Plan Review Details - Permit 01061475
Plan Review Stops For Permit 01061475
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-24 Cont ID  
Sent By lhatten Date 2001-10-24 Time 16:00 Rev Time 1.00
Received By lhatten Date 2001-10-24 Time 15:57 Sent To  
Notes
2001-10-24 00:00:00ASBUILT FOR INTERIOR RENOVATION AS WELL
 AS ELEVATIONS PER HISTORIC PRESERVATION
 10/24/2001
 SAME AS ABOVE 10/24/2001

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-07-20 Cont ID  
Sent By mmclean Date 2001-07-20 Time 16:16 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2001-07-20 00:00:00OK PER TOM SUFFLIED TO PRINT PERMIT
 07/20/01 MM

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-10-19 Cont ID  
Sent By dpalmer Date 2001-10-19 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2001-10-19 Time 10:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-11 Cont ID  
Sent By dpalmer Date 2001-10-11 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2001-10-11 Time 15:40 Sent To  
Notes
2001-10-11 00:00:00******** UNSAT ******
  
 SEE REDLINES ON PLANS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 18:30 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 18:30 Sent To  
Notes
2001-09-24 00:00:00PLANS ARE JUST NOW BEING SUBMITTED FOR
 REVIEW. ELEC PERMIT WAS ISSUED IN ERROR
 AS TURN AROUND WITH NO PLANS.
 OWES AS REVISION, NOT A RE-STAMP.
 PLANS WERE NEVER SUBMITTED FOR PLAN
 REVIEW. PERMIT WAS ISSUED AS MISC
 UNDER A PRE- INSPECT. PER TOM SUFF

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-23 Cont ID  
Sent By kstevens Date 2001-10-23 Time 14:33 Rev Time 0.33
Received By kstevens Date 2001-10-23 Time 14:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-17 Cont ID  
Sent By dpalmer Date 2001-10-19 Time 10:03 Rev Time 0.50
Received By kstevens Date 2001-10-17 Time 17:13 Sent To  
Notes
2001-10-17 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) RISER DIAGRAM NOT APPROVED. MANY
 FIXTURES MISSING, BAR SINK 1ST FLOOR,
 TUB, SHR, LAV, MASTER BATH, W/C, SHR, &
 LAV 2ND BATH. BATH #3 NOT DRAWN CORRECT-
 LY, SHOWS DRAINING UP TO CEILING.
 PLEASE RESUBMIT SANITARY RISER DIAGRAM
 THAT REFLECTS FLOOR PLAN AND HAS ALL
 FIXTURES. PLEASE SHOW ALL PIPE SIZES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 15:04 Rev Time 0.33
Received By kstevens Date 2001-10-11 Time 15:04 Sent To  
Notes
2001-10-11 00:00:00DENIED
 REFERENCE SPC-94
  
 1) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM THAT REFLECTS THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-20 Cont ID  
Sent By lsmith Date 2001-07-20 Time 09:21 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***