EXITING FROM THE
 BUILDING AND FIRE CODES. THE STAIR
 CANNOT BE REMOVED BECAUSE A DEAD-END
 CONDITION IS EVIDENT.
 4) WITH REGARDS TO THE EXTERIOR STAIRS,
 HOW IS EXIT DISCHARGE ACCOMPLISHED.
 DOES EXITING OCCUR ON THE SAME PROPERTY,
 SOMEONE ELSE'S PROPERTY, OR ALLEY.
 PLEASE EXPLAIN.
 5) FIRE ALARM NOTES INDICATE CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE D
 CIRCUITS ARE ALLOWED.
 6) EXIT DOORS FOR THE MERCANTILE
 OCCUPANCIES, DO THEY OPEN ONTO THE
 SAME PROPERTY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2003-01-02 Time 12:18 Rev Time 0.00
Received By btrobaug Date 2003-01-02 Time 12:17 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-09-04 Cont ID  
Sent By pkrauss Date 2002-09-03 Time 16:52 Rev Time 0.00
Received By pkrauss Date 2002-09-03 Time 16:52 Sent To B
Notes
2002-09-03 00:00:00 
 APPROVED BY BUILDING OFFICAL "ALTERNATE
 MEANS & METHODS" AS PER FIELD INSPECTION
 BY LUIS MARTINEZ, BILL STAPLES, & NEIL
 MELICK.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date 2002-04-26 Cont ID  
Sent By pkrauss Date 2002-04-26 Time 08:58 Rev Time 1.00
Received By pkrauss Date 2002-04-26 Time 08:58 Sent To  
Notes
2002-04-26 00:00:00MECHANICAL PERMIT 01020462
  
  
 AS PER THE COUNTYWIDE AMMENDMENTS TO THE
 1997 SMC 610.1.3 #2, WHERE BRANCH DUCTS
 CONNECT TO RETURN RISERS IN WHICH THE
 AIR IS UPWARD IN THE SUBDUCT, RISER
 SHALL BE CARRIED UP AT LEAST 22" INSIDE
 THE SUBDUCT.SUBDUCT MUST BE A MINIMUM
 OF 26 GA. GALVANIZED OR EQUIVALENT.
 RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE.EACH UNIT SHALL HAVE A
 BACKDRAFT DAMPER AS TO PREVENT
 INFLITRATION CAUSED BY PRESSURE
 DIFFERNTIAL.
  
 PLAN SHEET A9.01 DETAIL #3, 1 HOUR
 RATED SHAFT UL 415.UL415 IS FOR A NON
 BEARING WALL NOT A 1 HR SHAFT.PLEASE
 CORRECT.
  
 CHECK WITH NANCY -
 PLAN SHEET M-2 O.A. FROM THE FIRST FL TO
 THE AHU FD AT PENETRATION AHU 5 SUPPLY
 TO CORRIDOR FD IN SUP & RET.
  
 PLAN SH M-3 AHU 4 SUP & RET TO CORRIDOR
 & STAIRWELL BOTH HAVE FIRE DAMPERS.COR
 RIDOR RADIANT DAMPERS IN CEILING.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-22 Cont ID  
Sent By pkrauss Date 2002-02-22 Time 11:05 Rev Time 0.30
Received By pkrauss Date 2002-02-22 Time 11:05 Sent To  
Notes
2002-02-22 00:00:00 
 PROVISO UNDER PERMIT 00110504 (CLOSED)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-09-10 Cont ID  
Sent By kstevens Date 2002-09-10 Time 13:42 Rev Time 0.00
Received By kstevens Date 2002-09-10 Time 13:42 Sent To  
Notes
2002-09-10 00:00:00PASSED/PROVISO
  
 LETTER WITH ROOF DRAIN CALCULATIONS TO
 BE DELIVERED 9-16-02

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-07-09 Cont ID  
Sent By kstevens Date 2002-07-09 Time 12:19 Rev Time 0.00
Received By kstevens Date 2002-07-09 Time 12:15 Sent To  
Notes
2002-07-09 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) FROM PREVIOUS REVIEW: PLEASE SHOW ALL
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 LOCATION AND SQ FT FOR ALL DRAINS, SIZE
 OF DOWNSPOUTS. SHOW TOTAL SIZE OF ROOF
 BEING DRAINED, ADD 1/2 AREA OF ALL VERT-
 ICAL WALLS. PLEASE SUBMIT CALCULATIONS.
 - RESPONSE NOTED, BUT INFORMATION NOT
 SUFFICIENT. DOWNSPOUTS AND SECONDARY
 DRAINS NOT FOUND ON ARCHITECTURAL PLANS
 AS STATED IN RESPONSE.
 2) SHTS P6.1/P6.2 WATER RISER DIAGRAM.
 FROM PREVIOUS REVIEW: WATER HAMMER ARRES
 TORS SHALL BE LOCATED AT QUICK CLOSING
 VALVES. (IN KITCHEN - FOR DISHWASHER &
 ICE MAKER). RESPONSE NOTED, MORE W.H.A'S
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-04-18 Cont ID  
Sent By kstevens Date 2002-04-18 Time 08:21 Rev Time 0.00
Received By kstevens Date 2002-04-18 Time 08:21 Sent To  
Notes
2002-04-18 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT PO.1 NOTE #13 AIR CHAMBERS IF IN-
 STALLED SHALL BE ACCESSIBLE AND RECHARG-
 ABLE. (SEE ATTACHED SHEET FOR APPROVED
 AIR CHAMBERS). APPROVED WATER HAMMER
 ARRESTORS DO NOT REQUIRE ACCESS AND DO
 NOT REQUIRE TO BE RECHARGED. SUGGEST
 USING APPROVED WATER HAMMER ARRESTORS.
 2) SHT P0.1 SUBMIT MANUFACTURE INFORMAT-
 ION FOR TANKLESS WATER HEATERS.
 3) SHT P3.2 LAUNDRY ROOM HEATER, 1" PAN
 DRAIN REQUIRED NOT 3/4" AS SHOWN.
 4) SHT P3.2 - SHT P5.2 LAUNDRY ROOM
 FLOOR DRAIN REQUIRED WITH TRAP PRIMER.
 SPC SEC 409.4.5
 5) SHT P4.1 PLEASE SHOW ALL PRIMARY &
 SECONDARY ROOF DRAINS. SHOW LOCATION,
 SQUARE FOOTAGE AREA FOR EACH DRAIN, SIZE
 OF DRAINS, AND SIZE OF STORM DRAINAGE
 PIPING. SHOW TOTAL SQUARE FOOTAGE OF
 ROOF BEING DRAINED. ADD 1/2 AREA OF ALL
 VERTICAL WALLS AND AREA OF ROOFS DRAIN-
 ING FROM ABOVE. PLEASE SUBMIT ALL CAL-
 CULATIONS
 6) SHTS P6.1/P6.2 DOMESTIC WATER ISO-
 METRIC EAST/WEST. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE RANGE"
 CLOSE TO FIXTURES, NOT AT TOP OF DROPS
 AS SHOWN. PDI-WH 201 & MANUFACTURE IN-
 STALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-13 Cont ID  
Sent By pschmitz Date 2001-12-13 Time 09:49 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-13 00:00:00PLUMBING PLAN REVIEW, DENIED
 REFERENCE ORIGINAL PLAN 00110504.
 PLANS NOT COMPLETE, SHT'S MISSING.
 SHT, P5.1 DWV, 5 APTS MISSING,
 T/P TO BE RUN IN A COMMON SYSTEM TO THE
 OUT SIDE, NOT TO THE SANITARY DRAINS.
 SHT P0.1 DIELECTRIC UNIONS NOT APPRROVED
 SHT P0.1 WASHING MACHINE BOX ON A 1 HR
 RATED WALL. F/F REQUIRED IN LAUNDRY RM.
 1" WTR HTR PAN DRAIN REQ.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:55 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-06 Cont ID  
Sent By lmartine Date 2001-07-06 Time 15:55 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***