Plan Review Details - Permit 01061001
Plan Review Stops For Permit 01061001
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 14:24 Rev Time 0.75
Received By mcarsill Date 2001-08-14 Time 13:32 Sent To  
Notes
2001-08-02 00:00:001) PROPANE INSTALLATION TO COMPLY
 WITH NFPA 58 AND RECOGNIZED STANDARDS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-07-03 Cont ID  
Sent By mcarsill Date 2001-07-03 Time 14:10 Rev Time 0.00
Received By mcarsill Date 2001-07-03 Time 14:10 Sent To  
Notes
2001-07-03 00:00:001) PLEASE CLARIFY HOW MANY POOL HEATERS
 THERE ARE. ONLY TWO ARE SHOWN AND SEVEN
 ARE MENTIONED.
 2) PLEASE PROVIDE INFORMATION REQUESTED
 BY THE PLUMBING DIVISION SO THE PLANS
 CAN BE APPROVED.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-21 Cont ID  
Sent By mcarsill Date 2001-06-21 Time 13:38 Rev Time 0.00
Received By mcarsill Date 2001-06-21 Time 13:38 Sent To  
Notes
2001-06-21 00:00:001) PLEASE PROVIDE INFORMATION ON THE
 DEPTH OF THE BURIED UNDERGROUND PROPANE
 TANKS WITH REGARDS TO FINISHED GRADE.
 2) PLEASE INDICATE SEPARATION DISTANCES
 BETWEEN THE INDIVIDUAL PROPANE TANKS.
 3) PLEASE INDICATE SEPARATION DISTANCES
 OF THE TANKS TO ALL BUILDINGS, PROPERTY
 LINES, ETC.
 4) PLEASE PROVIDE INFORMATION ON ANY
 REGULATORS OR OTHER APPURTENANT
 EQUIPMENT.
 5) PLEASE PROVIDE MORE DETAILS ON
 POOL HEATERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-01-09 Cont ID  
Sent By pschmitz Date 2002-01-09 Time 16:01 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-09 00:00:00ADD ONE POOL HTR, TOT OF EIGHT.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-08-14 Cont ID  
Sent By kstevens Date 2001-08-14 Time 13:33 Rev Time 0.75
Received By kstevens Date 2001-08-14 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-08-03 Cont ID  
Sent By kstevens Date 2001-08-03 Time 11:29 Rev Time 0.50
Received By kstevens Date 2001-08-03 Time 11:29 Sent To  
Notes
2001-08-03 00:00:00DENIED
  
 1) ITEM #1 OF PREVIOUS COMMENTS NOT ADD-
 RESSED. SITE PLAN SHALL BE SIGNED AND
 SEALED. SEE ATTACHED SHEETS.
  
 REVIEW KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-07-02 Cont ID  
Sent By kstevens Date 2001-07-02 Time 15:13 Rev Time 0.75
Received By kstevens Date 2001-07-02 Time 15:13 Sent To  
Notes
2001-07-02 00:00:00FAILED
  
 1) SITE PLAN SHALL BE SIGNED AND SEALED
 AS PER #7 OF PRIOR PLAN REVIEW NOTES.
  
 2) ALL POOL HEATER LOCATIONS NOT SHOWN
 ON RESUBMITTAL. SHOW ALL 7 POOL HEATERS
 AND THEIR LOCATIONS.
  
 3) DISTANCE TO MOST REMOTE HEATER NOT
 SHOWN ON SUBMITTAL. PLEASE SHOW THIS
 MEASUREMENT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-21 Cont ID  
Sent By kstevens Date 2001-06-21 Time 15:31 Rev Time 1.50
Received By kstevens Date 2001-06-21 Time 15:30 Sent To  
Notes
2001-06-21 00:00:00REVIEW NOTES:FAILED
  
 REFERENCE NFPA-58 & SGC-97
  
 1) CONTAINERS TO BE MIN. OF 10' APART,
 AND 10' FROM ANY BLDG. OR EXTERIOR
 SOURCE OF IGNITION.
 SECTS. 3-2.2.2 (F), AND TABLE 3-2.2.2 (D
  
 2) UNDERGROUND CONTAINERS TO BE SECURELY
 ANCHORED PER SEC. 3-2.2.7 (H)
  
 3) PROVIDE PROTECTON AGAINST VEHICULAR
 DAMAGE PER 3.2.4.8 (B)
  
 4) AN ANODE BAG SHALL BE INSTALLED ON
 EACH CONTAINER PER 3-2.4.8 (F)
  
 5) SUBMIT MANUFACTURE SPEC. SHEET FOR
 EACH POOL HEATER TO VERIFY COMPLIENCE
 WITH STANDARDS OF NFPA 58 & SGC-97
 SEC 402.
  
 6) SUBMIT MANUFACTURE SPEC. SHEET ON P.E
 PIPE, AND SUBMIT A COPY OF THE SIZING
 TABLE FROM SGC-97 PER SGC SEC. 302.
  
 7) SUBMIT A SITE PLAN WITH WALK-WAYS,
 DRIVE-WAYS, PARKING LOTS, STRUCTURES,
 PROPERTY LINES, OR ANY STRUCTURES
 THAT MAY AFFECT THE PLACING OF THE
 CONTAINERS. THESE PLANS MUST BE SIGNED
 AND SEALED BY AN ARCHITECH OR AN
 ENGINEER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377