Plan Review Details - Permit 01061017
Plan Review Stops For Permit 01061017
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-25 Cont ID  
Sent By jleahy Date 2001-06-25 Time 10:44 Rev Time 0.39
Received By jleahy Date 2001-06-25 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-25 Cont ID  
Sent By pkrauss Date 2001-06-25 Time 11:44 Rev Time 0.30
Received By pkrauss Date 2001-06-25 Time 11:44 Sent To  
Notes
2001-06-25 00:00:00RESUB OKAY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-21 Cont ID  
Sent By pkrauss Date 2001-06-21 Time 09:45 Rev Time 0.45
Received By pkrauss Date 2001-06-21 Time 09:44 Sent To  
Notes
2001-06-21 00:00:00*******************DENIED***************
  
  
 ONLY ONE COPY OF PLAN SUBMITTED, NEED
 TWO.
  
 PLEASE DESIGNATE R/A SIZE ON PLAN.
  
 WHERE IS CONDENSATE BEING DISPOSED OF?
 NOTE:UNITS LARGER THAN 3 TON SHALL
 DRAIN TO STORM DRAIN OR APPROVED DRY
 WELL. (1997 SMC 304.8. #1)
  
 WHAT MATERIAL IS DUCTWORK?ALSO SIZE OF
 DUCT AND CFM BEING DISTRIBUTED.
  
 PLEASE INDICATE HOW AHU IS BEING
 SUPPORTED AND MATERIALS USED.
  
 NOTE:AS PER 1997 SMC 304.8.6.1,
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.