Plan Review Details - Permit 01061187
Plan Review Stops For Permit 01061187
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 15:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By dpalmer Date 2001-07-31 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2001-07-31 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By dpalmer Date 2001-07-05 Time 17:36 Rev Time 0.00
Received By dpalmer Date 2001-07-05 Time 17:36 Sent To  
Notes
2001-07-05 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN DISCONNECT AND
 PANEL AND PANEL AND PANEL "H".
 GROUNDING OF TRANSFORMER.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 15:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-06-28 Cont ID  
Sent By mcarsill Date 2001-06-28 Time 09:55 Rev Time 0.00
Received By mcarsill Date 2001-06-28 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-31 Cont ID  
Sent By pkrauss Date 2001-07-31 Time 11:43 Rev Time 0.35
Received By pkrauss Date 2001-07-31 Time 11:43 Sent To  
Notes
2001-07-31 00:00:00ADDRESSED PROVISOS FROM 1ST REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-07-06 Cont ID  
Sent By pkrauss Date 2001-07-06 Time 07:17 Rev Time 0.40
Received By pkrauss Date 2001-07-06 Time 07:05 Sent To  
Notes
2001-07-06 00:00:00*******************PROVISO**************
  
  
 PLEASE DUCT O.A. TO THE VICINITY OF EACH
 HEAT PUMP TO ENSURE EACH HEAT PUMP HAS
 O.A..
  
  
 NO COMBUSTIBLES ABOVE THE CEILING IN
 THERETURN AIR PLENUM AS PER 1997 SMC
 609.1.1.
  
 NOTE:HP2 ON THE SCHEDULE INDICATES
 1200 CFM, PLAN INDICATES 1450
 CFM BEING DISTRIBUTED. PLEASE
 VERIFY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 15:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-09 Cont ID  
Sent By hpiskura Date 2001-07-09 Time 15:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***