Plan Review Details - Permit 01061258
Plan Review Stops For Permit 01061258
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-17 Cont ID  
Sent By hpiskura Date 2001-08-17 Time 10:14 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-07 Cont ID  
Sent By hpiskura Date 2001-08-07 Time 09:02 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-07 00:00:00SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO
 BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH ONE HOUR CONSTRUCTION AND
 TWENTY MINUTE RATED OPENING PROTECTIVES.
 A "WATER CURTAIN" IN AND OF ITSELF IS
 NOT A LISTED ASSEMBLY OR A SUBSTITUTE
 FOR ONE.
  
 SEE SBC 705.1.3 FOR OPENING PROTECTION
 REQUIREMENTS.
  
 SEE SBC TABLE 705.1.2 FOR ELEVATOR SHAFT
 DOOR RATINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-10 Cont ID  
Sent By hpiskura Date 2001-07-10 Time 09:49 Rev Time 0.00
Received By hpiskura Date 2001-07-10 Time 08:51 Sent To  
Notes
2001-07-10 00:00:00PROVIDE THE TEST REPORT FOR THE WATER
 CURTAIN AT THE GLASS DOOR.
  
 NOTE 11 ON G2 RE PLANTONS FOR DOORS
 MUST COMPLY WITH NFPA 80
  
 NOTE 22, G2 RE UNDERCUT OF DOORS MUST
 COMPLY WITH NFPA 80 FOR ANY FIRE RATED
 DOORS.
  
 A LIFE SAFETY PLAN MUST ACCOMPANY THE
 PERMIT FOR THE TEMPORARY DEMISING OF
 THEFLOOR PLAN SHOWN ON SHEET D1.TWO
 INDEPENDENT MEANS OF EGRESS MUST BE
 MAINTAINED.SBC 1004.2.2
  
 DOOR #123D AT THE ELEVATOR LOBBY IS
 REQUIRED TO BE 20 MINUTE FIRE RATED.
 SEE SBC 412.6.1.
  
 PROVIDE THE HC ACCESSIBILTY TO THE
 TOILET ROOMS AND DRINKING FOUNTAINS AS
 REQUIRED BY FCBC 4.1.6. (2) (A)(III)
 AND (V)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 19:19 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 19:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-08 Cont ID  
Sent By dpalmer Date 2001-07-08 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2001-07-08 Time 13:56 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-26 Cont ID  
Sent By lsmith Date 2001-07-26 Time 11:15 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-10-31 Cont ID  
Sent By mcarsill Date 2001-10-31 Time 12:39 Rev Time 0.00
Received By mcarsill Date 2001-10-31 Time 12:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-17 Cont ID  
Sent By mcarsill Date 2001-08-17 Time 14:54 Rev Time 0.00
Received By mcarsill Date 2001-08-17 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-08-08 Cont ID  
Sent By mcarsill Date 2001-08-08 Time 12:01 Rev Time 0.00
Received By mcarsill Date 2001-08-08 Time 12:01 Sent To  
Notes
2001-08-08 00:00:001) PLEASE PROVIDE RATING OR TEST
 REPORTS FOR GLASS ENTRY DOORS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-27 Cont ID  
Sent By mcarsill Date 2001-06-27 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2001-06-27 Time 10:49 Sent To  
Notes
2001-06-27 00:00:001) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR TENANT SPACE.
 2) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 3) PLEASE PROVIDE MORE DETAILS ON DOORS
 WHERE "WATER CURTAIN" IS PLANNED. IS THE
 GLASS TEMPERED, SAFETY OR HAVE A FIRE
 RATING.
 4) PLEASE PROVIDE MORE INFORMATION ON
 SECURITY FEATURES PLANNED FOR EXIT
 DOORS. DO THE SECURITY FEATURES THAT ARE
 PLANNED MEET THE REQUIREMENTS OF SPECIAL
 LOCKING ARRANGEMENTS IN THE LIFE SAFETY
 CODE, 1985 EDITION. ARE THESE DOORS
 FAIL SAFE OR FAIL SECURE IN THE EVENT OF
 A PROBLEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-01 Cont ID  
Sent By pkrauss Date 2001-11-01 Time 14:02 Rev Time 0.35
Received By pkrauss Date 2001-11-01 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-07-10 Cont ID  
Sent By pkrauss Date 2001-07-10 Time 14:13 Rev Time 1.30
Received By pkrauss Date 2001-07-10 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-02-10 Cont ID  
Sent By pschmitz Date 2002-02-10 Time 11:03 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-02-10 00:00:00REVISION,OK PES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-27 Cont ID  
Sent By pschmitz Date 2001-10-27 Time 09:04 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-27 00:00:00PLUMBING PLAN REVIEW, PROVISO SEE SHTS
 P0.1,P2.2PAUL SCHMITZ

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-06 Cont ID  
Sent By jleech Date 2001-08-06 Time 17:33 Rev Time 1.00
Received By jleech Date 2001-08-06 Time 17:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-07-07 Cont ID  
Sent By jleech Date 2001-07-07 Time 10:16 Rev Time 1.00
Received By jleech Date 2001-07-07 Time 10:16 Sent To  
Notes
2001-07-07 00:00:00DENIED;
  
 1.KITCHEN SINK SHALL COMPLY WITH FACBC
 4.24.2, 4.24.3, 4.24.5, AND 4.24.6.
  
 2.FLOOR DRAINS SHALL BE USED IN PLACE OF
 HUB DRAINS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-26 Cont ID  
Sent By lsmith Date 2001-07-26 Time 11:15 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***