Plan Review Details - Permit 01061304
Plan Review Stops For Permit 01061304
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-04-22 Cont ID  
Sent By hpiskura Date 2002-04-22 Time 10:10 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-22 00:00:00THE STAIR AND PLATFORM SHOP DRAWINGS
 PREPARED BY RON UPHOFF, ARCH. HAVE
 INADEQUATE INFORMATION.
  
 THE STAIR RISERS SHOWN AS 8.43" DO NOT
 COMPLY WITH SBC 1007.3.1.
  
 THE 1" PIPE DOES NOT COMPLY WITH SBC
 1007.5.3.SEE ALSO 1022.4.
  
 SEE SBC 1007.5.5 FOR EXTENSIONS AT TOP
 AND BOTTOM.
  
 OPEN SIDED STAIRS REQUIRE 42" HIGH
 HAND/GUARD RAILS.SEE SBC 1015.1.
  
 PROVIDE SPECIFIC CONNECTION DETAILS.
 TERMS SUCH AS "FULL FILLET WELD" ARE
 INADEQUATE.SEE SBC 2207.
  
 PROVIDE CALCULATIONS DEMONSTRATING
 COMPLIANCE WITH SBC 1604.1 AND 1608.2.
  
 WHAT IS 2" X #9 EXPANDED METAL?

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-21 Cont ID  
Sent By hpiskura Date 2001-09-21 Time 13:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-25 Cont ID  
Sent By jwitmer Date 2001-07-25 Time 15:04 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-25 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01061304
 6554 N JOG ROAD
 640-4000
  
 SBC= STANDARD BUILDING CODE
 SBC* = STANDARD BUILDING CODE AMENDMENTS
  
 1)- SBC 1804.2* SOILS REPORT WITH THE
 BEARING VALUE
  
 2)- SBC 222203.1 PRE-ENGINEERED BUILDING
 REQUIRES SIGNED, SEALED RAISED SEAL
 DRAWINGS BY AN REGISTERED ENGINEER
 BEFORE A PERMIT CAN BE ISSUED.
  
 3)- 104.2.2. ADD INFO REQUIRED: DETAILS
 ON CLOSING THE OPEN END BETWEEN THE
 NEW & OLD BUILDINGS.
  
 4)- INFORMATION ON THE PRESORT PLATFORM
 AND STAIRS LEADING TO PLATFORM?

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-30 Cont ID  
Sent By dpalmer Date 2001-07-30 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2001-07-30 Time 17:57 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-09-20 Cont ID  
Sent By mamini Date 2001-09-20 Time 09:03 Rev Time 4.00
Received By mamini Date 2001-09-20 Time 09:03 Sent To  
Notes
2001-09-20 00:00:00PASSED:
 1. PLEASE CALL RODNEY COMPO, FOR
 INSPECTION AND CONNECTION TO EXISTING
 OIL/WATER SEPARATOR, 837-4074 EXT. 4074
  
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-07-02 Cont ID  
Sent By mamini Date 2001-07-02 Time 11:26 Rev Time 4.00
Received By mamini Date 2001-07-02 Time 11:26 Sent To  
Notes
2001-07-02 00:00:00FAILED :
 1. PLEASE PROVIDE STORM WATER
 CALCULATIONS DUE TO THE CHANGES FOR OUR
 REVIEW.
 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATIONS FOR ENTIRE SITE, DUE TO THE
 CHANGES.
 3. PLEASE INCLUDE PLANS, NOTES, DETAILS
 TO DIRECT THE CONTRACTOR TO PROTACT THE
 EXISTING CATCH BASINS AND STORM WATER
 SYS. DURING THE CONSTRUCTION.
 4. AN APPROVED BACKFLOW PREVENTER ASS.
 WILL NEED TO BE INSTALLED, IF NOT
 ALREADY IN PLACE AT THE POINT OF SERVICE
 ON PRIVATE PROPERTY.
 5. A CLEAN-OUT WILL NEED TO BE INSTALLED
 IN SANITARY SEWER LATERAL, ON THE
 PROPERTY IF NOT ALREADY INSTALLED.
 6. THE CITY'S STANDARD DETAILS MAY BE
 OBTAIN THROUGH PUBLIC UTILITIES
 ENGINEERING SERVICES. 659-8040
  
 IF ANY QUESTION PLEASE CONTACT 659- 8096
 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-20 Cont ID  
Sent By mcarsill Date 2001-09-20 Time 15:05 Rev Time 0.00
Received By mcarsill Date 2001-09-20 Time 15:04 Sent To  
Notes
2001-09-20 00:00:001) EXIT DOORS REQUIRE HARDWARE THAT
 IS OBVIOUS TO OPERATE EVEN IN
 DARKNESS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 09:16 Sent To  
Notes
2001-08-06 00:00:001) PLEASE EXPLAIN USE OF BUILDING.
 PLEASE INDICATE NUMBER OF EMPLOYEES
 AND HOURS OF OPERATION.
 2) IS THE BUILDING USED FOR STORAGE OR
 INDUSTRIAL PURPOSES.
 3) PLEASE CLEARLY INDICATE ALL
 EMERGENCY LIGHT FIXTURE LOCATIONS.
 4) PLEASE INDICATE WHAT FIRE PROTECTION
 FEATURES ARE PRESENT IN THE EXISTING
 BUILDING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-09-26 Cont ID  
Sent By pkrauss Date 2001-09-26 Time 10:08 Rev Time 0.35
Received By pkrauss Date 2001-09-26 Time 10:02 Sent To  
Notes
2001-09-26 00:00:00INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.
  
 PLEASE SUBMIT PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-08-20 Cont ID  
Sent By lsmith Date 2001-08-20 Time 16:45 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-15 Cont ID  
Sent By pschmitz Date 2001-10-15 Time 16:46 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-15 00:00:00BACK FLOW PREVENTERS TO BE CK IN FIELD.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-09 Cont ID  
Sent By jleech Date 2001-07-09 Time 17:47 Rev Time 1.50
Received By jleech Date 2001-07-09 Time 17:47 Sent To  
Notes
2001-07-09 00:00:00DENIED;
  
 1.SHOW SIZE, TYPE AND LOCATION OF
 BACKFLOW PROTECTION 94 SPC SEC. 606.
  
 2.SHOW DRAINS FOR EYEWASH AND DRENCH
 SHOWERS.
  
 3.SHOW CALKULATIONS FOR OIL INTERCEPTER
 IS INTERCEPTER LARGE ENOUGH TO EXCEPT
 THE ADDITIONAL FLOW?
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 2 Status P Date 2001-09-18 Cont ID  
Sent By sgraham Date 2001-09-18 Time 16:33 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-09-18 00:00:00LANDSCAPING MUST COMPLY WITH THE CODE

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-20 Cont ID  
Sent By lsmith Date 2001-08-20 Time 16:45 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***