Plan Review Details - Permit 01061355
Plan Review Stops For Permit 01061355
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-01 Cont ID  
Sent By jwitmer Date 2001-08-01 Time 09:02 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-07-24 Cont ID  
Sent By jwitmer Date 2001-07-24 Time 10:30 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01061355
 ADDRESS: 3230 COMMERCE PLACE
 SUITE : "A"
 CONT: PDC DEVELOPMENT CORP
 TEL: (561) 793-5852
  
 SECOND REQUEST ADD INFO:
 1)- PROVIDE THE TEST DATA AND OR REPORTS
 FOR THE NEW WINDOWS AND GLASS / ALUM
 DOOR. SBC AMEND 1606.4.1/ 1707.4.1
 SBCCI OR DADE COUNTY PRODUCT APPROVAL
 REPORT ARE REQUIRED.
 2)- SBC 1606.2.6.2:COMPONENTS & CLADDING
 SHOW WINDOW & DOOR BUCK DETAIL ATTACH-
 MENT.
 3)- SBC 1606.2.6.2: SHOW THE DESIGN PRES
 SURES FOR THE NEW WINDOWS & DOOR.
 4)- SBC 104.2.2* HOW WILL THE I HR.
 RATED WALL (UL# U 465), HOW WILL THE
 DRYWALL BE ATTACHED TO THE STUDS WHEN
 THE WALL STANDS NEXT TO AN EXISTING WALL
 ALSO HOW WILL THE JOINT TAPE AND COM-
 POUND BE APPLIED TO THE SIDE ADJACENT TO
 THE EXISTING WALL?
 5)- HIGHLIGHT THE WORK SPECIFICIALLY,
 WHAT PORTION OF WORK SHOWN ON THE PLAN
 IS INTENDED TO BE ACCOMPLISHED FOR THE
 DECLARED VALUE OF $12,000.00UNDER THIS
 PERMIT APPLICATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-11 Cont ID  
Sent By hpiskura Date 2001-07-11 Time 09:23 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-07-11 00:00:00PLEASE PROVIDE A RECENT SURVEY AND AN
 ELEVATIONOF THE WALLS RECEIVING NEW
 OPENINGS SO THAT COMPLIANCE WITH TABLE
 600 MAY BE DETERMINED.SHOW THE INTERIO
 R CEILING HEIGHT ALSO.
  
 SPECIFICALLY WHAT PORTION OF THE WORK
 SHOWN ON THE PLANS IS INTENDED TO BE
 ACCOMPLISHED FOR THE $12000 VALUATION
 DECLARED ON THE PERMIT APPLICATION??
  
 PROVIDE THE TEST DATA AND OR REPORTS FOR
 THE NEW WINDOWS.
  
 SHOW THE DESIGN PRESSURES FOR THE
 WINDOWS ON THE PLANS.
  
 WHAT IS THE PRESENT USE / OCCUPANCY OF
 THIS SPACE?

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-09-26 Cont ID  
Sent By dpalmer Date 2001-09-26 Time 07:20 Rev Time 0.00
Received By dpalmer Date 2001-09-26 Time 07:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-08-01 Cont ID  
Sent By dpalmer Date 2001-08-01 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2001-08-01 Time 16:42 Sent To  
Notes
2001-08-01 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR PANELS "C&D" BEFORE ROUGH INSPECTION
 IS CALLED IN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-07-30 Cont ID  
Sent By dpalmer Date 2001-07-30 Time 09:00 Rev Time 0.00
Received By dpalmer Date 2001-07-30 Time 09:00 Sent To  
Notes
2001-07-30 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT UNLESS A 2HR
 SEPARATION IS INSTALLED. A SEPARATE
 SERVICE MAY NOT BE INSTALLED. 230-2
 PLEASE NOTE THAT I DID HAVE A MEETING
 WITH THE CHIEF ELECTRICAL INSPECTOR
 (JAKE LEAHY) AND NO HARDSHIP EXISTS,
 FOR THE EXCEPTION IN ART 230-2.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-07-09 Cont ID  
Sent By dpalmer Date 2001-07-09 Time 16:27 Rev Time 0.00
Received By dpalmer Date 2001-07-09 Time 16:27 Sent To  
Notes
2001-07-09 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT UNDER 230-2
 A SEPARATE SERVICE IS NOT PERMITTED.
 TO HAVE A SEPARATE SERVICE THE SPACE
 WOULD HAVE TO HAVE A 2HR SEPARATION FOR
 BUILDING REQMENTS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS FOR NEW
 MAIN DISCONNECTS.
  
 3)NOTE: PLEASE NOTE THAT PERMIT APPLICA-
 -TION MENTIONS A NEW SUB-PANEL BUT NOTH-
 -ING IS SHOWNON RISER DIAGRAM.?
 PLEASE CLARIFY.
  
 4)NOTE: PLEASE PROVIDE CLARIFICATION
 ON RISER SHOWING AN 800A OVERHEAD DROP
 TO A 1200A SERVICE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-01 Cont ID  
Sent By jwitmer Date 2001-08-01 Time 09:07 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-25 Cont ID  
Sent By mcarsill Date 2001-07-25 Time 11:03 Rev Time 0.00
Received By mcarsill Date 2001-07-25 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By mcarsill Date 2001-07-05 Time 08:24 Rev Time 0.00
Received By mcarsill Date 2001-07-05 Time 08:24 Sent To  
Notes
2001-07-05 00:00:001) DOES THE NEW ONE HOUR WALL EXTEND
 THE ENTIRE DISTANCE OF THE WALL.
 2) PLEASE CLARIFY THE LOCATIONS OF THE
 TENANT SEPARATIONS.
 3) PLEASE IDENTIFY LOCATIONS OF THE
 TWO TENANT SPACES. DO THEY SHARE OR
 HAVE ANY COMMON SPACES.
 4) IS THE BUILDING FIRE SPRINKLER
 PROTECTED.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-24 Cont ID  
Sent By pkrauss Date 2001-07-24 Time 08:03 Rev Time 0.35
Received By pkrauss Date 2001-07-24 Time 08:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-07-09 Cont ID  
Sent By pkrauss Date 2001-07-09 Time 11:20 Rev Time 0.45
Received By pkrauss Date 2001-07-09 Time 11:04 Sent To  
Notes
2001-07-09 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE REVISED OUTSIDE AIR
 CALCULATIONS FOR THIS RENOVATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-09-17 Cont ID  
Sent By kstevens Date 2001-09-17 Time 08:42 Rev Time 0.50
Received By kstevens Date 2001-09-17 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-03 Cont ID  
Sent By kstevens Date 2001-08-03 Time 16:04 Rev Time 1.00
Received By kstevens Date 2001-08-03 Time 16:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-07-24 Cont ID  
Sent By pschmitz Date 2001-07-24 Time 15:18 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-24 00:00:00PLUMBING PLAN REVIEW DENIED,2ND TIME
 PLEASE ADDRESS PREVIOUS COMMENTS,7-7-01
 (1) SHT-1 COMPLY W/SEC 407.1.3 MINIMUM
 FACILITIES:USE TAB 407 TO CACULATE THE
 NUMBER OF FIXTURES FOR THE MEN,WOMEN'S
 REST RM'S BASED ON SQUARE FOOTAGE.
 (2) COMPLY W/FACBC SEC 4.1.8.3 URINALS,
 URINAL TO BE CENTERED IN THE 30"X 48"
 CLEAR FLOOR SPACE.
 (3) BREAK ROOM SINK COMPLY W/FACBC SEC.
 4.24.5 CLEAR FLR SPACE IN FRONT OF SINK,
 FRONT OR SIDE APPROACH.
 SEC 4.24.2 HIGHT OF COUNTER, 34" AFF.
 SEC 4.24.3 KNEE CLEARANCE, 27" HIGH,
 30" WIDE, & 19" DEEP SHALL BE PROVIDED
 UNDER SINK.
 (4)SHT-5, WTR HTR TO BE READLY ACESSIBLE
 SEC 501.7,SHOW A DETAIL OF HOW THIS WILL
 BE BE DONE IN A CABNET.
 (5) DWV ISOMETRIC,URI & LAV,ON A CROSS.
 2-LAV'S TIED TOGETHER ON 2 WASTE RISERS.
 (6) TRAP PRIMERS REQ.ON F/D'S IN PUBLIC
 REST RM'S,SEC 409.4
 (7)SHT-5,WATER RISER: COMPLY W/SEC 607.8
 NOTE #12 REFERES TO AIR CHAMBERS,NOT APP
 ROVED IN CEILING AS WELL AS WATER HAMMER
 ARRESTORS. PROVIDE MFG INSTRUCTIONS ON
 SIZE AND PLACEMENT.
 END OF COMMENTSPAULSCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 13:01 Rev Time 1.00
Received By pschmitz Date 2001-07-07 Time 13:01 Sent To  
Notes
2001-07-07 00:00:00DENIED;
  
 1.SHOW SQUIRE FOOTAGE OF OFFICE.COMPLY
 WITH 94 SPC TABLE 407 FOR MINIMUM
 PLUMBING FIXTURES.
  
 2.HANDICAP STALL DETAIL ON SHT.#1 ;
 DIAMENTIONS ARE NOT THE SAME AS FLOOR
 PLAN. SEE DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9B-7.0042FL ADMIN CODE.
 NOTES OF CHANGE.
  
 3.WATER HEATER IN CABINET SHALL BE
 READILY ACCESSIBLE.
  
 4.LOUNGE SINK SHALL COMPLY WITH FACBC
 SEC. 4.24 THRU 4.24.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-03 Cont ID  
Sent By kstevens Date 2001-08-03 Time 16:11 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***