| Plan Review Stops For Permit 01061355 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-01 |
Time |
09:02 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-24 |
Time |
10:30 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01061355 | | | ADDRESS: 3230 COMMERCE PLACE | | | SUITE : "A" | | | CONT: PDC DEVELOPMENT CORP | | | TEL: (561) 793-5852 | | | | | | SECOND REQUEST ADD INFO: | | | 1)- PROVIDE THE TEST DATA AND OR REPORTS | | | FOR THE NEW WINDOWS AND GLASS / ALUM | | | DOOR. SBC AMEND 1606.4.1/ 1707.4.1 | | | SBCCI OR DADE COUNTY PRODUCT APPROVAL | | | REPORT ARE REQUIRED. | | | 2)- SBC 1606.2.6.2:COMPONENTS & CLADDING | | | SHOW WINDOW & DOOR BUCK DETAIL ATTACH- | | | MENT. | | | 3)- SBC 1606.2.6.2: SHOW THE DESIGN PRES | | | SURES FOR THE NEW WINDOWS & DOOR. | | | 4)- SBC 104.2.2* HOW WILL THE I HR. | | | RATED WALL (UL# U 465), HOW WILL THE | | | DRYWALL BE ATTACHED TO THE STUDS WHEN | | | THE WALL STANDS NEXT TO AN EXISTING WALL | | | ALSO HOW WILL THE JOINT TAPE AND COM- | | | POUND BE APPLIED TO THE SIDE ADJACENT TO | | | THE EXISTING WALL? | | | 5)- HIGHLIGHT THE WORK SPECIFICIALLY, | | | WHAT PORTION OF WORK SHOWN ON THE PLAN | | | IS INTENDED TO BE ACCOMPLISHED FOR THE | | | DECLARED VALUE OF $12,000.00UNDER THIS | | | PERMIT APPLICATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-11 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-11 00:00:00 | PLEASE PROVIDE A RECENT SURVEY AND AN | | | ELEVATIONOF THE WALLS RECEIVING NEW | | | OPENINGS SO THAT COMPLIANCE WITH TABLE | | | 600 MAY BE DETERMINED.SHOW THE INTERIO | | | R CEILING HEIGHT ALSO. | | | | | | SPECIFICALLY WHAT PORTION OF THE WORK | | | SHOWN ON THE PLANS IS INTENDED TO BE | | | ACCOMPLISHED FOR THE $12000 VALUATION | | | DECLARED ON THE PERMIT APPLICATION?? | | | | | | PROVIDE THE TEST DATA AND OR REPORTS FOR | | | THE NEW WINDOWS. | | | | | | SHOW THE DESIGN PRESSURES FOR THE | | | WINDOWS ON THE PLANS. | | | | | | WHAT IS THE PRESENT USE / OCCUPANCY OF | | | THIS SPACE? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-26 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-26 |
Time |
07:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-01 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-01 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2001-08-01 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR PANELS "C&D" BEFORE ROUGH INSPECTION | | | IS CALLED IN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-30 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-30 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2001-07-30 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT UNLESS A 2HR | | | SEPARATION IS INSTALLED. A SEPARATE | | | SERVICE MAY NOT BE INSTALLED. 230-2 | | | PLEASE NOTE THAT I DID HAVE A MEETING | | | WITH THE CHIEF ELECTRICAL INSPECTOR | | | (JAKE LEAHY) AND NO HARDSHIP EXISTS, | | | FOR THE EXCEPTION IN ART 230-2. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-09 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-09 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2001-07-09 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT UNDER 230-2 | | | A SEPARATE SERVICE IS NOT PERMITTED. | | | TO HAVE A SEPARATE SERVICE THE SPACE | | | WOULD HAVE TO HAVE A 2HR SEPARATION FOR | | | BUILDING REQMENTS. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS FOR NEW | | | MAIN DISCONNECTS. | | | | | | 3)NOTE: PLEASE NOTE THAT PERMIT APPLICA- | | | -TION MENTIONS A NEW SUB-PANEL BUT NOTH- | | | -ING IS SHOWNON RISER DIAGRAM.? | | | PLEASE CLARIFY. | | | | | | 4)NOTE: PLEASE PROVIDE CLARIFICATION | | | ON RISER SHOWING AN 800A OVERHEAD DROP | | | TO A 1200A SERVICE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-08-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-01 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-25 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-25 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-07-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-05 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-05 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2001-07-05 00:00:00 | 1) DOES THE NEW ONE HOUR WALL EXTEND | | | THE ENTIRE DISTANCE OF THE WALL. | | | 2) PLEASE CLARIFY THE LOCATIONS OF THE | | | TENANT SEPARATIONS. | | | 3) PLEASE IDENTIFY LOCATIONS OF THE | | | TWO TENANT SPACES. DO THEY SHARE OR | | | HAVE ANY COMMON SPACES. | | | 4) IS THE BUILDING FIRE SPRINKLER | | | PROTECTED. | | | 5) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-24 |
Time |
08:03 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-07-24 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-09 |
Time |
11:20 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-07-09 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2001-07-09 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE REVISED OUTSIDE AIR | | | CALCULATIONS FOR THIS RENOVATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-17 |
Time |
08:42 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-09-17 |
Time |
08:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-03 |
Time |
16:04 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-08-03 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-07-24 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-07-24 |
Time |
15:18 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-24 00:00:00 | PLUMBING PLAN REVIEW DENIED,2ND TIME | | | PLEASE ADDRESS PREVIOUS COMMENTS,7-7-01 | | | (1) SHT-1 COMPLY W/SEC 407.1.3 MINIMUM | | | FACILITIES:USE TAB 407 TO CACULATE THE | | | NUMBER OF FIXTURES FOR THE MEN,WOMEN'S | | | REST RM'S BASED ON SQUARE FOOTAGE. | | | (2) COMPLY W/FACBC SEC 4.1.8.3 URINALS, | | | URINAL TO BE CENTERED IN THE 30"X 48" | | | CLEAR FLOOR SPACE. | | | (3) BREAK ROOM SINK COMPLY W/FACBC SEC. | | | 4.24.5 CLEAR FLR SPACE IN FRONT OF SINK, | | | FRONT OR SIDE APPROACH. | | | SEC 4.24.2 HIGHT OF COUNTER, 34" AFF. | | | SEC 4.24.3 KNEE CLEARANCE, 27" HIGH, | | | 30" WIDE, & 19" DEEP SHALL BE PROVIDED | | | UNDER SINK. | | | (4)SHT-5, WTR HTR TO BE READLY ACESSIBLE | | | SEC 501.7,SHOW A DETAIL OF HOW THIS WILL | | | BE BE DONE IN A CABNET. | | | (5) DWV ISOMETRIC,URI & LAV,ON A CROSS. | | | 2-LAV'S TIED TOGETHER ON 2 WASTE RISERS. | | | (6) TRAP PRIMERS REQ.ON F/D'S IN PUBLIC | | | REST RM'S,SEC 409.4 | | | (7)SHT-5,WATER RISER: COMPLY W/SEC 607.8 | | | NOTE #12 REFERES TO AIR CHAMBERS,NOT APP | | | ROVED IN CEILING AS WELL AS WATER HAMMER | | | ARRESTORS. PROVIDE MFG INSTRUCTIONS ON | | | SIZE AND PLACEMENT. | | | END OF COMMENTSPAULSCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-07 |
Time |
13:01 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
2001-07-07 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2001-07-07 00:00:00 | DENIED; | | | | | | 1.SHOW SQUIRE FOOTAGE OF OFFICE.COMPLY | | | WITH 94 SPC TABLE 407 FOR MINIMUM | | | PLUMBING FIXTURES. | | | | | | 2.HANDICAP STALL DETAIL ON SHT.#1 ; | | | DIAMENTIONS ARE NOT THE SAME AS FLOOR | | | PLAN. SEE DEPARTMENT OF COMMUNITY | | | AFFAIRS RULE 9B-7.0042FL ADMIN CODE. | | | NOTES OF CHANGE. | | | | | | 3.WATER HEATER IN CABINET SHALL BE | | | READILY ACCESSIBLE. | | | | | | 4.LOUNGE SINK SHALL COMPLY WITH FACBC | | | SEC. 4.24 THRU 4.24.7. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-08-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-03 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|