Plan Review Details - Permit 01061510
Plan Review Stops For Permit 01061510
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-10 Cont ID  
Sent By jwitmer Date 2001-09-10 Time 15:23 Rev Time 0.75
Received By jwitmer Date 2001-09-10 Time 15:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-29 Cont ID  
Sent By jwitmer Date 2001-08-29 Time 09:46 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-29 00:00:00PLAN REVIEW
 PERMIT# 01061510
 525 S FLAGLER 9C/9D
  
 1)- ADDITIONAL INFORMATION REQUIRED
 ADMINISTRATIVE CODE AMENDMENTS 104.2.2
 THE WALL SEEPERATING THE (2) UNITS, IS
 THIS A DRYWALL WALL OR IS THIS BLOCK OR
 A COMMON SHEER WALL? IF THIS IS A SOLID
 CONCRETE WALL THEN IT IS A SHEER WALL
 WHICH WILL REQUIRE AN ENGINEER TO DO AN
 ANALYSIS TO SEE IF ANY PORTION MAY BE RE
 MOVED. A THRESHHOLD INSPECTOR WILL ALSO
 BE REQUIRED FOR THE DURATION OF THE
 PROJECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 17:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-07-18 Cont ID  
Sent By rturnque Date 2001-07-18 Time 10:50 Rev Time 0.10
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-14 Cont ID  
Sent By pkrauss Date 2001-09-14 Time 10:35 Rev Time 0.40
Received By pkrauss Date 2001-09-14 Time 10:35 Sent To  
Notes
2001-09-14 00:00:00COMBINING 2 EXISTING APARTMENTS INTO 1 -
 A/C FOR BOTH UNITS EXISTING.MOVING
 SOME DUCTWORK FOR NEW HI-HATS, REPLACING
 WITH SAME SIZE AND NUMBER OF DROPS AND
 GRILLES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-07 Cont ID  
Sent By pkrauss Date 2001-09-07 Time 14:52 Rev Time 0.45
Received By pkrauss Date 2001-09-07 Time 14:37 Sent To  
Notes
2001-09-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.MAKE, MODEL AND LOCATION OF EXISTING
 EQUIPMENT.
  
 2.PLEASE SHOW LOCATIONS OF RETURN AIR.
  
 3.INDICATE SIZE OF DUCT/GRILLS BEING
 REMOVED AS WELL AS SIZE OF DUCT,
 GRILLS AND CFM DISTRIBUTION FOR NEW
 DUCTWORK.
  
 PRIOR TO CONNECTING TO ANY EXISTING DUCT
 WORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-18 Cont ID  
Sent By pschmitz Date 2001-10-18 Time 10:55 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-18 00:00:00REVISION FOR VENT ON NEW SINK AAV, OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-05 Cont ID  
Sent By kstevens Date 2001-09-05 Time 16:47 Rev Time 0.50
Received By kstevens Date 2001-09-05 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-14 Cont ID  
Sent By jleech Date 2001-07-14 Time 06:55 Rev Time 0.50
Received By jleech Date 2001-07-14 Time 06:55 Sent To  
Notes
2001-07-14 00:00:00DENIED;
  
 NOT ENOUGH INFORMATION;
  
 1.NEED LOCATION OF KITCHEN SINK.
  
 2.WHERE IS SINK IN PRINCESS ROOM TO BE
 LOCATED?
  
 3.SHOW LAUNDRY AND KITCHEN TO BE DELETED
  
 4.SHOW WHAT ROOMS GET NEW PLUMBING
 FIXTURES.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-18 Cont ID  
Sent By lsmith Date 2001-07-18 Time 10:28 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***