| Plan Review Stops For Permit 01061258 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-17 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-07 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO | | | BE SEPARATED FROM THE REMAINDER OF THE | | | BUILDING WITH ONE HOUR CONSTRUCTION AND | | | TWENTY MINUTE RATED OPENING PROTECTIVES. | | | A "WATER CURTAIN" IN AND OF ITSELF IS | | | NOT A LISTED ASSEMBLY OR A SUBSTITUTE | | | FOR ONE. | | | | | | SEE SBC 705.1.3 FOR OPENING PROTECTION | | | REQUIREMENTS. | | | | | | SEE SBC TABLE 705.1.2 FOR ELEVATOR SHAFT | | | DOOR RATINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-10 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-07-10 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2001-07-10 00:00:00 | PROVIDE THE TEST REPORT FOR THE WATER | | | CURTAIN AT THE GLASS DOOR. | | | | | | NOTE 11 ON G2 RE PLANTONS FOR DOORS | | | MUST COMPLY WITH NFPA 80 | | | | | | NOTE 22, G2 RE UNDERCUT OF DOORS MUST | | | COMPLY WITH NFPA 80 FOR ANY FIRE RATED | | | DOORS. | | | | | | A LIFE SAFETY PLAN MUST ACCOMPANY THE | | | PERMIT FOR THE TEMPORARY DEMISING OF | | | THEFLOOR PLAN SHOWN ON SHEET D1.TWO | | | INDEPENDENT MEANS OF EGRESS MUST BE | | | MAINTAINED.SBC 1004.2.2 | | | | | | DOOR #123D AT THE ELEVATOR LOBBY IS | | | REQUIRED TO BE 20 MINUTE FIRE RATED. | | | SEE SBC 412.6.1. | | | | | | PROVIDE THE HC ACCESSIBILTY TO THE | | | TOILET ROOMS AND DRINKING FOUNTAINS AS | | | REQUIRED BY FCBC 4.1.6. (2) (A)(III) | | | AND (V) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
19:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-07-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-08 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-08 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-07-26 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-07-26 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-31 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-31 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-17 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-17 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-08 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-08 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | 1) PLEASE PROVIDE RATING OR TEST | | | REPORTS FOR GLASS ENTRY DOORS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-06-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-27 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-27 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-06-27 00:00:00 | 1) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS FOR TENANT SPACE. | | | 2) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 3) PLEASE PROVIDE MORE DETAILS ON DOORS | | | WHERE "WATER CURTAIN" IS PLANNED. IS THE | | | GLASS TEMPERED, SAFETY OR HAVE A FIRE | | | RATING. | | | 4) PLEASE PROVIDE MORE INFORMATION ON | | | SECURITY FEATURES PLANNED FOR EXIT | | | DOORS. DO THE SECURITY FEATURES THAT ARE | | | PLANNED MEET THE REQUIREMENTS OF SPECIAL | | | LOCKING ARRANGEMENTS IN THE LIFE SAFETY | | | CODE, 1985 EDITION. ARE THESE DOORS | | | FAIL SAFE OR FAIL SECURE IN THE EVENT OF | | | A PROBLEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-01 |
Time |
14:02 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-11-01 |
Time |
14:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-10 |
Time |
14:13 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-07-10 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-02-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-02-10 |
Time |
11:03 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-10 00:00:00 | REVISION,OK PES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-10-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-27 |
Time |
09:04 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-27 00:00:00 | PLUMBING PLAN REVIEW, PROVISO SEE SHTS | | | P0.1,P2.2PAUL SCHMITZ |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-06 |
Time |
17:33 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-08-06 |
Time |
17:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-07-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-07-07 |
Time |
10:16 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-07-07 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2001-07-07 00:00:00 | DENIED; | | | | | | 1.KITCHEN SINK SHALL COMPLY WITH FACBC | | | 4.24.2, 4.24.3, 4.24.5, AND 4.24.6. | | | | | | 2.FLOOR DRAINS SHALL BE USED IN PLACE OF | | | HUB DRAINS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-07-26 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-07-26 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|