| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-29 |
Time |
09:46 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-29 00:00:00 | PLAN REVIEW | | | PERMIT# 01061510 | | | 525 S FLAGLER 9C/9D | | | | | | 1)- ADDITIONAL INFORMATION REQUIRED | | | ADMINISTRATIVE CODE AMENDMENTS 104.2.2 | | | THE WALL SEEPERATING THE (2) UNITS, IS | | | THIS A DRYWALL WALL OR IS THIS BLOCK OR | | | A COMMON SHEER WALL? IF THIS IS A SOLID | | | CONCRETE WALL THEN IT IS A SHEER WALL | | | WHICH WILL REQUIRE AN ENGINEER TO DO AN | | | ANALYSIS TO SEE IF ANY PORTION MAY BE RE | | | MOVED. A THRESHHOLD INSPECTOR WILL ALSO | | | BE REQUIRED FOR THE DURATION OF THE | | | PROJECT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-10 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-10 |
Time |
17:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-07-18 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2001-07-18 |
Time |
10:50 |
Rev Time |
0.10 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-14 |
Time |
10:35 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-14 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2001-09-14 00:00:00 | COMBINING 2 EXISTING APARTMENTS INTO 1 - | | | A/C FOR BOTH UNITS EXISTING.MOVING | | | SOME DUCTWORK FOR NEW HI-HATS, REPLACING | | | WITH SAME SIZE AND NUMBER OF DROPS AND | | | GRILLES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-07 |
Time |
14:52 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-09-07 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2001-09-07 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.MAKE, MODEL AND LOCATION OF EXISTING | | | EQUIPMENT. | | | | | | 2.PLEASE SHOW LOCATIONS OF RETURN AIR. | | | | | | 3.INDICATE SIZE OF DUCT/GRILLS BEING | | | REMOVED AS WELL AS SIZE OF DUCT, | | | GRILLS AND CFM DISTRIBUTION FOR NEW | | | DUCTWORK. | | | | | | PRIOR TO CONNECTING TO ANY EXISTING DUCT | | | WORK, CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-10-18 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-18 |
Time |
10:55 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-18 00:00:00 | REVISION FOR VENT ON NEW SINK AAV, OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-09-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-05 |
Time |
16:47 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-09-05 |
Time |
16:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-14 |
Time |
06:55 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2001-07-14 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2001-07-14 00:00:00 | DENIED; | | | | | | NOT ENOUGH INFORMATION; | | | | | | 1.NEED LOCATION OF KITCHEN SINK. | | | | | | 2.WHERE IS SINK IN PRINCESS ROOM TO BE | | | LOCATED? | | | | | | 3.SHOW LAUNDRY AND KITCHEN TO BE DELETED | | | | | | 4.SHOW WHAT ROOMS GET NEW PLUMBING | | | FIXTURES. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|