| Plan Review Stops For Permit 01070273 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-01-17 |
Time |
10:17 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | APPROVED 1/16/03 BY LUIS MARTINEZ & MIKE | | | CARSILLO (FIRE). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-09-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-04 |
Time |
13:38 |
Rev Time |
2.00 |
| Received By |
lmartine |
Date |
2002-08-30 |
Time |
09:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2002-08-02 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-07-02 |
Time |
12:30 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-02 00:00:00 | | | | REVISION COMMENTS | | | -------- -------- | | | | | | COMMENT FROM 4/20/02 REVIEW IS STILL | | | AN ISSUE, 13R VERSUS STRAIGHT 13 | | | SPRINLER SYSTEM AND FOOTNOTE [D] TABLE | | | 500. | | | | | | COMPLIANCE WITH 1006.2 IS NOT FOUND ON | | | SHEET A9.01 | | | | | | | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 | | 2002-07-02 00:00:00 | JOIST REPAIR |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-30 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | THE PLANS DECLARE AN NFPA 13R DESIGN | | | FIRE SPRINKLER SYSTEM.SEE FOOTNOTE | | | {D} TO SBC TABLE 500.THERE FORE THE | | | BUILDING IS REQUIRED TO BE ONE HOUR | | | PROTECTED ORA COMPLETE 13 SYSTEM FOR | | | THE THREE STORY REQUIREMENT. | | | | | | FURTHER, EGRESS WINDOWS, FIRE RATED | | | CORRIDORS, AND ANY OTHER REDUCTIONS | | | TAKEN FOR FIRE SPRINKLER SYSTEM ARE NOT | | | APPLICABLE TO THIS BUILDING.SEE ALSO | | | SBC 903.2. | | | | | | WHERE THE ROOF IS USED FOR EXIT ACCESS | | | IT MUST COMPLY WITH SBC 1006.2 FOR | | | SEPARATION FROM THE INTERIOR OF THE | | | BUILDING. | | | | | | SHOW THE DETAILS FOR THE THIRD FLOOR | | | EXTERIOR STAIR WITH REGARDS TO | | | DIMENSIONS, DESIGN LOADS, HAND AND | | | GUARD RAILS.SEE SBC 1007. | | | | | | THE PLANS DO NOT CLEARLY INDICATE THE | | | FIRE RATED TENANT SEPARATION REQUIRED | | | BY SBC 704.3.INCLUDING AT THE | | | "CORRIDOR SIDE". | | | | | | DOES THE EXIT DISCHARGE ON THE WEST | | | SIDECOMPLY WITH SBC 1010? | | | | | | SHEET A9.01.SHOW A SPECIFIC FRAMING | | | DETAIL FOR THE SOFFIT CONSTRUCTION. | | | HOW IS THE FIRE RATED SEPARATION | | | BETWEEN FLOORS MAINTAINED?HOW IS THE | | | MECHANICAL EQUIPMENT SUPPORTED AND | | | ACCESSED?SEE SBC 104.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-01-31 |
Time |
14:22 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-31 00:00:00 | | | | BUILDING COMMENTS | | | -------- -------- | | | | | | SCOPE OF WORK FOR THIS PERMIT DOES NOT | | | INCLUDE STOREFRONT INSTALLATION, | | | SEPERATE PERMIT IS REQUIRED. | | | | | | SUBMIT TEST REPORTS FOR FIXED GLASS AS | | | WELL AS THE DOORS. | | | | | | PROVIDE ENGINEERS DESIGN PRESSURES ON | | | THE EXISTING OPENINGS. | | | | | | IMPACT PROTECTION WILL BE REQUIRED FOR | | | NEW INSTALLATION. | | | | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-09-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-03 |
Time |
12:07 |
Rev Time |
1.50 |
| Received By |
btrobaug |
Date |
2002-09-03 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-02 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-28 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2002-07-02 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES IN | | | THE PLANS,AND RESUBMIT FOR REVIEW; | | | | | | 1} THE UNITS LABELED "F,D"AND"C,F" ON | | | THE ARCHITECTURAL SHEETS A2.02 AND | | | A3.03 STILL ARE INCONSISTENT AND DO NOT | | | CORRELATE WITH THE SHEETS IN THE | | | ELECTRICAL PLAN THAT CONSISTENTLY LIST | | | THEM AS TYPES "D" AND "F".PLEASE CLARIFY | | | | | | 2} THE HALL LIGHTING ON SHEET E2.1 NEEDS | | | A 4-WAY SWITCH. | | | | | | 3} SHEET M-1 LISTS THE AHU AS #6,SHEET | | | SHEET E3.1 LISTS IT AS AHU #4,WHICH | | | AGREES WITH PANEL SCHEDULE"LHP"AND | | | THE EQUIPMENT SCHEDULE ON SHEET | | | M-8.PLEASE CORRECT. | | | | | | 4} AHU'S #5 AND #6 DO NOT APPEAR ON THE | | | ELECTRICAL PLANS,EXCEPT ON PANEL | | | SCHEDULE "LHP",PLEASE INDICATE THEIR | | | LOCATIONS AND SHOW DISCONNECTS. | | | | | | 5} SHEET M-2 SHOWS THE WASHERS,DRYERS | | | AND WATER HEATER IN A DIFFERENT | | | LOCATION THAN SHEETS E3.2 AND | | | A2.02,PLEASE CORRELATE THESE DRAWINGS | | | TO SHOW THE CORRECT LOCATIONS. | | | | | | 6} WATER HEATER DISCONNECT LOCATION | | | SHOWN ON SHEET E3.2 WOULD NOT COMPLY | | | WITH 110-26.(NOTE:THE HEATER IS IN | | | SIGHT OF PANEL "L2".) | | | | | | 7} PLEASE NOTE THAT THE DISCONNECTS FOR | | | THE WATER HEATERS LOCATED IN THE CLOSETS | | | OF THE UNITS MUST COMPLY WITH 110-26. | | | | | | 8} PLEASE NOTE THAT THE CIRCUIT NUMBERS | | | ON SHEET E3.4 MUST CORRELATE WITH THE | | | PANEL SCHEDULES FOR THE CONDENSERS. | | | | | | 9} PLEASE INDICATE THE TYPE AND SIZE OF | | | THE CONDUIT AND CONDUCTORS FEEDING "L2" | | | ON SHEET E5.6. | | | | | | 10} PLEASE INDICATE FEEDER CONDUCTOR AND | | | CONDUIT TYPE AND SIZE FOR THE "FUTURE" | | | METERS AND DISCONNECTS IF THEY ARE BEING | | | INSTALLED UNDER THIS PERMIT. | | | | | | 11} PANEL"LHP" ON SHEET E5.1 IS SHOWN | | | BEING FED WITH A 3"PVC CONDUIT,IF IT IS | | | SHOWN AS THAT ON THE STAMPED PLANS IT | | | MUST BE INSTALLED. | | | | | | 12} THE LOCATION OF THE CATV BOARD SHOWN | | | ON RISER SHEET E5.1,IS NOT SHOWN ON THE | | | PLAN. PLEASE VERIFY THE SIZE AND NUMBER | | | OF THE FEEDERS FOR THIS SYSTEM.ONE 4" | | | IS SHOWN,SAME AS THE TELEPHONE RISER. | | | | | | 13} PLEASE VERIFY THE DIMENSIONS OF THE | | | ELECTRIC ROOM ON SHEET A2.01 AND E2.1. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-04-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-18 |
Time |
18:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-19 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2002-04-19 00:00:00 | ***************** UNSAT!**************** | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | AND MAKE NECESSARY CORRECTIONS AND | | | RESUBMIT FOR REVIEW: | | | | | | 1} THERE ARE DISCREPANCIES IN THE TYPES | | | OF UNITS LOCATED ON THE NORTH-WEST SIDE | | | OF THE BUILDING.SHEET A2.02 INDICATES | | | THE UNITS ARE TYPE"F"&"D",SHEET A2.03 | | | INDICATES THEY ARE TYPES"C"&"F" AND | | | E3.3 THEM AS"C"&"D".ALSO ON E3.3 THE"E" | | | UNITS AREN'T LABELED. | | | | | | 2} THE METER CENTER MAIN #1 LOAD | | | SUMMARY ON SHEET E6.1 LISTS ONLY 17 | | | UNITS.PLEASE CLARIFY WHICH UNITS ARE | | | NOT INCLUDED,LIST THEM AND PROVIDE LOAD | | | CALCULATIONS ON THE SUMMARY SHEET FOR | | | SAME. | | | | | | 3} ON SHEET E6.1,PANEL"LHP",CIRCUIT #'S | | | 12-14,28-30,38-40 THE OCP IS INCORRECT | | | FOR THE CONDUCTOR SIZE.THE"A"UNITS | | | PANELS CIRCUIT#13-15 IS ALSO INCORRECT. | | | | | | 4} PANEL "LHP" CIRCUIT #36 DOES NOT | | | CORRELATE TO SHEET E3.1 WHERE IT IS | | | SHOWN SERVING THE HALL RECEPTACLE | | | CIRCUIT. | | | | | | 5} THE HALL LIGHTING ON SHEET E2.1 NEEDS | | | A 4-WAY SWITCH. | | | | | | 6} THE TYPE"B"UNITS ON SHEETS E2.2 & E2. | | | 3 NEED A SMOKE DETECTOR IN BOTH BEDROOMS | | | PER 2-2.1.1.1 NFPA-72 (1996). | | | | | | 7} CIRCUIT L2-14 IN THE LAUNDRY ROOM | | | SHEET E3.2 IS MISMARKED. | | | | | | 8} SHEET E2.2 UNIT"D"HAS NO SMOKE | | | DETECTRS IN THE STUDY,IF IT IS INTENDED | | | AS A SLEEPING ROOM IT MUST COMPLY WITH | | | 2-2.1.1.1 AS THE 3RD FLOOR UNIT DOES. | | | | | | 9} PLEASE NOTE THE LOCATION OF THE SMOKE | | | DETECTORS IN UNIT TYPES"A","C"&"E" WITH | | | RESPECT TO THE KITCHENS IN THESE UNITS. | | | IF THESE WERE MOVED FURTHER FROM THE | | | KITCHEN, ESPECIALLY GIVEN THE FACT OF | | | THE DROPPED SOFFITS,IT COULD HELP | | | REDUCE THE THE PROBABILITY OF NUISANCE | | | ALARMS. | | | | | | 10} PLEASE VERIFY THE DIMENSIONS OF THE | | | MECHANICAL ROOM. | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659/8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-01-17 |
Time |
10:18 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | PER MEC 1/16/03 LS |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-09-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-02 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-09-03 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2002-09-03 00:00:00 | 1) EXISTING FIRE EXIT STAIR IS NOT | | | TO BE REMOVED. IT CAN BE REPLACED | | | WITH ANOTHER ONE SO LONG AS IT | | | COMPLIES WITH ALL APPROPRIATE | | | BUILDING AND FIRE CODE REQUIREMENTS. | | | THIS EXISTING DEVICE CANNOT BE REMOVED | | | AS A DEAD-END CORRIDOR WOULD EXIST | | | THAT EXCEEDS CODE REQUIREMENTS. | | | | | | 2) ENSURE ALL DEVICES ARE PLACED | | | ON THE BUILDING'S PROPERTY NOT | | | SOMEONE ELSE'S. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-02 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-02 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2002-07-02 00:00:00 | 1. PLEASE PROVIDE A COPY OF A SURVEY TO | | | THIS OFFICE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-30 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-30 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | 1) MERCANTILE TENANT SPACES ARE TO BE | | | PROPERLY FIRE RATED FROM ONE ANOTHER BY | | | AT LEAST ONE HOUR. | | | 2) NOTES INDICATE ON PAGE A2.01 | | | INDICATES A 13R FIRE SPRINKLER SYSTEM. | | | THE MERCANTILE OCCUPANCIES MUST BE | | | PROTECTED IN ACCORDANCE WITH NFPA 13. | | | 3) THE EXISTING FIRE EXIT STAIR "TO BE | | | REMOVED OR REPLACED WITH COMPLYING | | | STAIRS". THE EXISTING STAIRWAY MUST | | | BE COMPLIANT WITH ALL OF THE | | | REQUIREMENTS FOR EXITING FROM THE | | | BUILDING AND FIRE CODES. THE STAIR | | | CANNOT BE REMOVED BECAUSE A DEAD-END | | | CONDITION IS EVIDENT. | | | 4) WITH REGARDS TO THE EXTERIOR STAIRS, | | | HOW IS EXIT DISCHARGE ACCOMPLISHED. | | | DOES EXITING OCCUR ON THE SAME PROPERTY, | | | SOMEONE ELSE'S PROPERTY, OR ALLEY. | | | PLEASE EXPLAIN. | | | 5) FIRE ALARM NOTES INDICATE CLASS B, | | | STYLE C CIRCUITS. ONLY CLASS A, STYLE D | | | CIRCUITS ARE ALLOWED. | | | 6) EXIT DOORS FOR THE MERCANTILE | | | OCCUPANCIES, DO THEY OPEN ONTO THE | | | SAME PROPERTY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-01-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-02 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-01-02 |
Time |
12:17 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-09-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-09-03 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2002-09-03 |
Time |
16:52 |
Sent To |
B |
|
| Notes |
| 2002-09-03 00:00:00 | | | | APPROVED BY BUILDING OFFICAL "ALTERNATE | | | MEANS & METHODS" AS PER FIELD INSPECTION | | | BY LUIS MARTINEZ, BILL STAPLES, & NEIL | | | MELICK. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
|
Date |
2002-04-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-26 |
Time |
08:58 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-04-26 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2002-04-26 00:00:00 | MECHANICAL PERMIT 01020462 | | | | | | | | | AS PER THE COUNTYWIDE AMMENDMENTS TO THE | | | 1997 SMC 610.1.3 #2, WHERE BRANCH DUCTS | | | CONNECT TO RETURN RISERS IN WHICH THE | | | AIR IS UPWARD IN THE SUBDUCT, RISER | | | SHALL BE CARRIED UP AT LEAST 22" INSIDE | | | THE SUBDUCT.SUBDUCT MUST BE A MINIMUM | | | OF 26 GA. GALVANIZED OR EQUIVALENT. | | | RISERS WHICH ARE SUBJECT TO MOISTURE | | | SHALL BE LINED WITH SUITABLE MATERIAL | | | TO PREVENT DETERIORATION OF DRYWALL | | | ENCLOSURE.EACH UNIT SHALL HAVE A | | | BACKDRAFT DAMPER AS TO PREVENT | | | INFLITRATION CAUSED BY PRESSURE | | | DIFFERNTIAL. | | | | | | PLAN SHEET A9.01 DETAIL #3, 1 HOUR | | | RATED SHAFT UL 415.UL415 IS FOR A NON | | | BEARING WALL NOT A 1 HR SHAFT.PLEASE | | | CORRECT. | | | | | | CHECK WITH NANCY - | | | PLAN SHEET M-2 O.A. FROM THE FIRST FL TO | | | THE AHU FD AT PENETRATION AHU 5 SUPPLY | | | TO CORRIDOR FD IN SUP & RET. | | | | | | PLAN SH M-3 AHU 4 SUP & RET TO CORRIDOR | | | & STAIRWELL BOTH HAVE FIRE DAMPERS.COR | | | RIDOR RADIANT DAMPERS IN CEILING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-02-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-22 |
Time |
11:05 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-02-22 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2002-02-22 00:00:00 | | | | PROVISO UNDER PERMIT 00110504 (CLOSED) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-09-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-09-10 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-09-10 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2002-09-10 00:00:00 | PASSED/PROVISO | | | | | | LETTER WITH ROOF DRAIN CALCULATIONS TO | | | BE DELIVERED 9-16-02 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2002-07-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-09 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-09 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2002-07-09 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) FROM PREVIOUS REVIEW: PLEASE SHOW ALL | | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | | LOCATION AND SQ FT FOR ALL DRAINS, SIZE | | | OF DOWNSPOUTS. SHOW TOTAL SIZE OF ROOF | | | BEING DRAINED, ADD 1/2 AREA OF ALL VERT- | | | ICAL WALLS. PLEASE SUBMIT CALCULATIONS. | | | - RESPONSE NOTED, BUT INFORMATION NOT | | | SUFFICIENT. DOWNSPOUTS AND SECONDARY | | | DRAINS NOT FOUND ON ARCHITECTURAL PLANS | | | AS STATED IN RESPONSE. | | | 2) SHTS P6.1/P6.2 WATER RISER DIAGRAM. | | | FROM PREVIOUS REVIEW: WATER HAMMER ARRES | | | TORS SHALL BE LOCATED AT QUICK CLOSING | | | VALVES. (IN KITCHEN - FOR DISHWASHER & | | | ICE MAKER). RESPONSE NOTED, MORE W.H.A'S | | | REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-04-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-18 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-18 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2002-04-18 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SHT PO.1 NOTE #13 AIR CHAMBERS IF IN- | | | STALLED SHALL BE ACCESSIBLE AND RECHARG- | | | ABLE. (SEE ATTACHED SHEET FOR APPROVED | | | AIR CHAMBERS). APPROVED WATER HAMMER | | | ARRESTORS DO NOT REQUIRE ACCESS AND DO | | | NOT REQUIRE TO BE RECHARGED. SUGGEST | | | USING APPROVED WATER HAMMER ARRESTORS. | | | 2) SHT P0.1 SUBMIT MANUFACTURE INFORMAT- | | | ION FOR TANKLESS WATER HEATERS. | | | 3) SHT P3.2 LAUNDRY ROOM HEATER, 1" PAN | | | DRAIN REQUIRED NOT 3/4" AS SHOWN. | | | 4) SHT P3.2 - SHT P5.2 LAUNDRY ROOM | | | FLOOR DRAIN REQUIRED WITH TRAP PRIMER. | | | SPC SEC 409.4.5 | | | 5) SHT P4.1 PLEASE SHOW ALL PRIMARY & | | | SECONDARY ROOF DRAINS. SHOW LOCATION, | | | SQUARE FOOTAGE AREA FOR EACH DRAIN, SIZE | | | OF DRAINS, AND SIZE OF STORM DRAINAGE | | | PIPING. SHOW TOTAL SQUARE FOOTAGE OF | | | ROOF BEING DRAINED. ADD 1/2 AREA OF ALL | | | VERTICAL WALLS AND AREA OF ROOFS DRAIN- | | | ING FROM ABOVE. PLEASE SUBMIT ALL CAL- | | | CULATIONS | | | 6) SHTS P6.1/P6.2 DOMESTIC WATER ISO- | | | METRIC EAST/WEST. WATER HAMMER ARRESTORS | | | SHALL BE LOCATED IN AN "EFFECTIVE RANGE" | | | CLOSE TO FIXTURES, NOT AT TOP OF DROPS | | | AS SHOWN. PDI-WH 201 & MANUFACTURE IN- | | | STALLATION INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-12-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-12-13 |
Time |
09:49 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-13 00:00:00 | PLUMBING PLAN REVIEW, DENIED | | | REFERENCE ORIGINAL PLAN 00110504. | | | PLANS NOT COMPLETE, SHT'S MISSING. | | | SHT, P5.1 DWV, 5 APTS MISSING, | | | T/P TO BE RUN IN A COMMON SYSTEM TO THE | | | OUT SIDE, NOT TO THE SANITARY DRAINS. | | | SHT P0.1 DIELECTRIC UNIONS NOT APPRROVED | | | SHT P0.1 WASHING MACHINE BOX ON A 1 HR | | | RATED WALL. F/F REQUIRED IN LAUNDRY RM. | | | 1" WTR HTR PAN DRAIN REQ. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:55 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-07-06 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-07-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|