Plan Review Details - Permit 01070072
Plan Review Stops For Permit 01070072
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2002-08-22 Cont ID  
Sent By jwitmer Date 2002-08-22 Time 13:40 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-22 00:00:00 
 AS BUILTS/ REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-08-15 Cont ID  
Sent By jwitmer Date 2002-08-15 Time 05:55 Rev Time 1.25
Received By jwitmer Date 2002-08-15 Time 05:55 Sent To  
Notes
2002-08-15 00:00:00PLEASE INDICATE REVISIONS OR PREVIOUS
 REVISIONS WITH AN INDICARION AS DELTA,
 CLOUDS,OR OTHER IDENTIFIABLE SYMBLE.
 IN GOING OVER PART OF PLANS THERE ARE
 PREVIOUS REVISIONS THAT ARE NOT NOW
 SHOWN.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-06-29 Cont ID  
Sent By jwitmer Date 2002-06-29 Time 09:22 Rev Time 0.00
Received By jwitmer Date 2002-06-29 Time 09:32 Sent To  
Notes
2002-06-29 00:00:001) TRUSS SUBMITTALS
 2) RAILINGS/ PAVERS
 3) DELETION OF SHAFT WALL @ NE SE STAIR-
 WELL(MECHANICAL)

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-05-29 Cont ID  
Sent By pkrauss Date 2002-06-13 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2002-06-29 Time 09:32 Sent To  
Notes
2002-05-29 00:00:00TRUSS ENGINEERING:
 1) THE DESIGN PROFESSIONAL SHALL REVIEW
 AND APPROVE BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT.
  
 2) THE BUILDING WAS DESIGNED UNDER THE
 1997 STANDARD BUILDING CODE, ASCE 7-95,
 THE TRUSS ENGINEERING INDICATES ASCE
 7-98.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-10-03 Cont ID  
Sent By jwitmer Date 2001-10-03 Time 15:44 Rev Time 0.50
Received By jwitmer Date 2001-10-03 Time 15:44 Sent To  
Notes
2001-10-03 00:00:00PROVISO: SUBMIT PRODUCT APPROVAL REPORTS
  
 1)- FENESTRATION TESTING LABS REQUIRE
 SITE SPECIFIC CERTIFICATION
  
 2)- ARCH ALUM IMPACT WALL 3000 SYSTEM
 EXPIRED A CURRENT REPORT SHALL BE
 REQUIRED.
  
 (3) COPIES OF PRODUCT TESTING REPORTS
 ARE REQUIURED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-10-02 Cont ID  
Sent By jwitmer Date 2001-10-02 Time 14:05 Rev Time 3.00
Received By jwitmer Date 2001-10-02 Time 14:05 Sent To  
Notes
2001-10-02 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070072
 1000 S DIXIE
 FINFROCK CONSTRUCTION
 (407) 293-4000
  
 1)- PRODUCT APPROVAL
 A) FENESTRATION TESTING LAB - WILL
 REQUIRE SITE SPECIFIC CERTIFICATION
 B) ARCH ALUM IMPACT WALL 3000 REPORT
 EXPIRED
 C) NO ROOFING REPORT, FOR ROOFING
 ASSEMBLY
  
 2)- ENERGY CALCULATION (2) SETS TO BE
 SIGNED.
  
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-09-04 Cont ID  
Sent By jwitmer Date 2001-09-04 Time 14:03 Rev Time 1.50
Received By jwitmer Date 2001-09-04 Time 14:02 Sent To  
Notes
2001-09-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070072
 1000 S. DIXIE HWY
 FINFROCK CONSTRUCTION
 (407) 293-4000
  
 SBC= STANDARD BUIULDING CODE
 SBC*= 1997 AMENDMENTS STANDARD BUILDING
 CODE
  
 1)- SHEET A803 NOTES 1&2 GLAZED OPENINGS
 ARE TO MEET THE STANDARD BUILDING CODE
 FOR DETERMINING IMPACT RESISTANCE FROM
 WINDBORNE DEBRIS, SEE SSTD-12-97. THE
 CITY DOES RECONIZE THE DADE COUNTY PRO-
 DUCT TESTING REPORTS.
  
 2)- SHEETS A3-302 THE DETAIL INDICATES
 THERE IS A LAUNDRY WITH DRYERS, THE MISS
 ING INFORMATION ON THE CHASE FOR THE DRY
 ER VENTS. RESPONCE SEE HILL-YORK DRAW-
 INGS. SHEET AC-5 DOES NOTE THAT THERE
 WILL BE A 2 HR. CHASE BY G. C.WHAT IS
 THE U.L. LISTING OR GYPSUM ASS.#?
  
 3)- SBC 1606.4.1 / 1707.4.1 THE CODE RE-
 QUIRES GLAZED OPENINGS TO HAVE LARGE
 MISSLE IMPACT TESTING FOR THE FIRST 30'
 OF ELEVATION, ABOVE THIS HEIGHT WILL BE
 SMALL IMPACT TESTING REQUIRED. A PROVISO
 CAN BE WRITTEN THOUGH A SEPERATE PERMIT
 AND FEES WILL BE REQUIRED.(3 COPIES OF
 REPORT WILL BE REQUIRED.
  
 4)- SBC 1606.2.6.2/ 1707.5 CLAY TILE &
 CEMENT TILE WILL ALSO REQUIRE THE PRO-
 DUCT TESTING REPORTS (3 COPIES).
  
 5)- FLORIDA STATE STATUTE553.79 (5)(A)
 THRESHOLD BUILDING INSPECTION PLAN FROM
 THE ENGINEER OR ARCHETECT OF RECORD WILL
 BE REQUIRED BEFORE THE ISSUANCE OF THE
 BUILDING PERMIT. THE PURPOSE OF THE
 STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND
 SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH
 THE PERMITTED DOCUMENTS.
  
 6)- THREE SETS OF PLANS WILL BE REQUIRED
 BEFORE THE ISSUANCE OF THE PERMIT.
  
 7)- PLANS WILL NEED COUNTY IMPACT FEE
 STAMP AND RECEIPT.
  
 8)- RADON FEES TO CITY $2323.54
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-30 Cont ID  
Sent By jwitmer Date 2001-07-30 Time 06:50 Rev Time 0.00
Received By jwitmer Date 2002-06-29 Time 10:02 Sent To  
Notes
2001-07-30 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070072
 1000 S DIXIE HWY
 FINFROCK CONSTRUCTION
 (407) 293-4000
  
 SBC = STANDARD BUILDING CODE 1997 EDI.
 SBC* = 1997 AMENDMENTS STANDARD BUILDING
 CODE
 1)- SHEET A-803 NOTES 1 & 2 GLAZED OPEN-
 INGS ARE TO MEET THE STANDARD BUILDING
 CODE STANDARD FOR DETERMINING IMPACT
 RESISTANCE FROM WINDBORNE DEBRIS, SEE
 SSTD-12-97. THE CITY DOES ACCEPT THE
 DADE COUNTY PRODUCT APPROVAL.
  
 2)- FL ACCESSIBILITY CODE 4.6.4:
 SIGNAGE FOR HANDICAPPED VANS.
  
 3)- SHEET A-C 9 SIZE OF BOILER? SBC 704.
 1.3.3.3.
  
 4)_ SHEET A-302 DETAILS 3,5 & 6 ALL
 DETAILS INDICATE A SOLID BLUE LINE, IS
 THIS A VOID FOR UTILITIES?
  
 5)- SHEET A-302 THE DETAILS INDICATE
 THERE IS A LAUNDRY WITH DRYERS, MISSING
  
 INFORMATION ON THE CHASE FORTHE DRYER
 VENTS?
  
 6)- SHEET A-504 SEC. A INDICATES THERE
 WILL BE ROOF SHEATHING, THE PLANS DO
 NOT INDICATE WHAT TYPE OF SHEATHING IS
 TO BE USED, THICKNESS, ETC.
  
 7)- ROOM 1-003 UNDER RAMP STORAGE:
 2,740 SQ FT & TRAVEL DISTANCE 80',THE
 SBC 1027.1.1 SINGLE EXIT REQUIREMENTS:
 2500 MAX SQ FT, TRAVEL DISTANCE NOT TO
 EXCEED 50'.
  
 8)- SBC 411.3 OPEN PARKING GARAGE : SHOW
 CALCULATIONS FOR OPEN WALL AREA, DETER-
 MINATION METHOD #1 OR #2.
  
 9)- STRUCTURAL DRAWINGS ARE NOT COMPLETE
 THEY DO NOT SHOW DETAILS PAST THE FIRST
 FLOOR, MISSING WELDING INFORMATION FOR
 CONNECTING PLATES, LOCATION, DIRECTION
 AND MAGNITUDE OF LOADS TO BE RESISTED.
  
 10)- SBC 1606.4.1 /1707.4.1 THE CODE
 REQUIRES GLAZED OPENINGS TO HAVE LARGE
 MISSLE TESTING,PRODUCT TESTING REPORTS
 ARE REQUIRED TO SHOW COMPLIANCE, A NOTE
 ON THE DRAWINGS INDICATING WHAT WILL BE
 DONE DOES SHOW INTENT, A PROVISO CAN BE
 WRITTEN FOR THIS SECTION OF THE CODE.
 SINCE THE WINDOWS AND DOORS WOULD BE RE-
 VIEWED AT A LATER DATE THEYWOULD BE
 UNDER A SEPERATE PERMIT WITH ASSOCIATED
 FEES.
  
 11)- SBC 1606.2.6.2/ 1707.5 CLAY TILE &
 CEMENT TILE WILL ALSO REQUIRE THE PRODUC
 T TESTING REPORTS (2 COPIES REQUIRED)
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 7 Status N Date 2002-07-30 Cont ID  
Sent By dpalmer Date 2002-07-30 Time 12:48 Rev Time 0.00
Received By dpalmer Date 2002-07-30 Time 12:48 Sent To  
Notes
2002-07-30 00:00:00*************** NOTE *****************
  
 1)NOTE: PLEASE NOTE THAT NONE OF THE
 ELECTRICAL SHEETS IN EITHER STE ARE
 SIGNED AND SEALED. PER FS/471.025
  
 2)NOTE: PLEASE NOTE THAT AS PER CONVER-
 -SATION WITH ENGINEER. ALL PREVIUOUS
 REVS WERE SUBMITTED AND REVIEW,
  
 IF THERE AREN ANY QUESTIONS, PLEASE CALL
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-07-29 Cont ID  
Sent By btrobaug Date 2002-07-29 Time 14:17 Rev Time 0.00
Received By btrobaug Date 2002-07-29 Time 14:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-07-26 Cont ID  
Sent By btrobaug Date 2002-07-26 Time 10:45 Rev Time 0.00
Received By btrobaug Date 2002-07-26 Time 10:45 Sent To  
Notes
2002-07-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE FIRE PUMP HP ON THE PLAN IS NOT
 WHAT IS INSTALLED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-03-28 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 12:10 Rev Time 0.00
Received By btrobaug Date 2002-03-28 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 20:45 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 20:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 22:11 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 22:11 Sent To  
Notes
2001-09-17 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASENOTE THAT NOTES FROM
 FIRST REVIEW.
  
 2)NOTE: PLEASE ADDRESS AND SUBMIT FOR
 REVIEW.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2001-07-30 Time 21:33 Sent To  
Notes
2001-07-31 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NO GFI PROTECT-
 -ION OF MDP AND MCC IS SHOWN. PLEASE
 NOTE THAT 230-95 REQ`SPROTECTION
 FOR 1000A`S OR MORE OVER 150V TO GRND.
  
 2)NOTE: PLEASE NOTE THAT CONDUCTOR FEED-
 ING MDP DO NOT MEET 240-3-C. PLEASE
 NOTE THAT CONDUCTORS ARE TO BE SIZED
 PER 310-16 75'COL. PER 110-14
  
 3)NOTE: PLEASE CLARIFY OCP IN MOTOR
 CONTRLOLLER PER 695-3-1, PLEASE ASLO
 NOTE GROUPING OF DISCS REFERENCED BY
 SAME ART TO 230-72B. PLEASE SEE 695-4B-1
 PLEASE SUBMIT CODE LETTER OF MOTOR.
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 OF DISCONNECTINGS MEANS OF GENERATOR
 GROUPED WITH MAIN PER 230-70 AND 230-72.
 PLEASE NOTE THAT MUST MEET 230-76 AND
 230-79.
  
 5)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODE SYSTEM WAS NOT SUBMITTED ON
 ONE LINE DIAGRAM. PLEASE SUBMIT.
 PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-05 Cont ID  
Sent By mamini Date 2001-07-05 Time 14:55 Rev Time 0.00
Received By mamini Date 2001-07-05 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-02 Cont ID  
Sent By mcarsill Date 2001-10-02 Time 08:28 Rev Time 0.00
Received By mcarsill Date 2001-10-02 Time 08:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-29 Cont ID  
Sent By mcarsill Date 2001-08-29 Time 17:31 Rev Time 0.00
Received By mcarsill Date 2001-08-29 Time 17:31 Sent To  
Notes
2001-08-29 00:00:001) PLEASE INDICATE DISTANCES FROM STAIR
 # 1 AND # 4 TO THE ADJACENT BUILDING,
 TRANSFORMERS, OBSTACLES, ETC.
 2) GENERATOR ROOM TO BE AT LEAST TWO
 HOUR FIRE RATED.
 3) EMERGENCY LIGHTING REQUIRED IN FIRE
 PUMP ROOM.
 4) HOW IS COMBUSTIBLE LINT REMOVED FROM
 DRYER RISER.
 5) FIRE DAMPERS TO COMPLY WITH UL 555.
 6) PLEASE SHOW DIMENSION OF WALL AND
 RAILING FOR BALCONIES.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 10:54 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 10:54 Sent To  
Notes
2001-07-05 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) PLEASE EXPLAIN 1-003 UNDER RAMP
 STORAGE.
 3) PLEASE PROVIDE EVIDENCE OF COMPLIANCE
 WITH STANDARD BUILDING CODE, SECTION
 3003.4 STRETCHER REQUIREMENTS.
 4) PLEASE EXPLAIN ROOMS 6-011 AND 6-012
 TRASH.
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR
 THE FOUR ROLLING FIRE SHUTTERS.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS OF BUILDING.
 7) PRIOR TO OCCUPANCY ALL UNFINSHED
 AREAS OF THE BUILDING ARE TO MEET ALL
 MINIMUM LIFE SAFETY REQUIREMENTS.
 8) ADDITIONAL ILLUMINATED EXIT SIGNS
 APPEAR TO BE NEEDED ON THE SECOND,
 THIRD, AND FOURTH FLOOR GARAGE LIGHTING
 PLANS. PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHT FIXTURES ON GARAGE FLOORS.
 9) PLEASE EXPLAIN SMOKE DETECTOR NOTE
 ON PAGE E404.
 10) NO SMOKE DETECTORS SHOWN IN
 ELEVATOR LOBBIES 6-010 AND 6-013.
 11) PLEASE PROVIDE MORE DETAILS ON
 DIESEL GENERATOR.PRODUCT APPROVALS
 REQUIRED FOR GENERATOR AND DIESEL TANK.
 12) PLEASE PROVIDE EXIT DISCHARGE
 DISTANCES FROM STAIR # 1 AND # 4 TO
 BAXTER HALL OR TO ANY EQUIPMENT
 ASSOCIATED WITH IT.
 13) DOES THE NEW BUILDING BLOCK OR
 OBSCURE ANY EXISTING FIRE PROTECTION
 EQUIPMENT OR DEVICES FOR BAXTER HALL.
 14) PLEASE PROVIDE CODE REFERENCE THAT
 ALLOWS NO FIRE PROTECTION FOR COOLING
 TOWER.
 15) DOES THE EXHAUST FANS RUN
 CONTINOUSLY IN THE GARAGE.
 16) PROVIDE MORE DETAILS ON RAILINGS
 AT DORM BALCONIES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-12 Time 14:58 Rev Time 0.45
Received By pkrauss Date 2002-08-12 Time 14:00 Sent To  
Notes
2002-08-12 00:00:00AS BUILT DWGS

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-06-13 Cont ID  
Sent By pkrauss Date 2002-06-13 Time 10:51 Rev Time 0.40
Received By pkrauss Date 2002-06-13 Time 10:51 Sent To B
Notes
2002-06-13 00:00:00SPOKE WITH THOMAS CUNNINGHAM, CHIEF
 ARCHITECT - REFERNENCE LETTER DATED
 APRIL 8, 2002, SHAFT WALL NEXT TO THE
 NORTH & SOUTH STAIR WALLS WHERE
 REMOVED.MECHANICAL SHAFTS WERE NEVER
 UTILIZED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-11-15 Cont ID  
Sent By ndenmark Date 2001-11-15 Time 15:29 Rev Time 0.50
Received By ndenmark Date 2001-11-15 Time 15:29 Sent To  
Notes
2001-11-15 00:00:00REVISION ADDING CH WTR PIPE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-10-03 Cont ID  
Sent By pkrauss Date 2001-10-03 Time 14:14 Rev Time 2.00
Received By pkrauss Date 2001-10-03 Time 12:00 Sent To  
Notes
2001-10-03 00:00:00******************PROVISO***************
  
 1.TERMINATION OF RELIEF VENT SHALL
 ALSO NOT LESS THAN 20' FROM ANY
 WINDOW, OR EXIT FROM ANY BUILDING
 IN ADDITION TO THE 15 FT ABOVE THE
 ADJOINING GRADE AS STATED ON PLAN
 SHEET AC-7.
  
 2.ACCESS FOR SERVICE/REPLACEMENT OF
 FCU IS UNDER REVIEW.ACCESS DOORS
 MAY BE REQUIRED IN THE APARTMENT
 AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-09-18 Cont ID  
Sent By pkrauss Date 2001-09-18 Time 10:30 Rev Time 4.00
Received By pkrauss Date 2001-09-17 Time 13:49 Sent To  
Notes
2001-09-18 00:00:00*******************DENIED***************
  
  
 1.THERE SHALL BE NO RECIRCULATION OF
 AIR IN THE TRUCK LOADING AREA, PLAN
 AC-2.EXHAUST SHALL TERMINATE TO
 OUTDOORS, 1997 SMC 1105.7.2 AND
 SECTION 506.1.OUTSIDE AIR SHALL
 BE BROUGHT IN FROM OUTDOORS AND NOT
 FROM THE TRUCK LOADING AREA, RISK
 OF CARBON MONOXIDE BEING TRANSFERED
 INTO THESE SPACES.
  
 2.PLEASE PROVIDE SEQUENCE OF
 OPERATION SHOWING COMPLIANCE WITH
 CHAPTER 11 SECTION 1105.7.4 FOR
 NORMAL VENTILATION AND SECTION
 1105.7.5 FOR EMERGENCY OPERATION.
  
 3.SIGNS SHALL BE POSTED AT CHILLER
 ROOM DOORS PROHIBITING ACCESS OF
 UNAUTHORIZED PERSONNEL.
  
 4.BOTH BREATHING APPARATUS SHALL BE
 LOCATED OUTSIDE OF THE CHILLER
 ROOM.
  
 5.ALARM/STROBE SHALL BE LOCATED IN
 SUCH A MANNER THAT ALL ENTRANCES
 WILL HAVE NOTIFICATION OF A
 HAZARDOUS SITUATION.
  
 6.PLAN SHEET INDICATES A REFRIGERANT
 SENSOR OUTSIDE THE CHILLER ROOM.
 WHAT PURPOSE DOES IT SERVE?
  
 7.REFRIGERANT SENSORS SHALL BE
 LOCATED IN CLOSE PROXIMITY TO THE
 EQUIPMENT.PLAN SHEET AC-7 SENSORS
 ARE LOCATED NEXT TO DOORS AND
 AN EXHAUST FAN, THIS MAY HAVE AN
 ADVERSE EFFECT ON THE SENSORS.
  
 8.FAN COIL ACCESS MUST BE ADEQUATE
 FOR SERVICE, CLEANING AND REMOVAL.
  
 NOTE:UNDER THE 1998 FAIR HOUSING ACT
 PART TWO CHAPTER 5, THERMOSTATS
 AND OTHER CONTROLS THAT MUST BE
 READ ARE MOUNTED AT OR LOWER THAN
 48" ABOVE THE FLOOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By pkrauss Date 2001-08-02 Time 09:01 Rev Time 8.00
Received By pkrauss Date 2001-07-31 Time 12:57 Sent To  
Notes
2001-08-02 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 CHILLER ROOM SHALL COMPLY WITH CHAPTER
 11 OF THE 1997 SMC.
  
 1.REFRIGERANT DETECTOR SHALL BE TIED
 TO AN ALARM/STROBE.
  
 2.ALARM/STROBE SHALL BE LOCATED OUT-
 SIDE OF CHILLER ROOM ENTRANCE AS
 WELL AS INSIDE. ALL ALARM/STROBES
 MUST BE IDENTIFIED ON THE PLAN.
  
 3.SIGNS SHALL BE POSTED AT CHILLER
 ROOM DOORS PROHIBITING ACCESS OF
 UNAUTHORIZED PERSONNEL.
  
 4.PLEASE DESCRIBE VENTILATION FOR
 CHILLER ROOM BOTH NORMAL AND
 EMERGENCY SITUATIONS.
  
 5.BREATHING APPARATUS SHALL BE
 LOCATED OUTSIDE CHILLER ROOM AT
 A LOCATION CONVENIENT TO CHILLER
 ROOM.
  
 6.TERMINATION OF RELIEF DEVICES SHALL
 BE OUTSIDED AND A MINIMUM OF 15 FT
 ABOVE THE ADJOINING GRADE LEVEL AND
 20 FT FROM ANY WINDOW, AIR INTAKE,
 OR EXIT TO ANY BUILING.
  
 7.CONDENSATE DRAIN LINES NEED TO BE
 IDENTIFIED ON PLAN.
  
 8.DRYER VENTS ARE BE RUN TO THE
 ATMOSPHERE INDIVIDUALLY IN SHAFT.
  
 9.FAN COIL ACCESS MUST BE ADEQUATE
 FOR SERVICE, CLEANING, AND REMOVAL.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-08-22 Cont ID  
Sent By kstevens Date 2002-08-22 Time 12:52 Rev Time 0.00
Received By kstevens Date 2002-08-22 Time 12:52 Sent To  
Notes
2002-08-22 00:00:00AS BUILTS

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-08-10 Cont ID  
Sent By kstevens Date 2002-08-10 Time 16:47 Rev Time 0.00
Received By kstevens Date 2002-08-10 Time 16:47 Sent To  
Notes
2002-08-10 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) UNABLE TO REVIEW REVISIONS. PLEASE
 INDICATE REVISIONS WITH CLOUDS, DARTS,
 TRIANGLES ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-06-08 Cont ID  
Sent By kstevens Date 2002-06-08 Time 07:43 Rev Time 0.00
Received By kstevens Date 2002-06-08 Time 07:43 Sent To  
Notes
2002-06-08 00:00:00REVISION OK - NEW SLOT DRAINS AND RE-
 ROUTED LINES. NEW FIXTURE UNIT COUNTS.
 CHANGED ELEVATIONS AND SQ FOOTAGE ON
 STORM SYSTEMS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-09-26 Cont ID  
Sent By kstevens Date 2001-09-26 Time 14:18 Rev Time 1.25
Received By kstevens Date 2001-09-26 Time 14:17 Sent To  
Notes
2001-09-26 00:00:00PASSED - WENT OVER COMMENTS AND EVERY-
 THING OK. CIVIL PLAN MISSING ON ONE SET
 OF PLANS, STAMPED BACKFLOW REQUIRED ON
 THIS SHEET ON OTHER SETS OF PLANS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-15 Cont ID  
Sent By kstevens Date 2001-09-15 Time 07:45 Rev Time 4.00
Received By kstevens Date 2001-09-15 Time 07:45 Sent To  
Notes
2001-09-15 00:00:00DENIED
 REFERENCES: SPC-94 - SGC-97 - FHA-98
 DESIGN MANUAL
 (1) SHEETS A002 & A302. PLEASE INDICATE
 SPECIFICATION A OR B AS REQUIRED IN FHA-
 98 REQUIREMENT 7B BATHROOM REQUIREMENTS.
 (2) SHEET A302 DETAIL & FLOOR PLAN, BATH
 ROOM 1-009F. PARALLEL APPROACH TO BASIN,
 BASIN TO BE CENTERED ON 48".
 (3) SHEET A302 TYPICAL DORM UNIT A B C.
 SHOW CLEAR FLOOR SPACE FOR DRESSING ROOM
 BASIN.
 (4) REQ. 2 COMMON USE SPACES PAGE 2.27.
 SHEET A302 SHOW CLEAR FLOOR SPACE FOR
 LAUNDRY AND PANTRY SINKS. FHA-98
 (5) PAGE P002 ELECTRIC WATER HEATER DE-
 TAIL. PAN DRAIN (1") AND P&T (FULL SIZE)
 TO RUN SEPARATELY TO A FLOOR SINK WITH A
 TRAP PRIMER. SPC-94 SECTIONS 507.8.2,
 507.8.4, 507.8.5 AND 802.
 (6) PAGE P002 ELECT. WATER HEATER DETAIL
 COLD WATER SHUT OFF VALVE TO BE ACCESS-
 ABLE WITH OUT THE USE OF LADDERS ECT.
 SPC-94 SECT. 610.3.3
 (7) PAGE P201 NO HOT WATER SHOWN TO KIT-
 CHEN SINK IN DIRECTORS APT RM #1-009A.
 (8) PAGE P201 ROOM #1-022, ELECT. WATER
 HEATER DETAIL, WATER HEATER PAN DRAIN TO
 RUN 1" TO FLOOR SINK W/TRAP PRIMER NOT
 TO FLOOR DRAIN.
 (9) PAGE P401 DIRECTORS APT RM #1-009A,
 NO COLD WATER TO W/C'S ON WATER RISER.
 (10) PAGE P401 NO COLD WATER SHOWN FOR
 CENTER LAV IN WOMENS RESTROOM RISER DIA.
 (11) PAGE P401 WATER HAMMER ARRESTOR AT
 TOP OF DROP IN MENS RESTROOM NOT LOCATED
 PROPERLY. PLEASE SHOW PROPER LOCATION
 PER WH-PDI 201.
 (12) SHEET A-301 RM #1-009B. SHOW CLEAR
 FLOOR SPACE FOR KITCHEN PER FHA-98
 (13) SHEET A-208 PLEASE SHOW SECONDARY
 ROOF DRAINS. GIVE CALCULATIONS AND SIZE
 PER SPC-94 SECTION 1108.5 & FIG 1109.3.
 (14) SHEET C-1, FIRE AND IRRIGATION BACK
 FLOW PREVENTERS NOT SHOWN. SEE COMMENT
 #5 OF PLAN REVIEW DATED 7-15-01.
 (15) PAGES P002, P201, & P401. INFORMAT-
 ION STILL REQUIRED FOR GAS PERMIT APPLI-
 CATION. #1 TYPE OF MATERIAL, #2 TYPE OF
 GAS & #3 MANUFACTURE INFORMATION FOR GAS
 BOILER.
 (16) PAGE P201 PLEASE PROVIDE A CONDEN-
 SATE RISER DIAGRAM WITH PIPE SIZES AND
 SHOW LOAD OF EACH NUMBERED RISER.
 (17) PAGE P203 PLEASE PROVIDE A RISER
 DIAGRAM WITH PIPE SIZE FOR TRENCH DRAINS
 FOR THE FOURTH AND FIFTH FLOOR PARKING
 GARAGE.
 (18) PAGE P401 GAS RISER DIAGRAM. ARE
 ALL 4 SHUT OFF VALVES NECESSARY?
 (19) PAGE P301 FLOOR DRAINS AT THE WATER
 CLOSETS, ARE ALL THESE NECESSARY?
 (20) PAGES P203 & P204, KEY NOTES #2.
 PLEASE CHANGE TO REFLECT CHANGE ON P205
 SAME NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-15 Cont ID  
Sent By pschmitz Date 2001-07-15 Time 13:56 Rev Time 4.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-15 00:00:00PLUMBING PLAN REVIEW, DENIED.
 FAIR HOUSING ACT,24 (CFR) 100.205(C)(IV)
 REVISED APRIL 1998,DESIGN MANUAL
 CODE REFERENCES FACBC-97,SPC-94,SGC-97
 (1)SHT A-201 PANTRY RM #1-011, SINK TO
 COMPLY FACBC W/SEC 4.24.1 HEIGHT 34" FF.
 (2)SHT A-201,DIRECTORS APT RM# 1-009A,
 NOT SHOWN ON SHT A-302,FAIR HOUSING ACT
 ADAPTABILITY PLAN.
 (3A) SHT A-302 DETAIL 7, 20 GA SHEET
 METAL DOES NOT MEET THE GUIDE LINES FOR
 INSTALLATION OF GRABS,SEE APPEX-A,PG.A3
 (3B) CLEAR FLOOR SPACE AND DOOR SWING IS
 REQUIRED AT TIME OF CONSTRUCTION, WALLS
 AND DOORS ARE NOT TO BE ALTERED, AFTER
 THE COMPLETION OF CONSTRUCTION. SEE PG.
 7.39 MANEUVERING SPACE IN BATH ROOMS.
 BATH TUB CLEAR FLR SPACE AT CONTROL END.
 (3C) SHOW ALL DIMENSIONS FOR CLEAR FLOOR
 SPACE ON ARCHITECTURAL PLANS,SEE DESIGN
 MANUAL. INCLUDE REQUIRMENTS IN CHAPT. 5
 ELECTRICAL OUTLETS, CONTROLS.
 (4)SHT A-208 PRIMARY ROOF DRAINS, CALCUL
 ATIONS FOR ROOF DRAINS,INCLUDE HALF THE
 VERTICAL WALLS (PARAPET WALLS) AND UPPER
 ROOFS,DRAINING DOWN ON MAIN ROOF.
 SECONDARY DRAINS,SEC 1108.5,FIG.1109.3
 RAIN FALL RATE, CALCULATIONS AND SIZE.
 (5) SHT C-1 SHOW LOCATION OF BACK FLOW
 PREVENTERS,IRRIGATION,FIRE,DOMESTIC
 WATER, ALSO SANITARY SEWER TIE INS.
 (6)SHT P-201,204,SEE ATTACHED GAS PERMIT
 APPLICATION REQUIRMENTS, ADDRESS EA ITEM
 (7) SHT P-201 TO P-206, SEC 104.3 PLANS
 PROVIDE A ISOMETRIC DRAWING OF DWV,RWL
 RISERS THRU THE ROOF, NUMBER EA RISER,
 SIZE AND LOAD, REQUIRED.
 (8A) SHT P-201 ELECTRICAL RM # 1-107
 DRAIN PAN OVER ELECTRICAL EQUIPMENT.
 NEC-99, ART.1010-26 PANNEL HEAD RM.
 (8B) MECHANICAL RM # 1-019 WATER HEATER
 IN CEILING, SEC 501.7,READLY ACCESSIBLE.
 PROVIDE A DETAIL OF A WORKING PLATFORM
 WITH A SHIPS LADDER,FIXED IN PLACE, OR
 RELOCATE TO FLOOR LEVEL.
 (8C) RESIDENT DIRECTOR APT.# 1-009A, NO
 DWV AND WATER PIPING SHOWN FOR THIS UNIT
 (8C) TRUCK BAY RM # 1-020, TRENCH DRAINS
 SHALL BE CONNECTED TO STORM DRAIN.
 (9)SHT P-205,206 NOTE (2) A/C CONDENSATE
 TO TERMINATE IN 5TH FLR CEILING, VENT AT
 HIGHEST POINT.SPC-94 AMENDMENTS TO MODEL
 CNTY.WIDE PLBG CODE,SEC 804.3(5). (VTR)
 (10) SHT P-301 FIXTURE WATER PIPING,
 SEC 607.7, AMENDMENTS TO MODEL CNTY.WIDE
 PLBG CODE,NO MORE THAN 2 FIXTURES ON 1/2
 COLD WATER, NO MORE THAN 4 FIXTURES ON
 1/2" HOT WATER. SUITES A,B,C,,E.
 (11) SHT 401, WATER HAMMER ARRESTORS TO
 BE INSTALLED AS PER MANFACTURE INSTRUCT-
 IONS, NOT AT THE HIGH POINT. USE WATER
 HAMMER ARRESTOR STD PDI-201 FOR PLACE-
 MENT AND SIZE.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop Z ZONING
Rev No 3 Status P Date 2001-09-28 Cont ID  
Sent By sgraham Date 2001-09-28 Time 13:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-09-28 00:00:00APPROVED BY RANDALL GRANBERRY

Review Stop Z ZONING
Rev No 2 Status F Date 2001-08-29 Cont ID  
Sent By sgraham Date 2001-08-29 Time 09:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-29 00:00:00DENIED NO APPROVED SITE PLAN 8-29-01RG

Review Stop Z ZONING
Rev No 1 Status F Date 2001-07-03 Cont ID  
Sent By sgraham Date 2001-07-03 Time 08:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-07-03 00:00:00NEED COMMISSION APPROVAL, SENT TO BLDG