Plan Review Details - Permit 01070180
Plan Review Stops For Permit 01070180
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By jwitmer Date 2001-08-06 Time 08:20 Rev Time 11.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070180
 909 EVERNIA ST
  
 COMPLETE PROPERTY MANAGEMENT
 632-1669
  
 1)- FL S S 481./ 61G15-23.002
 SEAL, SIGNATURE & DATE SHALL BE AFFIXED.
  
 2)- SBC 104.2.2 ADD INFO REQUIRED: PER-
 MIT APP INDICATES (2) SURVEYS ATTACHED,
 PLOT PLAN YES BUT NO SURVEY.
  
 3)- ADDRESS: 909 EVERNIA STREET
 PCN # 74-43-43-21-01-042-0060
  
 4) SBC* 1804.2 SOILS TEST REPORT,
 MINIMUM SOIL BEARING VALUE
  
 5)- S S FL 553.79(2)/ 553.79(6) (C):
 FIRE SPRINKLER PLANS REQUIRED FOR 3
 STORY RESIDENTIAL, OVER 50 HEADS WILL
 REQUIRES A DESIGN PROFESSIONAL.
  
 6)- FIRE DISTRICT:REQUIREMENTS MUST BE
 MET FOR FIRE DISTRICT SBC APPENDIX"F".
 ROOF COVERINGS CLASS "A-B"
  
 7)- SBC 104.2.2: MEAN ROOF HEIGTH?
  
 8)- MISSING SURVEY TABLE 600 % OF OPEN-
 INGS CAN'T BE COMPUTED.
  
 9)- SHEET A-5 DETAIL # 1, 1HR. RATED
 WALL ASSEMBLY,NO UL RATING OR GYOSUM ASS
 OCIATION #, SBC 704.1 OCCUPANCY SEPERA-
 TION FOR APARTMENTS.
  
 10)- SBC 704.2.1.4- CORRIDOR PARTITIONS
 1 HR RATING 2ND /3RD FLOOR
  
 11)- SHEET A-2,A-3 CHASE, SBC 705.2.3:
 SHAFT ENCLOSURE, < THAN 4 STORIES 1 HR.
 USAGE?
  
 12)- EXIT STAIRWELLS, TO COMPLY WITH
 DEFINITION OF " MEANSOF EGRESS".
 SBC 1001.1.3.MEANS OF EGRESS SHALL CON-
 SIST OF CONTINUOUS AND UNOBSTRUCTED
 PATHS OF TRAVEL TO THE EXTERIOR OF A
 BUILDING. THE EXIT IS TO BE 1 HR. CONTIN
 UOUS TO THE EXTERIOR, NOT THE PARKING
 AREA UNDER THE BUILDING. SEE THE (2)
 DOORS ON THE 1ST FLOOR LABELED #9 FOR
 MEANS OF EGRESS. SEE SECTION 1010 FOR
 EXIT DISCHARGE.
  
 13)- EXIT STAIRWELL DOORS,SBC705.1.3.2.1
 OPENING PROTECTIVES FIRE RATED DOORS
  
 14)- SHEET A-8 GUTTERS & LEADERS: 1516.1
  
 15)- SBC 1517.6.4.3 OVERFLOWS SEE REQUIR
 ED HEIGTHS.
  
 16)-SBC 2603- ADDITIONAL INFORMATION ON
 THE PREFAB STUCCO BANDS.
  
 17)- SBC 104.2.2 ADD. INFO REQUIRED,
 ATTACHMENT OF FAKE BALCONY, RAILING &
 SILL MEMBER. SBC 1404.
  
 18)- SBC 1507.4 /1705.1 CONCRETE & ROOF
 TILE: OVERTURNING RESISTANCE.
  
 19)- SHEET A-9 DETAIL #9 FRAME TO MASON-
 RY SBC 607 TYPE V CONSTRUCTION: EXTERIOR
 WALLS BEARING & NON BEARING ARE TO BE
 NON-COMBUSTIBLE,
  
 20)- SHEET A-8 DEPICTS THE SAME AREA ADD
 RESSED ABOVE "STORAGE"THE SBC SEC.
 1517.1.1.3: A PENHOUSE, BULKHEAD, OR ANY
 OTHER SIMILAR PROJECTION ABOVE THE ROOF
 SHALL NOT BE USED FOR PURPOSES OTHER
 THAN SHELTER OF MECHANICAL EQUIPMENT OR
 SHELTER OF VERTICAL SHAFT OPENINGS IN
 THE ROOF. PENTHOUSES OR BULKHEADS USED
 FOR PURPOSES OTHER THAN PERMITTED BY
 THIS SECTION SHALL CONFORM TO THE
 REQUIREMENTS OF THIS CODE FOR AN ADDITIO
 NAL STORY.
  
 21)- STRUCTURAL SHEET S-6 NOTE 1.02: NOT
 SHOWN TABLE 1604.1, RES. MULTI-FAMILY
 LIVE LOADS,PUBLIC ROOMS: 100
 CORRIDORS:80
  
 22)- WIND ZONES : ROOFING T 1606.2E
 WALL / END ZONES 1606.2.C
 SHOW POSITIVE AND NEGATIVE PRESSURES FOR
 ALL OPENINGS.
  
 23)- SBC 1606.2.6.2COMPONENTS & CLADDING
 PROVIDE (2) COPIES OF ALL PRODUCT APPROV
 ALS FOR GLAZED OPENINGS, DOORS. SBCCI OR
 DADE COUNTY PRODUCT APPROVAL REPORTS ARE
 ACCEPTED.
  
 24)- SBC 1606.4.1/1707.4.1 STORM SHUTTER
 REQUIREMENTS SEE CITY POLICY #14.
  
 25)- DISCREPANCY STRUCTURAL STAIRS:
 SHEET S-7 LONGITUDINAL STEEL STAIRS INDI
 CATE 4'-0" WIDE DETAIL DEPICTS 3/35'S &
 2#5'S.
 LANDINGS ARE 8'-0" X 4'X0", WITH 4#5 E.W
 THIS PUTS THE STEEL 2'-0" O.C.?
  
 26)- SHEET S-7 DETAIL "D",SBC 1015.3
 OPENINGS EXCEPTION(2) A 6" SPHERE CAN
 NOT PASS THROUGH THE TRIANGULAR OPENING
 FORMED BY THE RISER,TREAD & GUARDRAIL.
  
 27)- SBC 1204.2 PUBLIC RESTROOMS, FLOOR
 AND WALLS ARE TO BE LINED WITH AN NON-
 ABSORBANT MATERIALS TO A HEIGHT OF 4'-0"
  
 28)- SBC 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION SEE TABLE 803.3.
  
 29)- PARKING GARAGES: PARKING SURFACES
 CONCRETE OR SIMILAR SURFACES, NONCOMBUST
 IBLE & NONABSORBANT.SBC 411.2.5.
  
 30)- DEMONSTRATE THE COMPLIANCE OF OPEN
 PARKING GARAGES 411.3.2. 411.4.2ENCLOSED
 PARKING GARAGES: 6 AIR CHANGES OF AIR
 PER HOUR.
  
 THESE IS NOT ENOUGH INFORMATION TO DO
 A THOROUGH REVIEW AT THIS TIME.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By dpalmer Date 2001-08-02 Time 09:10 Rev Time 0.00
Received By dpalmer Date 2001-08-02 Time 09:10 Sent To  
Notes
2001-08-02 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED, DATED, SEALED PER FS/FAC
 471.025.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL.
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-07-06 Cont ID  
Sent By mamini Date 2001-07-06 Time 11:13 Rev Time 3.00
Received By mamini Date 2001-07-06 Time 11:12 Sent To  
Notes
2001-07-06 00:00:00FAILED:
 1. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY CITY OR IF IT IS PRIVATE
 PICK UP, IF TO BE PICKED UP BY THE CITY
 THEN THE DUMPSTER LOCATION AND
 DIMENSIONS SHOULD BE PER CITY
 REQUIREMENTS.
 2. AN APPROVED BACKFLOW PREVENTER ASS.
 ON ALL CROSS CONNECTIONS IS REQUIRED.
 3. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN THE SANITARY SEWER LATERAL, ON THE
 PROPERTY, AT THE BACK OF THE SIDEWALK.
 4. ANY NEW CONNECTION TO CITY' SERVICES
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT, 659-8040
 5. ANY WORKS WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT THROUGH OFFICE
 OF CITY ENGINEER, 659-8040
 6. PLEASE SHOW ALL THE LOCATIONS FOR
 CONNECTIONS TO CITY SERVICES.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT.8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 19:08 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 19:08 Sent To  
Notes
2001-07-05 00:00:001) FIRE HYDRANT LOCATIONS NOT SHOWN ON
 SITE PLAN. WHERE IS BACKFLOW DEVICE.
 2) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. PLEASE BE ADVISED THAT FS 553.895
 REQUIRES ANY BUILDING THREE OR MORE
 STORIES IN HEIGHT REGARDLESS OF
 OCCUPANCY BE PROVIDED WITH AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
 3) PLEASE PROVIDE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM
 INSTALLATION. FIRE ALARM SYSTEM TO BE
 CLASS A OR FULLY ADDRESSABLE. CUT
 SHEETS, WIRING DIAGRAMS AND BATTERY
 CALCULATIONS ARE TO BE PROVIDED.
 4) SMOKE DETECTORS WITHIN APARTMENTS
 ARE TO BE ELECTRICAL AND BE LOCATED
 NO CLOSER THAN 3 FEET AWAY FROM
 AIR CONDITIONER DIFFUSERS.
 5) SEPARATE PERMIT REQUIRED FOR FIRE
 ALARM INSTALLATION.
 6) EXIT DOORS INTO STAIRWELLS SHOULD
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 7) STAIR TREADS ARE TO BE AT LEAST 11"
 AS REQUIRED BY THE LIFE SAFETY CODE,
 1985 EDITION.
 8) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS OF THE BUILDING.
 9) STAIRWELL DOORS ARE TO BE AT LEAST
 C LABELED (45 MINUTE) FIRE DOORS
 WITH CLOSERS.
 10) ALL RATED FIRE DOORS ARE TO BE
 INSTALLED IN FIRE RATED FRAMES AND
 BE EQUIPPED WITH SELF-CLOSING DEVICES
 THAT CAUSE THE DOORS TO LATCH.
 11) CLEARLY IDENTIFY ALL FIRE RATED
 SEPARATIONS BETWEEN TENANTS, PARKING,
 ETC.
 12) PLEASE IDENTIFY FIRE EXTINGUISHER
 LOCATIONS WITHIN BUILDING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-09-12 Cont ID  
Sent By pkrauss Date 2002-09-12 Time 10:54 Rev Time 0.00
Received By pkrauss Date 2001-08-01 Time 10:22 Sent To  
Notes
2001-08-01 00:00:00********************DENIED**************
  
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH
 MACHANICAL PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-23 Cont ID  
Sent By jleech Date 2001-07-23 Time 07:14 Rev Time 4.00
Received By jleech Date 2001-07-23 Time 07:14 Sent To  
Notes
2001-07-23 00:00:00DENIED;
  
 1.PAGE A-1 PUBLIC RESTROOMS; SHOW TURN-
 ING CIRCLE.
 2.SHOW COMPLIANCE TO 94 SPC TABLE 407.
 MINIMUM BATHROOM FACILITIES.
 3.PAGE P-1 NOTE 7 MECHANICAL WATER
 HAMMER ARRESTERS SHALL COMPLY WITH
 SPC SEC 607.8.2 AND INSTALLED PER
 MANUFACTOR'S SPECIFCATIONS.
 4.WASHING MACHINES SHALL NOTE CONNECT
 TO A 2" CROSS. SEC. 409.12.3 RECOMMEND
 3" PIPE.
 5.FLOOR DRAINS REQUIRED IN LAUNDRY ROOM
 WITH TRAP PRIMERS.
 6.PAGE P-4 NOTE 19 FIRE PROTECTION.
 PLEASE SUBMIT MANUFACTORS SPECIFICA-
 TIONS AND GIVE UL LISTING NUMBER.
 7.SHOW DOMESTIC WATER RISER.
 8.SHOW ROOF DRAIN RISER DIAGRAM.
 9.PAGE A-8 ROOF DRAINS. CALCULATE SQUARE
 FOOTAGE FOR EACH DRAIN AND SIZE PIPE
 PER CHAPTER 11.
 10.SHOW WATER PIPE ON P-2 AND 3.
 11.SITE PLAN GIVES NO INFORMATION.
 A.SHOW WATER LOCATION AND SIZE
 SHOW BACKFLOW.
 B.SEWER WHERE AND WHAT SIZE?
 C.STORM WHERE DOES RAIN WATER GO?
  
 FAIR HOUSING ACT NOTES;
 1.SPECIFY ON DRAWING IF PLANS ARE TO
 COMPLY WITH SPECIFICATION "A" OR "B".
 2.DOOR OPENINGS TO BATHROOMS MUST HAVE
 A CLEAR DOOR OPENING OFV 32".
 3.SHOW CLEAR FLOOR SPACE FOR BATHROOM
 FIXTURES AND KITCHEN APPLIACES.
 4.SHOW REINFORCED WALLS FOR LATER
 INSTALLATION OF GRAB BARS.
 5.UNIT A PAGE A-4 WHAT IS THE DIMENSION
 BETWEEN CABINETS IN KITCHEN. SEE SEC.
 7.9.
 6.UNIT D BATHROOM DOES NOT COMPLY WITH
 FHA REQUIREMENTS. SEE EXAMPLE B PAGE
 7.36. ALSO KITCHEN SINK, AN ADAPTIBLE
 CABINET WILL BE REQUIRED SINCE THERE
 IS NOT ENOUGH ROOM FOR A PARALLEL
 APPROACH. PLEASE SHOW DETAIL.
 7.UNIT B DOES NOT COMPLY. SEE EXAMPLE B
 PAGE 7.37.
 8.UNIT H SAME AS B SEE PLAN REVIEW NOTE
 7.
 9.SHOW DETAIL OF TOILET. WHAT SIDE IS
 18"S AND A TOTAL OF 33"S CLEARANCE.
 SEE FHA 7.43
 10.IF UNIT G IS AN OFFICE BATHROOM AND
 KITCHEN SHALL COMPLY WITH FACBC IF
 IT WILL BE A MANAGERS APT. IT SHALL
 COMPLY WITH FHA REQUIREMENTS.
 11.LAUNDRY ROOMS SHALL COMPLY WITH FHA
 2.26.
  
 PLUMBING PLAN REVIEW NOTES BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***