Plan Review Details - Permit 01061173
Plan Review Stops For Permit 01061173
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-03 Cont ID  
Sent By dpalmer Date 2001-07-03 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2001-07-03 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-15 Cont ID  
Sent By hmoser Date 2001-08-15 Time 19:38 Rev Time 0.50
Received By hmoser Date 2001-08-15 Time 19:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-07-30 Cont ID  
Sent By hmoser Date 2001-06-25 Time 19:10 Rev Time 0.33
Received By hmoser Date 2001-06-25 Time 19:10 Sent To  
Notes
2001-07-30 00:00:00PLANS DENIED
 #1 PLANS ARE NOT STAMPED
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-22 Cont ID  
Sent By jleech Date 2001-09-22 Time 11:46 Rev Time 0.33
Received By jleech Date 2001-09-22 Time 11:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-26 Cont ID  
Sent By kstevens Date 2001-06-26 Time 10:49 Rev Time 0.50
Received By kstevens Date 2001-06-26 Time 10:48 Sent To  
Notes
2001-06-26 00:00:00...PROVISO...
  
 SEPARATION WALL REQUIRED TO KEEP FLAM-
 ABLE MATERIAL AWAY FROM GAS W/HEATER
 PER SGC-97 SEC 504.3 (IN CLOSET)

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2002-10-22 Cont ID  
Sent By rmcdouga Date 2002-10-22 Time 15:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-22 00:00:00SUBMITTAL FOR BUTT GLASS WITH LETTER
 FROM ARCHITECT REVISING POSITIVE AND
 NEGATIVE WINDLOAD PRESSURES FOR THE
 OPENING IS OK.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2002-10-17 Cont ID  
Sent By rmcdouga Date 2002-10-17 Time 17:28 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-17 00:00:00SUBMITTAL FOR BUTT GLASS DENIED. THE
 LETTER FROM THE ARCHITECT STATES THAT
 THE CALCULATIONS FOR THE REVISED WIND
 LOAD PRESSURE AT THE BUTT GLASS WINDOW
 IS ATTACHED. HOWEVER NO CALCULATIONS
 WERE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2002-10-10 Cont ID  
Sent By rmcdouga Date 2002-10-10 Time 17:29 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-10-10 00:00:00SUBMITTAL DENIED
  
 BUTT GLAZING
  
 1) THE ENGINEERING FOR THE BUTT GLAZING
 MUST BE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD FOR THE STRUCTURE.
  
 2) THE WIND PRESSURE AT THIS OPENING IS
 GIVEN AS -48 AND +47 PSF ON SHEET A-5 OF
 THE PLANS. THE PRODUCT ENGINEERING IS
 ONLY GOOD FOR -34.2 AND +33.6 PSF.
  
  
 FRONT DOORS
  
 1) THE PRODUCT APPROVAL SUBMITTAL FORM
 IS ILLEGIBLE.
  
 2) THE ENGINEER'S SIGNATURE IS NOT
 ORIGINAL.
  
 3) THE ENGINEER'S NAME AND LICENSE
 NUMBER SHOULD BE ON DOCUMENT AND BE
 LEGIBLE.
  
 4) INSTALLATION SITE LOCATION IS
 REQUIRED TO BE ON THE FORM.
  
 5) THE DESIGNER OF RECORD IS REQUIRED TO
 REVIEW AND APPROVE THE INFORMATION AND
 SIGN AND SEAL THE FORM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-10-05 Cont ID  
Sent By rmcdouga Date 2001-10-05 Time 16:26 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-05 00:00:00REVISION OK W/PROVISO 10-5-01 RM
 PROVISO
 PROVIDE DETAIL DRAWING OF C13 STEEL
 COLUMN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-29 Cont ID  
Sent By rmcdouga Date 2001-08-29 Time 16:11 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-08-29 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - CASEMENT WINDOWS
 - STRUCTURAL MULLIONS (DOOR & WINDOW
 ASSEMBLIES)
  
 NOTE: ALL EXTERIOR GLAZING MUST BE
 IMPACT RESISTANT OR A SEPARATE PERMIT
 FOR STORM PANELS WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-27 Cont ID  
Sent By rmcdouga Date 2001-07-27 Time 11:14 Rev Time 5.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-27 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE EGRESS WINDOW IN EXERCISE
 ROOM, WHICH COULD BE USED AS A SLEEPING
 ROOM. 97 SBC 1005.4
  
 3) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
  
 4) PROVIDE AT LEAST ONE BATHROOM WITH A
 DOOR THAT HAS A 29" CLEAR OPENING PER 97
 FLORIDA ACCESSIBILITY CODE 4.22.2.
  
 5) PROVIDE ROOF FRAMING PLAN FOR CHIMNEY
 INDICATING CONNECTORS THAT WILL BE USED
 TO ANCHOR TRUSSES.
  
 6) THE NAIL SPACING FOR ROOFS USING 8D
 COMMON NAILS IN ZONE 3 IS 4" AT THE
 EDGES AND 6" INTERMEDIATE PER CITY
 AMENDMENTS TO THE 97 SBC SEC.2306.
 PLEASE CORRECT SCHEDULE ON SHEET A-8.
  
 7) PLEASE CLARIFY DETAIL AA-2 AND AA-3
 INDICATED ON SHEET A-7. THEY ARE NOT
 SHOWN ON SHEET A-8.
  
 8) SPECIFY THE CONNECTORS FOR ALL OF THE
 TRUSSES NOT SPECIFICALLY INDICATED ON
 SHEET A-7.
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS FOR WINDOW
 ASSEMBLIES
 - STRUCTURAL MULLIONS FOR DOOR WITH
 TRANSOM ABOVE ASSEMBLIES
 - CASEMENT WINDOWS
  
 NOTE: ALL EXTERIOR GLAZINGS TO BE IMPACT
 GLASS OR STORM PANELS WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-25 Cont ID  
Sent By sgraham Date 2001-06-25 Time 15:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***