Plan Review Details - Permit 01070223
Plan Review Stops For Permit 01070223
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-17 Cont ID  
Sent By dpalmer Date 2001-07-17 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2001-07-17 Time 18:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-13 Cont ID  
Sent By pkrauss Date 2001-09-13 Time 14:32 Rev Time 0.35
Received By pkrauss Date 2001-09-13 Time 12:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-07-14 Cont ID  
Sent By hmoser Date 2001-07-14 Time 11:20 Rev Time 0.33
Received By hmoser Date 2001-07-14 Time 11:19 Sent To  
Notes
2001-07-14 00:00:00PLANS DENIED ENERGY CALC. CALL FOR
 HEAT RECOVERY UNIOT. HEAT RECOVERY IS
 NOT ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-07-10 Cont ID  
Sent By kstevens Date 2001-07-10 Time 13:23 Rev Time 0.33
Received By kstevens Date 2001-07-10 Time 13:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-09-14 Cont ID  
Sent By rmcdouga Date 2001-09-14 Time 15:07 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-09-14 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR 6FT.X 6FT. FIXED GLASS
 WINDOW. THE ONES PROVIDED ARE FOR FIXED
 GLASS WINDOWS WITH MAXIMUM SIZES OF
 5FT.X5FT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-21 Cont ID  
Sent By rmcdouga Date 2001-07-21 Time 11:27 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-21 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) SHEET 1 OF BOTH SETS OF PLANS ARE THE
 ONLY ONES THAT HAVE THE SIGNATURE AND
 RAISED SEAL OF THE ENGINEER. THE OTHER
 SHEETS ARE SIGNED BUT NOT SEALED. PLEASE
 CORRECT.
  
 4) PLEASE INDICATE ON SHEET 3B, THE
 TRUSS ANCHOR THAT WILL BE USED TO ATTACH
 GIRDER TRUSS GT1 ON THE RIGHT SIDE OF
 THE GARAGE AND RESIST THE 5470# UPLIFT
 AND 13,104# LATERAL LOAD.
  
 5) THE WALL SECTION ON SHEET 5 INDICATES
 FOOTER WIDTH OF 12 INCHES AND FOUNDATION
 PLAN HAS 16 INCH WIDTH AND 16 INCH DEPTH
 IN ONE PLACE AND 16 INCH WIDTH AND 12
 INCH DEPTH IN ANOTHER. PLEASE CLARIFY.
  
  
 TRUSSES
 UNSAT
  
 1) THE MEAN ROOF HEIGHT OF THE STRUCTURE
 IS LISTED AS 16 FT. ON SHEET 1 OF THE
 PLANS, HOWEVER THE TRUSS DRAWINGS LIST
 15 FT. AS THE MEAN ROOF HEIGHT (EXCEPT
 PAGES 7 & 8 WHICH DIFFER). PLEASE
 CORRECT.
  
 2) THE TRUSS DRAWINGS LIST SBCCI 97 AS
 THE DESIGN CRITERIA. SBCCI IS THE
 ORGANIZATION. THE DESIGN CRITERIA IS
 CONTAINED IN THE 97 STANDARD BUILDING
 CODE (97 SBC). PLEASE CORRECT.
  
 3) IF USING A COVER OR INDEX SHEET IN
 LIEU OF SIGNING AND SEALING EACH SHEET,
 THE REQUIREMENTS OF 61G15-31.003 MUST BE
 MET. SEE ATTACHED SHEET FOR REQUIREMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-10 Cont ID  
Sent By sgraham Date 2001-07-10 Time 07:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***