| 2001-08-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01070180 |
| | 909 EVERNIA ST |
| | |
| | COMPLETE PROPERTY MANAGEMENT |
| | 632-1669 |
| | |
| | 1)- FL S S 481./ 61G15-23.002 |
| | SEAL, SIGNATURE & DATE SHALL BE AFFIXED. |
| | |
| | 2)- SBC 104.2.2 ADD INFO REQUIRED: PER- |
| | MIT APP INDICATES (2) SURVEYS ATTACHED, |
| | PLOT PLAN YES BUT NO SURVEY. |
| | |
| | 3)- ADDRESS: 909 EVERNIA STREET |
| | PCN # 74-43-43-21-01-042-0060 |
| | |
| | 4) SBC* 1804.2 SOILS TEST REPORT, |
| | MINIMUM SOIL BEARING VALUE |
| | |
| | 5)- S S FL 553.79(2)/ 553.79(6) (C): |
| | FIRE SPRINKLER PLANS REQUIRED FOR 3 |
| | STORY RESIDENTIAL, OVER 50 HEADS WILL |
| | REQUIRES A DESIGN PROFESSIONAL. |
| | |
| | 6)- FIRE DISTRICT:REQUIREMENTS MUST BE |
| | MET FOR FIRE DISTRICT SBC APPENDIX"F". |
| | ROOF COVERINGS CLASS "A-B" |
| | |
| | 7)- SBC 104.2.2: MEAN ROOF HEIGTH? |
| | |
| | 8)- MISSING SURVEY TABLE 600 % OF OPEN- |
| | INGS CAN'T BE COMPUTED. |
| | |
| | 9)- SHEET A-5 DETAIL # 1, 1HR. RATED |
| | WALL ASSEMBLY,NO UL RATING OR GYOSUM ASS |
| | OCIATION #, SBC 704.1 OCCUPANCY SEPERA- |
| | TION FOR APARTMENTS. |
| | |
| | 10)- SBC 704.2.1.4- CORRIDOR PARTITIONS |
| | 1 HR RATING 2ND /3RD FLOOR |
| | |
| | 11)- SHEET A-2,A-3 CHASE, SBC 705.2.3: |
| | SHAFT ENCLOSURE, < THAN 4 STORIES 1 HR. |
| | USAGE? |
| | |
| | 12)- EXIT STAIRWELLS, TO COMPLY WITH |
| | DEFINITION OF " MEANSOF EGRESS". |
| | SBC 1001.1.3.MEANS OF EGRESS SHALL CON- |
| | SIST OF CONTINUOUS AND UNOBSTRUCTED |
| | PATHS OF TRAVEL TO THE EXTERIOR OF A |
| | BUILDING. THE EXIT IS TO BE 1 HR. CONTIN |
| | UOUS TO THE EXTERIOR, NOT THE PARKING |
| | AREA UNDER THE BUILDING. SEE THE (2) |
| | DOORS ON THE 1ST FLOOR LABELED #9 FOR |
| | MEANS OF EGRESS. SEE SECTION 1010 FOR |
| | EXIT DISCHARGE. |
| | |
| | 13)- EXIT STAIRWELL DOORS,SBC705.1.3.2.1 |
| | OPENING PROTECTIVES FIRE RATED DOORS |
| | |
| | 14)- SHEET A-8 GUTTERS & LEADERS: 1516.1 |
| | |
| | 15)- SBC 1517.6.4.3 OVERFLOWS SEE REQUIR |
| | ED HEIGTHS. |
| | |
| | 16)-SBC 2603- ADDITIONAL INFORMATION ON |
| | THE PREFAB STUCCO BANDS. |
| | |
| | 17)- SBC 104.2.2 ADD. INFO REQUIRED, |
| | ATTACHMENT OF FAKE BALCONY, RAILING & |
| | SILL MEMBER. SBC 1404. |
| | |
| | 18)- SBC 1507.4 /1705.1 CONCRETE & ROOF |
| | TILE: OVERTURNING RESISTANCE. |
| | |
| | 19)- SHEET A-9 DETAIL #9 FRAME TO MASON- |
| | RY SBC 607 TYPE V CONSTRUCTION: EXTERIOR |
| | WALLS BEARING & NON BEARING ARE TO BE |
| | NON-COMBUSTIBLE, |
| | |
| | 20)- SHEET A-8 DEPICTS THE SAME AREA ADD |
| | RESSED ABOVE "STORAGE"THE SBC SEC. |
| | 1517.1.1.3: A PENHOUSE, BULKHEAD, OR ANY |
| | OTHER SIMILAR PROJECTION ABOVE THE ROOF |
| | SHALL NOT BE USED FOR PURPOSES OTHER |
| | THAN SHELTER OF MECHANICAL EQUIPMENT OR |
| | SHELTER OF VERTICAL SHAFT OPENINGS IN |
| | THE ROOF. PENTHOUSES OR BULKHEADS USED |
| | FOR PURPOSES OTHER THAN PERMITTED BY |
| | THIS SECTION SHALL CONFORM TO THE |
| | REQUIREMENTS OF THIS CODE FOR AN ADDITIO |
| | NAL STORY. |
| | |
| | 21)- STRUCTURAL SHEET S-6 NOTE 1.02: NOT |
| | SHOWN TABLE 1604.1, RES. MULTI-FAMILY |
| | LIVE LOADS,PUBLIC ROOMS: 100 |
| | CORRIDORS:80 |
| | |
| | 22)- WIND ZONES : ROOFING T 1606.2E |
| | WALL / END ZONES 1606.2.C |
| | SHOW POSITIVE AND NEGATIVE PRESSURES FOR |
| | ALL OPENINGS. |
| | |
| | 23)- SBC 1606.2.6.2COMPONENTS & CLADDING |
| | PROVIDE (2) COPIES OF ALL PRODUCT APPROV |
| | ALS FOR GLAZED OPENINGS, DOORS. SBCCI OR |
| | DADE COUNTY PRODUCT APPROVAL REPORTS ARE |
| | ACCEPTED. |
| | |
| | 24)- SBC 1606.4.1/1707.4.1 STORM SHUTTER |
| | REQUIREMENTS SEE CITY POLICY #14. |
| | |
| | 25)- DISCREPANCY STRUCTURAL STAIRS: |
| | SHEET S-7 LONGITUDINAL STEEL STAIRS INDI |
| | CATE 4'-0" WIDE DETAIL DEPICTS 3/35'S & |
| | 2#5'S. |
| | LANDINGS ARE 8'-0" X 4'X0", WITH 4#5 E.W |
| | THIS PUTS THE STEEL 2'-0" O.C.? |
| | |
| | 26)- SHEET S-7 DETAIL "D",SBC 1015.3 |
| | OPENINGS EXCEPTION(2) A 6" SPHERE CAN |
| | NOT PASS THROUGH THE TRIANGULAR OPENING |
| | FORMED BY THE RISER,TREAD & GUARDRAIL. |
| | |
| | 27)- SBC 1204.2 PUBLIC RESTROOMS, FLOOR |
| | AND WALLS ARE TO BE LINED WITH AN NON- |
| | ABSORBANT MATERIALS TO A HEIGHT OF 4'-0" |
| | |
| | 28)- SBC 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION SEE TABLE 803.3. |
| | |
| | 29)- PARKING GARAGES: PARKING SURFACES |
| | CONCRETE OR SIMILAR SURFACES, NONCOMBUST |
| | IBLE & NONABSORBANT.SBC 411.2.5. |
| | |
| | 30)- DEMONSTRATE THE COMPLIANCE OF OPEN |
| | PARKING GARAGES 411.3.2. 411.4.2ENCLOSED |
| | PARKING GARAGES: 6 AIR CHANGES OF AIR |
| | PER HOUR. |
| | |
| | THESE IS NOT ENOUGH INFORMATION TO DO |
| | A THOROUGH REVIEW AT THIS TIME. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |