| Plan Review Stops For Permit 01070072 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-08-22 |
Time |
13:40 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | | | | AS BUILTS/ REVIEWED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2002-08-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-08-15 |
Time |
05:55 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2002-08-15 |
Time |
05:55 |
Sent To |
|
|
| Notes |
| 2002-08-15 00:00:00 | PLEASE INDICATE REVISIONS OR PREVIOUS | | | REVISIONS WITH AN INDICARION AS DELTA, | | | CLOUDS,OR OTHER IDENTIFIABLE SYMBLE. | | | IN GOING OVER PART OF PLANS THERE ARE | | | PREVIOUS REVISIONS THAT ARE NOT NOW | | | SHOWN. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-06-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-06-29 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-06-29 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2002-06-29 00:00:00 | 1) TRUSS SUBMITTALS | | | 2) RAILINGS/ PAVERS | | | 3) DELETION OF SHAFT WALL @ NE SE STAIR- | | | WELL(MECHANICAL) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-13 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-06-29 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | TRUSS ENGINEERING: | | | 1) THE DESIGN PROFESSIONAL SHALL REVIEW | | | AND APPROVE BEFORE SUBMITTAL TO THE | | | BUILDING DEPARTMENT. | | | | | | 2) THE BUILDING WAS DESIGNED UNDER THE | | | 1997 STANDARD BUILDING CODE, ASCE 7-95, | | | THE TRUSS ENGINEERING INDICATES ASCE | | | 7-98. | | | | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-03 |
Time |
15:44 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-10-03 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | PROVISO: SUBMIT PRODUCT APPROVAL REPORTS | | | | | | 1)- FENESTRATION TESTING LABS REQUIRE | | | SITE SPECIFIC CERTIFICATION | | | | | | 2)- ARCH ALUM IMPACT WALL 3000 SYSTEM | | | EXPIRED A CURRENT REPORT SHALL BE | | | REQUIRED. | | | | | | (3) COPIES OF PRODUCT TESTING REPORTS | | | ARE REQUIURED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-02 |
Time |
14:05 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2001-10-02 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2001-10-02 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01070072 | | | 1000 S DIXIE | | | FINFROCK CONSTRUCTION | | | (407) 293-4000 | | | | | | 1)- PRODUCT APPROVAL | | | A) FENESTRATION TESTING LAB - WILL | | | REQUIRE SITE SPECIFIC CERTIFICATION | | | B) ARCH ALUM IMPACT WALL 3000 REPORT | | | EXPIRED | | | C) NO ROOFING REPORT, FOR ROOFING | | | ASSEMBLY | | | | | | 2)- ENERGY CALCULATION (2) SETS TO BE | | | SIGNED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-09-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-04 |
Time |
14:03 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-09-04 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2001-09-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01070072 | | | 1000 S. DIXIE HWY | | | FINFROCK CONSTRUCTION | | | (407) 293-4000 | | | | | | SBC= STANDARD BUIULDING CODE | | | SBC*= 1997 AMENDMENTS STANDARD BUILDING | | | CODE | | | | | | 1)- SHEET A803 NOTES 1&2 GLAZED OPENINGS | | | ARE TO MEET THE STANDARD BUILDING CODE | | | FOR DETERMINING IMPACT RESISTANCE FROM | | | WINDBORNE DEBRIS, SEE SSTD-12-97. THE | | | CITY DOES RECONIZE THE DADE COUNTY PRO- | | | DUCT TESTING REPORTS. | | | | | | 2)- SHEETS A3-302 THE DETAIL INDICATES | | | THERE IS A LAUNDRY WITH DRYERS, THE MISS | | | ING INFORMATION ON THE CHASE FOR THE DRY | | | ER VENTS. RESPONCE SEE HILL-YORK DRAW- | | | INGS. SHEET AC-5 DOES NOTE THAT THERE | | | WILL BE A 2 HR. CHASE BY G. C.WHAT IS | | | THE U.L. LISTING OR GYPSUM ASS.#? | | | | | | 3)- SBC 1606.4.1 / 1707.4.1 THE CODE RE- | | | QUIRES GLAZED OPENINGS TO HAVE LARGE | | | MISSLE IMPACT TESTING FOR THE FIRST 30' | | | OF ELEVATION, ABOVE THIS HEIGHT WILL BE | | | SMALL IMPACT TESTING REQUIRED. A PROVISO | | | CAN BE WRITTEN THOUGH A SEPERATE PERMIT | | | AND FEES WILL BE REQUIRED.(3 COPIES OF | | | REPORT WILL BE REQUIRED. | | | | | | 4)- SBC 1606.2.6.2/ 1707.5 CLAY TILE & | | | CEMENT TILE WILL ALSO REQUIRE THE PRO- | | | DUCT TESTING REPORTS (3 COPIES). | | | | | | 5)- FLORIDA STATE STATUTE553.79 (5)(A) | | | THRESHOLD BUILDING INSPECTION PLAN FROM | | | THE ENGINEER OR ARCHETECT OF RECORD WILL | | | BE REQUIRED BEFORE THE ISSUANCE OF THE | | | BUILDING PERMIT. THE PURPOSE OF THE | | | STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND | | | SCHEDULES SO THAT THE BUILDING CAN BE | | | ADEQUATELY INSPECTED FOR COMPLIANCE WITH | | | THE PERMITTED DOCUMENTS. | | | | | | 6)- THREE SETS OF PLANS WILL BE REQUIRED | | | BEFORE THE ISSUANCE OF THE PERMIT. | | | | | | 7)- PLANS WILL NEED COUNTY IMPACT FEE | | | STAMP AND RECEIPT. | | | | | | 8)- RADON FEES TO CITY $2323.54 | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-30 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-06-29 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2001-07-30 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01070072 | | | 1000 S DIXIE HWY | | | FINFROCK CONSTRUCTION | | | (407) 293-4000 | | | | | | SBC = STANDARD BUILDING CODE 1997 EDI. | | | SBC* = 1997 AMENDMENTS STANDARD BUILDING | | | CODE | | | 1)- SHEET A-803 NOTES 1 & 2 GLAZED OPEN- | | | INGS ARE TO MEET THE STANDARD BUILDING | | | CODE STANDARD FOR DETERMINING IMPACT | | | RESISTANCE FROM WINDBORNE DEBRIS, SEE | | | SSTD-12-97. THE CITY DOES ACCEPT THE | | | DADE COUNTY PRODUCT APPROVAL. | | | | | | 2)- FL ACCESSIBILITY CODE 4.6.4: | | | SIGNAGE FOR HANDICAPPED VANS. | | | | | | 3)- SHEET A-C 9 SIZE OF BOILER? SBC 704. | | | 1.3.3.3. | | | | | | 4)_ SHEET A-302 DETAILS 3,5 & 6 ALL | | | DETAILS INDICATE A SOLID BLUE LINE, IS | | | THIS A VOID FOR UTILITIES? | | | | | | 5)- SHEET A-302 THE DETAILS INDICATE | | | THERE IS A LAUNDRY WITH DRYERS, MISSING | | | | | | INFORMATION ON THE CHASE FORTHE DRYER | | | VENTS? | | | | | | 6)- SHEET A-504 SEC. A INDICATES THERE | | | WILL BE ROOF SHEATHING, THE PLANS DO | | | NOT INDICATE WHAT TYPE OF SHEATHING IS | | | TO BE USED, THICKNESS, ETC. | | | | | | 7)- ROOM 1-003 UNDER RAMP STORAGE: | | | 2,740 SQ FT & TRAVEL DISTANCE 80',THE | | | SBC 1027.1.1 SINGLE EXIT REQUIREMENTS: | | | 2500 MAX SQ FT, TRAVEL DISTANCE NOT TO | | | EXCEED 50'. | | | | | | 8)- SBC 411.3 OPEN PARKING GARAGE : SHOW | | | CALCULATIONS FOR OPEN WALL AREA, DETER- | | | MINATION METHOD #1 OR #2. | | | | | | 9)- STRUCTURAL DRAWINGS ARE NOT COMPLETE | | | THEY DO NOT SHOW DETAILS PAST THE FIRST | | | FLOOR, MISSING WELDING INFORMATION FOR | | | CONNECTING PLATES, LOCATION, DIRECTION | | | AND MAGNITUDE OF LOADS TO BE RESISTED. | | | | | | 10)- SBC 1606.4.1 /1707.4.1 THE CODE | | | REQUIRES GLAZED OPENINGS TO HAVE LARGE | | | MISSLE TESTING,PRODUCT TESTING REPORTS | | | ARE REQUIRED TO SHOW COMPLIANCE, A NOTE | | | ON THE DRAWINGS INDICATING WHAT WILL BE | | | DONE DOES SHOW INTENT, A PROVISO CAN BE | | | WRITTEN FOR THIS SECTION OF THE CODE. | | | SINCE THE WINDOWS AND DOORS WOULD BE RE- | | | VIEWED AT A LATER DATE THEYWOULD BE | | | UNDER A SEPERATE PERMIT WITH ASSOCIATED | | | FEES. | | | | | | 11)- SBC 1606.2.6.2/ 1707.5 CLAY TILE & | | | CEMENT TILE WILL ALSO REQUIRE THE PRODUC | | | T TESTING REPORTS (2 COPIES REQUIRED) | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
N |
Date |
2002-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-30 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-30 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2002-07-30 00:00:00 | *************** NOTE ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT NONE OF THE | | | ELECTRICAL SHEETS IN EITHER STE ARE | | | SIGNED AND SEALED. PER FS/471.025 | | | | | | 2)NOTE: PLEASE NOTE THAT AS PER CONVER- | | | -SATION WITH ENGINEER. ALL PREVIUOUS | | | REVS WERE SUBMITTED AND REVIEW, | | | | | | IF THERE AREN ANY QUESTIONS, PLEASE CALL | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2002-07-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-29 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-07-29 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2002-07-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-26 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-07-26 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2002-07-26 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | THE FIRE PUMP HP ON THE PLAN IS NOT | | | WHAT IS INSTALLED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-28 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-28 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
20:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-01 |
Time |
20:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-17 |
Time |
22:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-17 |
Time |
22:11 |
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASENOTE THAT NOTES FROM | | | FIRST REVIEW. | | | | | | 2)NOTE: PLEASE ADDRESS AND SUBMIT FOR | | | REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-31 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-30 |
Time |
21:33 |
Sent To |
|
|
| Notes |
| 2001-07-31 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT NO GFI PROTECT- | | | -ION OF MDP AND MCC IS SHOWN. PLEASE | | | NOTE THAT 230-95 REQ`SPROTECTION | | | FOR 1000A`S OR MORE OVER 150V TO GRND. | | | | | | 2)NOTE: PLEASE NOTE THAT CONDUCTOR FEED- | | | ING MDP DO NOT MEET 240-3-C. PLEASE | | | NOTE THAT CONDUCTORS ARE TO BE SIZED | | | PER 310-16 75'COL. PER 110-14 | | | | | | 3)NOTE: PLEASE CLARIFY OCP IN MOTOR | | | CONTRLOLLER PER 695-3-1, PLEASE ASLO | | | NOTE GROUPING OF DISCS REFERENCED BY | | | SAME ART TO 230-72B. PLEASE SEE 695-4B-1 | | | PLEASE SUBMIT CODE LETTER OF MOTOR. | | | 4)NOTE: PLEASE PROVIDE CLARIFICATION | | | OF DISCONNECTINGS MEANS OF GENERATOR | | | GROUPED WITH MAIN PER 230-70 AND 230-72. | | | PLEASE NOTE THAT MUST MEET 230-76 AND | | | 230-79. | | | | | | 5)NOTE: PLEASE NOTE THAT GROUNDING | | | ELECTRODE SYSTEM WAS NOT SUBMITTED ON | | | ONE LINE DIAGRAM. PLEASE SUBMIT. | | | PER 250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-05 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-07-05 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-02 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-02 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-29 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-29 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2001-08-29 00:00:00 | 1) PLEASE INDICATE DISTANCES FROM STAIR | | | # 1 AND # 4 TO THE ADJACENT BUILDING, | | | TRANSFORMERS, OBSTACLES, ETC. | | | 2) GENERATOR ROOM TO BE AT LEAST TWO | | | HOUR FIRE RATED. | | | 3) EMERGENCY LIGHTING REQUIRED IN FIRE | | | PUMP ROOM. | | | 4) HOW IS COMBUSTIBLE LINT REMOVED FROM | | | DRYER RISER. | | | 5) FIRE DAMPERS TO COMPLY WITH UL 555. | | | 6) PLEASE SHOW DIMENSION OF WALL AND | | | RAILING FOR BALCONIES. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-05 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2001-07-05 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) PLEASE EXPLAIN 1-003 UNDER RAMP | | | STORAGE. | | | 3) PLEASE PROVIDE EVIDENCE OF COMPLIANCE | | | WITH STANDARD BUILDING CODE, SECTION | | | 3003.4 STRETCHER REQUIREMENTS. | | | 4) PLEASE EXPLAIN ROOMS 6-011 AND 6-012 | | | TRASH. | | | 5) PLEASE PROVIDE PRODUCT APPROVALS FOR | | | THE FOUR ROLLING FIRE SHUTTERS. | | | 6) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS OF BUILDING. | | | 7) PRIOR TO OCCUPANCY ALL UNFINSHED | | | AREAS OF THE BUILDING ARE TO MEET ALL | | | MINIMUM LIFE SAFETY REQUIREMENTS. | | | 8) ADDITIONAL ILLUMINATED EXIT SIGNS | | | APPEAR TO BE NEEDED ON THE SECOND, | | | THIRD, AND FOURTH FLOOR GARAGE LIGHTING | | | PLANS. PLEASE CLEARLY IDENTIFY EMERGENCY | | | LIGHT FIXTURES ON GARAGE FLOORS. | | | 9) PLEASE EXPLAIN SMOKE DETECTOR NOTE | | | ON PAGE E404. | | | 10) NO SMOKE DETECTORS SHOWN IN | | | ELEVATOR LOBBIES 6-010 AND 6-013. | | | 11) PLEASE PROVIDE MORE DETAILS ON | | | DIESEL GENERATOR.PRODUCT APPROVALS | | | REQUIRED FOR GENERATOR AND DIESEL TANK. | | | 12) PLEASE PROVIDE EXIT DISCHARGE | | | DISTANCES FROM STAIR # 1 AND # 4 TO | | | BAXTER HALL OR TO ANY EQUIPMENT | | | ASSOCIATED WITH IT. | | | 13) DOES THE NEW BUILDING BLOCK OR | | | OBSCURE ANY EXISTING FIRE PROTECTION | | | EQUIPMENT OR DEVICES FOR BAXTER HALL. | | | 14) PLEASE PROVIDE CODE REFERENCE THAT | | | ALLOWS NO FIRE PROTECTION FOR COOLING | | | TOWER. | | | 15) DOES THE EXHAUST FANS RUN | | | CONTINOUSLY IN THE GARAGE. | | | 16) PROVIDE MORE DETAILS ON RAILINGS | | | AT DORM BALCONIES. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
N |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-12 |
Time |
14:58 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-08-12 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2002-08-12 00:00:00 | AS BUILT DWGS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-06-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-13 |
Time |
10:51 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-13 |
Time |
10:51 |
Sent To |
B |
|
| Notes |
| 2002-06-13 00:00:00 | SPOKE WITH THOMAS CUNNINGHAM, CHIEF | | | ARCHITECT - REFERNENCE LETTER DATED | | | APRIL 8, 2002, SHAFT WALL NEXT TO THE | | | NORTH & SOUTH STAIR WALLS WHERE | | | REMOVED.MECHANICAL SHAFTS WERE NEVER | | | UTILIZED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2001-11-15 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-11-15 |
Time |
15:29 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-11-15 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-11-15 00:00:00 | REVISION ADDING CH WTR PIPE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-03 |
Time |
14:14 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-10-03 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | ******************PROVISO*************** | | | | | | 1.TERMINATION OF RELIEF VENT SHALL | | | ALSO NOT LESS THAN 20' FROM ANY | | | WINDOW, OR EXIT FROM ANY BUILDING | | | IN ADDITION TO THE 15 FT ABOVE THE | | | ADJOINING GRADE AS STATED ON PLAN | | | SHEET AC-7. | | | | | | 2.ACCESS FOR SERVICE/REPLACEMENT OF | | | FCU IS UNDER REVIEW.ACCESS DOORS | | | MAY BE REQUIRED IN THE APARTMENT | | | AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-18 |
Time |
10:30 |
Rev Time |
4.00 |
| Received By |
pkrauss |
Date |
2001-09-17 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.THERE SHALL BE NO RECIRCULATION OF | | | AIR IN THE TRUCK LOADING AREA, PLAN | | | AC-2.EXHAUST SHALL TERMINATE TO | | | OUTDOORS, 1997 SMC 1105.7.2 AND | | | SECTION 506.1.OUTSIDE AIR SHALL | | | BE BROUGHT IN FROM OUTDOORS AND NOT | | | FROM THE TRUCK LOADING AREA, RISK | | | OF CARBON MONOXIDE BEING TRANSFERED | | | INTO THESE SPACES. | | | | | | 2.PLEASE PROVIDE SEQUENCE OF | | | OPERATION SHOWING COMPLIANCE WITH | | | CHAPTER 11 SECTION 1105.7.4 FOR | | | NORMAL VENTILATION AND SECTION | | | 1105.7.5 FOR EMERGENCY OPERATION. | | | | | | 3.SIGNS SHALL BE POSTED AT CHILLER | | | ROOM DOORS PROHIBITING ACCESS OF | | | UNAUTHORIZED PERSONNEL. | | | | | | 4.BOTH BREATHING APPARATUS SHALL BE | | | LOCATED OUTSIDE OF THE CHILLER | | | ROOM. | | | | | | 5.ALARM/STROBE SHALL BE LOCATED IN | | | SUCH A MANNER THAT ALL ENTRANCES | | | WILL HAVE NOTIFICATION OF A | | | HAZARDOUS SITUATION. | | | | | | 6.PLAN SHEET INDICATES A REFRIGERANT | | | SENSOR OUTSIDE THE CHILLER ROOM. | | | WHAT PURPOSE DOES IT SERVE? | | | | | | 7.REFRIGERANT SENSORS SHALL BE | | | LOCATED IN CLOSE PROXIMITY TO THE | | | EQUIPMENT.PLAN SHEET AC-7 SENSORS | | | ARE LOCATED NEXT TO DOORS AND | | | AN EXHAUST FAN, THIS MAY HAVE AN | | | ADVERSE EFFECT ON THE SENSORS. | | | | | | 8.FAN COIL ACCESS MUST BE ADEQUATE | | | FOR SERVICE, CLEANING AND REMOVAL. | | | | | | NOTE:UNDER THE 1998 FAIR HOUSING ACT | | | PART TWO CHAPTER 5, THERMOSTATS | | | AND OTHER CONTROLS THAT MUST BE | | | READ ARE MOUNTED AT OR LOWER THAN | | | 48" ABOVE THE FLOOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-02 |
Time |
09:01 |
Rev Time |
8.00 |
| Received By |
pkrauss |
Date |
2001-07-31 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | CHILLER ROOM SHALL COMPLY WITH CHAPTER | | | 11 OF THE 1997 SMC. | | | | | | 1.REFRIGERANT DETECTOR SHALL BE TIED | | | TO AN ALARM/STROBE. | | | | | | 2.ALARM/STROBE SHALL BE LOCATED OUT- | | | SIDE OF CHILLER ROOM ENTRANCE AS | | | WELL AS INSIDE. ALL ALARM/STROBES | | | MUST BE IDENTIFIED ON THE PLAN. | | | | | | 3.SIGNS SHALL BE POSTED AT CHILLER | | | ROOM DOORS PROHIBITING ACCESS OF | | | UNAUTHORIZED PERSONNEL. | | | | | | 4.PLEASE DESCRIBE VENTILATION FOR | | | CHILLER ROOM BOTH NORMAL AND | | | EMERGENCY SITUATIONS. | | | | | | 5.BREATHING APPARATUS SHALL BE | | | LOCATED OUTSIDE CHILLER ROOM AT | | | A LOCATION CONVENIENT TO CHILLER | | | ROOM. | | | | | | 6.TERMINATION OF RELIEF DEVICES SHALL | | | BE OUTSIDED AND A MINIMUM OF 15 FT | | | ABOVE THE ADJOINING GRADE LEVEL AND | | | 20 FT FROM ANY WINDOW, AIR INTAKE, | | | OR EXIT TO ANY BUILING. | | | | | | 7.CONDENSATE DRAIN LINES NEED TO BE | | | IDENTIFIED ON PLAN. | | | | | | 8.DRYER VENTS ARE BE RUN TO THE | | | ATMOSPHERE INDIVIDUALLY IN SHAFT. | | | | | | 9.FAN COIL ACCESS MUST BE ADEQUATE | | | FOR SERVICE, CLEANING, AND REMOVAL. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-22 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-22 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | AS BUILTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2002-08-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-10 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-10 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2002-08-10 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 - SGC-97 | | | | | | 1) UNABLE TO REVIEW REVISIONS. PLEASE | | | INDICATE REVISIONS WITH CLOUDS, DARTS, | | | TRIANGLES ECT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-06-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-08 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-08 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2002-06-08 00:00:00 | REVISION OK - NEW SLOT DRAINS AND RE- | | | ROUTED LINES. NEW FIXTURE UNIT COUNTS. | | | CHANGED ELEVATIONS AND SQ FOOTAGE ON | | | STORM SYSTEMS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-26 |
Time |
14:18 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-09-26 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | PASSED - WENT OVER COMMENTS AND EVERY- | | | THING OK. CIVIL PLAN MISSING ON ONE SET | | | OF PLANS, STAMPED BACKFLOW REQUIRED ON | | | THIS SHEET ON OTHER SETS OF PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-09-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-15 |
Time |
07:45 |
Rev Time |
4.00 |
| Received By |
kstevens |
Date |
2001-09-15 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2001-09-15 00:00:00 | DENIED | | | REFERENCES: SPC-94 - SGC-97 - FHA-98 | | | DESIGN MANUAL | | | (1) SHEETS A002 & A302. PLEASE INDICATE | | | SPECIFICATION A OR B AS REQUIRED IN FHA- | | | 98 REQUIREMENT 7B BATHROOM REQUIREMENTS. | | | (2) SHEET A302 DETAIL & FLOOR PLAN, BATH | | | ROOM 1-009F. PARALLEL APPROACH TO BASIN, | | | BASIN TO BE CENTERED ON 48". | | | (3) SHEET A302 TYPICAL DORM UNIT A B C. | | | SHOW CLEAR FLOOR SPACE FOR DRESSING ROOM | | | BASIN. | | | (4) REQ. 2 COMMON USE SPACES PAGE 2.27. | | | SHEET A302 SHOW CLEAR FLOOR SPACE FOR | | | LAUNDRY AND PANTRY SINKS. FHA-98 | | | (5) PAGE P002 ELECTRIC WATER HEATER DE- | | | TAIL. PAN DRAIN (1") AND P&T (FULL SIZE) | | | TO RUN SEPARATELY TO A FLOOR SINK WITH A | | | TRAP PRIMER. SPC-94 SECTIONS 507.8.2, | | | 507.8.4, 507.8.5 AND 802. | | | (6) PAGE P002 ELECT. WATER HEATER DETAIL | | | COLD WATER SHUT OFF VALVE TO BE ACCESS- | | | ABLE WITH OUT THE USE OF LADDERS ECT. | | | SPC-94 SECT. 610.3.3 | | | (7) PAGE P201 NO HOT WATER SHOWN TO KIT- | | | CHEN SINK IN DIRECTORS APT RM #1-009A. | | | (8) PAGE P201 ROOM #1-022, ELECT. WATER | | | HEATER DETAIL, WATER HEATER PAN DRAIN TO | | | RUN 1" TO FLOOR SINK W/TRAP PRIMER NOT | | | TO FLOOR DRAIN. | | | (9) PAGE P401 DIRECTORS APT RM #1-009A, | | | NO COLD WATER TO W/C'S ON WATER RISER. | | | (10) PAGE P401 NO COLD WATER SHOWN FOR | | | CENTER LAV IN WOMENS RESTROOM RISER DIA. | | | (11) PAGE P401 WATER HAMMER ARRESTOR AT | | | TOP OF DROP IN MENS RESTROOM NOT LOCATED | | | PROPERLY. PLEASE SHOW PROPER LOCATION | | | PER WH-PDI 201. | | | (12) SHEET A-301 RM #1-009B. SHOW CLEAR | | | FLOOR SPACE FOR KITCHEN PER FHA-98 | | | (13) SHEET A-208 PLEASE SHOW SECONDARY | | | ROOF DRAINS. GIVE CALCULATIONS AND SIZE | | | PER SPC-94 SECTION 1108.5 & FIG 1109.3. | | | (14) SHEET C-1, FIRE AND IRRIGATION BACK | | | FLOW PREVENTERS NOT SHOWN. SEE COMMENT | | | #5 OF PLAN REVIEW DATED 7-15-01. | | | (15) PAGES P002, P201, & P401. INFORMAT- | | | ION STILL REQUIRED FOR GAS PERMIT APPLI- | | | CATION. #1 TYPE OF MATERIAL, #2 TYPE OF | | | GAS & #3 MANUFACTURE INFORMATION FOR GAS | | | BOILER. | | | (16) PAGE P201 PLEASE PROVIDE A CONDEN- | | | SATE RISER DIAGRAM WITH PIPE SIZES AND | | | SHOW LOAD OF EACH NUMBERED RISER. | | | (17) PAGE P203 PLEASE PROVIDE A RISER | | | DIAGRAM WITH PIPE SIZE FOR TRENCH DRAINS | | | FOR THE FOURTH AND FIFTH FLOOR PARKING | | | GARAGE. | | | (18) PAGE P401 GAS RISER DIAGRAM. ARE | | | ALL 4 SHUT OFF VALVES NECESSARY? | | | (19) PAGE P301 FLOOR DRAINS AT THE WATER | | | CLOSETS, ARE ALL THESE NECESSARY? | | | (20) PAGES P203 & P204, KEY NOTES #2. | | | PLEASE CHANGE TO REFLECT CHANGE ON P205 | | | SAME NOTE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-15 |
Time |
13:56 |
Rev Time |
4.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-15 00:00:00 | PLUMBING PLAN REVIEW, DENIED. | | | FAIR HOUSING ACT,24 (CFR) 100.205(C)(IV) | | | REVISED APRIL 1998,DESIGN MANUAL | | | CODE REFERENCES FACBC-97,SPC-94,SGC-97 | | | (1)SHT A-201 PANTRY RM #1-011, SINK TO | | | COMPLY FACBC W/SEC 4.24.1 HEIGHT 34" FF. | | | (2)SHT A-201,DIRECTORS APT RM# 1-009A, | | | NOT SHOWN ON SHT A-302,FAIR HOUSING ACT | | | ADAPTABILITY PLAN. | | | (3A) SHT A-302 DETAIL 7, 20 GA SHEET | | | METAL DOES NOT MEET THE GUIDE LINES FOR | | | INSTALLATION OF GRABS,SEE APPEX-A,PG.A3 | | | (3B) CLEAR FLOOR SPACE AND DOOR SWING IS | | | REQUIRED AT TIME OF CONSTRUCTION, WALLS | | | AND DOORS ARE NOT TO BE ALTERED, AFTER | | | THE COMPLETION OF CONSTRUCTION. SEE PG. | | | 7.39 MANEUVERING SPACE IN BATH ROOMS. | | | BATH TUB CLEAR FLR SPACE AT CONTROL END. | | | (3C) SHOW ALL DIMENSIONS FOR CLEAR FLOOR | | | SPACE ON ARCHITECTURAL PLANS,SEE DESIGN | | | MANUAL. INCLUDE REQUIRMENTS IN CHAPT. 5 | | | ELECTRICAL OUTLETS, CONTROLS. | | | (4)SHT A-208 PRIMARY ROOF DRAINS, CALCUL | | | ATIONS FOR ROOF DRAINS,INCLUDE HALF THE | | | VERTICAL WALLS (PARAPET WALLS) AND UPPER | | | ROOFS,DRAINING DOWN ON MAIN ROOF. | | | SECONDARY DRAINS,SEC 1108.5,FIG.1109.3 | | | RAIN FALL RATE, CALCULATIONS AND SIZE. | | | (5) SHT C-1 SHOW LOCATION OF BACK FLOW | | | PREVENTERS,IRRIGATION,FIRE,DOMESTIC | | | WATER, ALSO SANITARY SEWER TIE INS. | | | (6)SHT P-201,204,SEE ATTACHED GAS PERMIT | | | APPLICATION REQUIRMENTS, ADDRESS EA ITEM | | | (7) SHT P-201 TO P-206, SEC 104.3 PLANS | | | PROVIDE A ISOMETRIC DRAWING OF DWV,RWL | | | RISERS THRU THE ROOF, NUMBER EA RISER, | | | SIZE AND LOAD, REQUIRED. | | | (8A) SHT P-201 ELECTRICAL RM # 1-107 | | | DRAIN PAN OVER ELECTRICAL EQUIPMENT. | | | NEC-99, ART.1010-26 PANNEL HEAD RM. | | | (8B) MECHANICAL RM # 1-019 WATER HEATER | | | IN CEILING, SEC 501.7,READLY ACCESSIBLE. | | | PROVIDE A DETAIL OF A WORKING PLATFORM | | | WITH A SHIPS LADDER,FIXED IN PLACE, OR | | | RELOCATE TO FLOOR LEVEL. | | | (8C) RESIDENT DIRECTOR APT.# 1-009A, NO | | | DWV AND WATER PIPING SHOWN FOR THIS UNIT | | | (8C) TRUCK BAY RM # 1-020, TRENCH DRAINS | | | SHALL BE CONNECTED TO STORM DRAIN. | | | (9)SHT P-205,206 NOTE (2) A/C CONDENSATE | | | TO TERMINATE IN 5TH FLR CEILING, VENT AT | | | HIGHEST POINT.SPC-94 AMENDMENTS TO MODEL | | | CNTY.WIDE PLBG CODE,SEC 804.3(5). (VTR) | | | (10) SHT P-301 FIXTURE WATER PIPING, | | | SEC 607.7, AMENDMENTS TO MODEL CNTY.WIDE | | | PLBG CODE,NO MORE THAN 2 FIXTURES ON 1/2 | | | COLD WATER, NO MORE THAN 4 FIXTURES ON | | | 1/2" HOT WATER. SUITES A,B,C,,E. | | | (11) SHT 401, WATER HAMMER ARRESTORS TO | | | BE INSTALLED AS PER MANFACTURE INSTRUCT- | | | IONS, NOT AT THE HIGH POINT. USE WATER | | | HAMMER ARRESTOR STD PDI-201 FOR PLACE- | | | MENT AND SIZE. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-28 |
Time |
13:36 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | APPROVED BY RANDALL GRANBERRY |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2001-08-29 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-29 |
Time |
09:31 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-29 00:00:00 | DENIED NO APPROVED SITE PLAN 8-29-01RG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-03 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-07-03 |
Time |
08:23 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-03 00:00:00 | NEED COMMISSION APPROVAL, SENT TO BLDG |
|
|