| Plan Review Stops For Permit 01061304 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-04-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-22 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-22 00:00:00 | THE STAIR AND PLATFORM SHOP DRAWINGS | | | PREPARED BY RON UPHOFF, ARCH. HAVE | | | INADEQUATE INFORMATION. | | | | | | THE STAIR RISERS SHOWN AS 8.43" DO NOT | | | COMPLY WITH SBC 1007.3.1. | | | | | | THE 1" PIPE DOES NOT COMPLY WITH SBC | | | 1007.5.3.SEE ALSO 1022.4. | | | | | | SEE SBC 1007.5.5 FOR EXTENSIONS AT TOP | | | AND BOTTOM. | | | | | | OPEN SIDED STAIRS REQUIRE 42" HIGH | | | HAND/GUARD RAILS.SEE SBC 1015.1. | | | | | | PROVIDE SPECIFIC CONNECTION DETAILS. | | | TERMS SUCH AS "FULL FILLET WELD" ARE | | | INADEQUATE.SEE SBC 2207. | | | | | | PROVIDE CALCULATIONS DEMONSTRATING | | | COMPLIANCE WITH SBC 1604.1 AND 1608.2. | | | | | | WHAT IS 2" X #9 EXPANDED METAL? |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-21 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-25 |
Time |
15:04 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-25 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01061304 | | | 6554 N JOG ROAD | | | 640-4000 | | | | | | SBC= STANDARD BUILDING CODE | | | SBC* = STANDARD BUILDING CODE AMENDMENTS | | | | | | 1)- SBC 1804.2* SOILS REPORT WITH THE | | | BEARING VALUE | | | | | | 2)- SBC 222203.1 PRE-ENGINEERED BUILDING | | | REQUIRES SIGNED, SEALED RAISED SEAL | | | DRAWINGS BY AN REGISTERED ENGINEER | | | BEFORE A PERMIT CAN BE ISSUED. | | | | | | 3)- 104.2.2. ADD INFO REQUIRED: DETAILS | | | ON CLOSING THE OPEN END BETWEEN THE | | | NEW & OLD BUILDINGS. | | | | | | 4)- INFORMATION ON THE PRESORT PLATFORM | | | AND STAIRS LEADING TO PLATFORM? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-30 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-30 |
Time |
17:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-09-20 |
Time |
09:03 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-09-20 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2001-09-20 00:00:00 | PASSED: | | | 1. PLEASE CALL RODNEY COMPO, FOR | | | INSPECTION AND CONNECTION TO EXISTING | | | OIL/WATER SEPARATOR, 837-4074 EXT. 4074 | | | | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-07-02 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-02 |
Time |
11:26 |
Rev Time |
4.00 |
| Received By |
mamini |
Date |
2001-07-02 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2001-07-02 00:00:00 | FAILED : | | | 1. PLEASE PROVIDE STORM WATER | | | CALCULATIONS DUE TO THE CHANGES FOR OUR | | | REVIEW. | | | 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS | | | CALCULATIONS FOR ENTIRE SITE, DUE TO THE | | | CHANGES. | | | 3. PLEASE INCLUDE PLANS, NOTES, DETAILS | | | TO DIRECT THE CONTRACTOR TO PROTACT THE | | | EXISTING CATCH BASINS AND STORM WATER | | | SYS. DURING THE CONSTRUCTION. | | | 4. AN APPROVED BACKFLOW PREVENTER ASS. | | | WILL NEED TO BE INSTALLED, IF NOT | | | ALREADY IN PLACE AT THE POINT OF SERVICE | | | ON PRIVATE PROPERTY. | | | 5. A CLEAN-OUT WILL NEED TO BE INSTALLED | | | IN SANITARY SEWER LATERAL, ON THE | | | PROPERTY IF NOT ALREADY INSTALLED. | | | 6. THE CITY'S STANDARD DETAILS MAY BE | | | OBTAIN THROUGH PUBLIC UTILITIES | | | ENGINEERING SERVICES. 659-8040 | | | | | | IF ANY QUESTION PLEASE CONTACT 659- 8096 | | | EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-20 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-20 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2001-09-20 00:00:00 | 1) EXIT DOORS REQUIRE HARDWARE THAT | | | IS OBVIOUS TO OPERATE EVEN IN | | | DARKNESS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-06 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-06 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2001-08-06 00:00:00 | 1) PLEASE EXPLAIN USE OF BUILDING. | | | PLEASE INDICATE NUMBER OF EMPLOYEES | | | AND HOURS OF OPERATION. | | | 2) IS THE BUILDING USED FOR STORAGE OR | | | INDUSTRIAL PURPOSES. | | | 3) PLEASE CLEARLY INDICATE ALL | | | EMERGENCY LIGHT FIXTURE LOCATIONS. | | | 4) PLEASE INDICATE WHAT FIRE PROTECTION | | | FEATURES ARE PRESENT IN THE EXISTING | | | BUILDING. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-26 |
Time |
10:08 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-09-26 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW. | | | | | | PLEASE SUBMIT PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-08-20 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-15 |
Time |
16:46 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-15 00:00:00 | BACK FLOW PREVENTERS TO BE CK IN FIELD. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-09 |
Time |
17:47 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-07-09 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2001-07-09 00:00:00 | DENIED; | | | | | | 1.SHOW SIZE, TYPE AND LOCATION OF | | | BACKFLOW PROTECTION 94 SPC SEC. 606. | | | | | | 2.SHOW DRAINS FOR EYEWASH AND DRENCH | | | SHOWERS. | | | | | | 3.SHOW CALKULATIONS FOR OIL INTERCEPTER | | | IS INTERCEPTER LARGE ENOUGH TO EXCEPT | | | THE ADDITIONAL FLOW? | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-18 |
Time |
16:33 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | LANDSCAPING MUST COMPLY WITH THE CODE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-08-20 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-08-20 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|