Plan Review Details - Permit 01061165
Plan Review Stops For Permit 01061165
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-28 Cont ID  
Sent By pkrauss Date 2001-06-28 Time 08:54 Rev Time 1.00
Received By pkrauss Date 2001-06-26 Time 11:23 Sent To  
Notes
2001-06-28 00:00:00*******************PROVISO**************
  
  
 THE FOLLOWING NOTES WERE NEVER ADDRESSED
 ON PLAN REVIEW WITH MASTER PERMIT
 #00071404.
  
 PLEASE PROVIDE ENERGY EFFICIENCY RATING
 OF SYSTEM AS PER FLORIDA ENERGY EFFIENCY
 CODE.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION BY FIRE ALARM SYSTEM OR
 TIED IN TO HORM/STROBE AS PER NFPA 90A
 4-4.4.2 OF 4-4.4.3.
  
 SEPERATE PLANS AND PERMIT FOR FIRE
 SUPRESSION SYSTEM.
  
 NOTE:EQUIPMENT ON ROOF SHALL COMPLY
 WITH AMENDED 1997 SMC 304.2.5,
 18" MINIMUM BETWEEN ROOF SURFACE
 AND BOTTOM OF SUPPORT RAIL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.