Plan Review Details - Permit 01070019
Plan Review Stops For Permit 01070019
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-08 Cont ID  
Sent By jwitmer Date 2001-08-08 Time 16:08 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-01 Cont ID  
Sent By jwitmer Date 2001-08-01 Time 16:30 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-01 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01070019
 400 EXECUTIVE CENTER DR
  
 CONT A. O. SABA ENTERPRISES, INC.
 TEL: (561) 969-2920
  
 SBC= STANDARD BUILDING CODE
 SBC*= STANDARD BUILDING CODE AMENDMENTS
  
 1)- FLORIDA ACCESSIBILITY CODE 4.1.6.2:
 DISPROPORTIONATE COST, REQUIRES ACCESS
 TO ALL ACCESSIBILE AREAS, CONTRACTOR TO
 SHOW WHERE $6,400.00 WILL BE USED IN
 COMPLYING WITH THIS CODE ARTICLE, ATTACH
 ED IS A COPY OF THE SCHEDULE AS TO WHAT
 AREAS THESE MONIES WILL BE ALLOCATED.
  
 (I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED
 AREA.
 (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM
 (IV) ACCESSIBLE TELEPHONES
 (V) ACCESSIBLE DRINKING FOUNTAINS
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESS-
 IBLE ELEMENTS SUCH AS PARKING, STORAGE
 AND ALARMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-25 Cont ID  
Sent By jwitmer Date 2001-07-25 Time 13:20 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-25 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01070019
 400 EXECUTIVE CENTER DR.
 CONT: A.O. SABA ENTERPRISES, INC.
 TEL: (561) 969-2920
  
 SBC= STANDARD BUILDING CODE
 SBC* = STANDARDBUILDING CODE AMENDMENTS
  
 1)- FLORIDA ACCESSIBILITY REQUIRES
 ACCESS TO ALL ACCESSIBLE AREAS, FINAN-
 CIALLY THIS MAY BE DEEMED "DISPROPORTION
 ATE". 4.1.6.2 ALLOWS UP TO 20% OF THE
 CONTRACT TO UPDATE THE SPACE TO BECOME
 CODE COMPLIANT OVER A PERIOD OF TIME
 WHEN ALTERATIONS ARE COMPLETED. THE
 ATTACHED SHEET SHOWS THE PRIORITY IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TAKE
 PRIORITY.
 2)- FLORIDA ACCESSIBILITY CODE 4.13.6
 MANEUVERING AT DOORS,SEE ATTACHED SHEET
 3)- FL ACCESS CODE 4.13. 5 CLEAR WIDTH:
 DOORWAYS SHALL HAVE A CLEAR OPENING OF
 32" WITH THE DOOR OPENED 90 DEGREES
 BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE STOP.
 4)_ SBC* 104.2.3/ FL STATE STATUTE
 489.229(C) BUILDINGS INTENDED FOR PUBLIC
 USE WHEN THE AMOUNT EXCEEDS $25,000.00.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-18 Cont ID  
Sent By lsmith Date 2001-07-24 Time 11:16 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-07-24 00:00:00PER DVP 7/24/01 LS

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-18 Cont ID  
Sent By lsmith Date 2001-07-18 Time 12:30 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 16:18 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 16:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 15:20 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 15:20 Sent To  
Notes
2001-07-31 00:00:00PREVIOUS PLAN REVIEW COMMENTS NOT
 ADDRESSED BY SUBMITTER.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 08:38 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 08:38 Sent To  
Notes
2001-07-05 00:00:001) PLANS NOT SIGNED AND SEALED.
 ACCORDING TO PERMIT APPLICATION WORK
 IS VALUED AT 32,000.00 DOLLARS. PLANS
 APPEAR TO BE COPIES.
 2) PLEASE SHOW NEW OR EXISTING EMERGENCY
 LIGHTS AND EXIT SIGNS.
 3) PLEASE PROVIDE FLAME SPREAD RATING
 FOR NEW CEILING TILES.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-08 Cont ID  
Sent By pkrauss Date 2001-08-08 Time 14:40 Rev Time 0.30
Received By pkrauss Date 2001-08-08 Time 14:37 Sent To  
Notes
2001-08-08 00:00:00*******************PROVISO**************
  
  
 NO COMBUSTIBLES ABOVE CEILING IN THE
 RETURN AIR PLENUM.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-07-24 Cont ID  
Sent By pkrauss Date 2001-07-24 Time 12:11 Rev Time 0.35
Received By pkrauss Date 2001-07-24 Time 12:08 Sent To  
Notes
2001-07-24 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMAITON
 FOR MECHANICAL REVIEW:
  
  
 1.DUCT MATERIAL, SIZE AND ROUTING OF
 DUCT WORK.
  
 2.SIZE OF GRILLS & CFM DISTRIBUTION.
  
 3.LOCATION OF RETURN AIR.NOTE, AREAS
 WITH GREATER THAN 300 CFM REQUIRE
 A RETURN AIR.SHOULD SPACE ABOVE
 THE CEILING BE A RETURN AIR PLENUM,
 NO COMBUSTIBLES ARE ALLOWED.
  
 IF YOU HAVE ANY QUESITONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-07-18 Cont ID  
Sent By lsmith Date 2001-07-18 Time 12:32 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-18 Cont ID  
Sent By lsmith Date 2001-07-18 Time 12:30 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***