Plan Review Details - Permit 01061114
Plan Review Stops For Permit 01061114
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-09-27 Cont ID  
Sent By bstaples Date 2001-09-27 Time 10:20 Rev Time 0.00
Received By bstaples Date   Time   Sent To  
Notes
2001-09-27 00:00:00THREE REVISIONS TO FOUNDATION PERMIT 39
 PAGES OF DRAWINGS AND TWO PACKAGES OF
 CUT SHEETS, PRODUCT APPROVALS AND
 LETTERS.
 REVISION DATED 9/20/01 FOR TWO SETS AND
 PLANS DATED 9/17/01.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-09-05 Cont ID  
Sent By lmartine Date 2001-09-05 Time 09:52 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-05 00:00:00DUCT BANK REVISIONOK LM 8/31/013

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-08-24 Cont ID  
Sent By bstaples Date 2001-08-24 Time 09:12 Rev Time 1.50
Received By bstaples Date   Time   Sent To  
Notes
2001-08-24 00:00:00SPECIAL INSPECTION PLAN RECEIVED AND
 FILED WITH PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-08-22 Cont ID  
Sent By lsmith Date 2001-08-22 Time 13:10 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2001-08-22 00:00:00PER BILL STAPLES:
  
 1. SPECIAL INSPECTOR PLAN, SUBMIT FOR
 REVIEW & APPROVAL.
  
 ALL COMMENTS FROM 7/18/01 REVIEW ARE
 OKAY LS 8/22/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-18 Cont ID  
Sent By bstaples Date 2001-07-18 Time 11:33 Rev Time 4.00
Received By bstaples Date   Time   Sent To  
Notes
2001-07-18 00:00:00FOUNDATION PERMIT REVIEW COMMENTS.
 1. PAY IMPACT FEES.
 2. SPECIAL INSPECTOR PLAN, SUBMIT FOR
 REVIEW AND APPROVAL.
 3. PERMIT DOES NOT INCLUDE ANY WORK
 ABOVE THE SLAB.
 4. PROVIDE EASEMENT INFORMAION FOR ALL
 ENCROACHMENTS, IE: BELL SOUTH DUCT BANK
 SEE S3-1.1.
 5. SOIL TEST REPORTS SUBMIT.
 6. SHEET S4-1.1 QUESTION WHY IS FLOOR
 LOAD REDUCED IN CLASSROOM AREA FROM 100
 PSF TO 40 PSF, NOT REQUIRED FOR
 FOUNDATION PERMIT.
 7. SEE CITY CODE AMENDMENTS SECTION
 1804.1.1 ALL FOOTINGS SHALL BE FORMED.
 8. SEE CITY CODE AMENDMENTS FOR MASONERY
 CONSTRUCTION SECTION 2111.6 FOR WATER
 STOP DETAIL.
 9. NOTE SECTION 1 ON S6-1.6 RISE AND
 RUN OF STAIRS NOT IN COMPLIANCE WITH
 SBC1007.3.1 AND 1007.3.1B.
 CONTACT BILL STAPLES AT 561-659-8096 IF
 ANY QUESTIONS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-07-18 Cont ID  
Sent By bstaples Date 2001-07-18 Time 11:31 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-07-18 00:00:00OK FOR UNDERGROUND INDICATED IN SET
 CONDUCT ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-07-10 Cont ID  
Sent By mcarsill Date 2001-07-10 Time 16:23 Rev Time 0.00
Received By mcarsill Date 2001-07-10 Time 16:23 Sent To  
Notes
2001-07-10 00:00:00APPROVAL FOR FOUNDATION ONLY.

Review Stop P PLUMBING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2001-10-24 00:00:00PLUMBING PLAN REVIEW APPROVED
 FOR FOUNDATION ONLY, PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-26 Cont ID  
Sent By pschmitz Date 2001-09-26 Time 05:35 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-26 00:00:00PLUMBING FOUNDATION PLAN REVIEW,PROVISO
 (1) SHT P2-1.3 TRASH COMPACTOR TRENCH
 DRAIN TO GREASE WASTE.
 (2)SHT P2-1.7, 3" VENT ON CONDENSATE NOT
 APPROVED, PROVIDE A 3" RELIEF VENT OUT
 SIDE, TERMINATE 6" ABOVE GRADE WITH A
 180 DEGREE ELBOW.
 WHEN THE BUILDING IS SUBJECT TO BACK
 WATER (CONDENSATE) A BACK WATER VALVE
 IS REQUIRED,SPC-94 SEC 1101.5
 (3) SHT P2-4.2 OVER-FLO-DAINS TIED
 TOGETHER,ARCHITURAL PLANS SHOW
 INDIVIDUAL DRAINS?
 (4) SHT P2-1.8 RWL COL 20 & W, TICKET
 OFFICE AREA, 4" RWL TIED IN TWICE, ALSO
 1" CONDENSATE TO BE RUN SEPERATE.
 (5) SHT P2-1.7 RM #1E22 TRASH HOLDING
 AREA, WHAT TYPE OF TRASH IS STORED HERE?
 IF THIS IS RESTAURANT WASTE, THIS F/D
 WILL NEED TO GO TO GREASE WASTE.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561 659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-07-21 Cont ID  
Sent By pschmitz Date 2001-07-21 Time 07:38 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-07-21 00:00:00PLUMBING PLAN REVIEW,FOUNDATION ONLY
 CODE REFERENCES,STD PLBG-94,STD GAS-97,
 FL ACCESSIBILTY CODE FOR BLDG CONST-97
 BUILDINGPLAN REVIEW TO FOLLOW
 "PROVISO"
 ALL WORK PER CITY CODES,SUBJECT TO FIELD
 INSPECTOR APPROVAL.
 (1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW AND COMMENTS BEFORE PLUMBING
 PLAN REVIEW APPROVAL, 954-958-5520.
 (2) GREASE TRAP TO BE SIZED BY W. PALM
 BCH RSTP, ENVIROMENTAL COMPLIANCE.
 CONTACT, RODNEY COMPO 561-837-4074.
 LOCAL ORD# 2938-96. SEPERATE PERMIT REQ.
 (3) MODEL CNTY WIDE AMENDMENTS TO SPC-94
 SEC 804.3 A/C CONDENSATE, PROVIDE COMMON
 SYSTEM FOR ENTIRE BLDG, CONNECTED TO THE
 STORM DRAINAGE,OUT SIDE OF THE BUILDING,
 WITH A RELIEF VENT.
 (4) MINIMUM FACILITIES SEC 407.1.3 SHOW
 CALCULATIONS FOR NUMBER OF PERSONS FOR
 THE ENTIRE BLDG,BROKEN DOWN TO THE REST
 RM'S IN EACH AREA, FOR PLAN REVIEW APPR.
 (5) PUBLIC REST RM'S TO COMPLY W/FACBC97
 TOILET STALLS, SIZE AND ARRANGMENT, DCA
 RULE 9B-7.0042, FL ADM CODE ,FIG 30(E).
 SIX OR MORE W/C,SEC 4.23.4-ONE ADDITONAL
 STALL.SIZE & DOOR SWING, SEC 4.17.3.
 URINAL SEC 4.18 HEIGHT,CLEAR FLR SPACE.
 (6) SEC 409.4 FLR DRAINS IN PUBLIC REST
 RM'S, TRAP PRIMERS REQ.
 (7) SEC 104.3 PLANS,SANITARY SEWER.SHOW
 FIXTURE LOAD ON ENTIRE SYSTEM,INCLUDING
 BRANCHES. PRIOR TO INSTALLATION.
 (8)ELEVATOR SUMP PITS,QUESTION ON DRAIN.
 (9) SHT P2-1.3 COL C-C8,13-14, CAN WASH,
 TO GREASE WASTE, LOCAL ORD# 2938-96
 (10) DISH WASHERS, TO SANITARY SEWER,
 LOCAL ORD# 2938-96.
 (11) ALL INDIRECT WASTE TO FLR SINKS,
 NO HUB DRAINS.SEC SEC 802.
 (12) SHTS P2-1.2 TO P2-1.8 EXHIBIT AREA
 DRAINS. COMPLY W/SEC 921,"HORIZONTAL"
 COMBINATION WASTE AND VENT SYSTEM, SEE
 PG-275,276 ILLUSTRATIONS, NO DRY VENTS.
 (13)SHT P2-1.1 REST RM,IN-23,24.TYPICAL.
 SEC 914, CIRUIT & LOOP VENTS, FIXTURES
 FROM UPPER FLRS SHALL NOT DISCHARGE INTO
 A BATTERY VENTED BRANCH.
 (14) SHT P2-1.1 TO P2-1.8 EXHIBIT AREA,
 PROVIDE MFG. CUT SHEET ON UTILITY BOX,
 PRIOR TO INSTALLATION, FOR APPROVAL.
 (15) SHT P2-1.1 TO P2-2.8, U/G PRIMARY
 STORM DRAINAGE SYSTEM, SEC 1108.2.2
 PROVIDE CALCULATIONS FOR DRAINAGE SYSTEM
 ,INCLUDE CALCULATIONS FOR VERTICAL WALLS
 SEC 1108.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS 561 659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2001-07-19 Cont ID  
Sent By sgraham Date 2001-07-19 Time 07:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-07-19 00:00:00DOES NOT INCCLUDE FIRE DEPT ACCESS
 CONNECTION/GATE AT SW CORNER