Plan Review Details - Permit 01060828
| Plan Review Stops For Permit 01060828 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-07-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-13 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-07-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-07-13 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-04 |
Time |
09:37 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01060828 | | | 2805-A PINEWOOD AVE | | | CONT: ALLIANCE CONST. | | | PHONE: 748-9135 | | | | | | 1)- IN REVIEWING THIS PLAN THE 1997 | | | STANDARD BUILDING CODE DOES NOT ALLOW | | | A WAREHOUSE OF 3150 SQ FT TO HAVE A SIN- | | | GLE MEANS OF EGRESS. | | | SBC 1027.1.1 SINGLE EXIT REQUIREMENTS | | | FOR STORAGE OCCUPANCY: | | | 1- ONE STORY MAXIMUM | | | 2- THE FLOOR AREA DOES NOT EXCEED | | | 2,500 SQ FT | | | 3- THE MAXIMUM DISTANCE OF TRAVEL TO | | | THE EXIT DOES NOT EXCEED 50 FT. | | | | | | 2)- SBC 1004.1.4: WHERE 2 OR MORE EXITS | | | OR EXIT DOORS ARE REQUIRED, AT LEAST 2 | | | EXITS OR EXIT ACCESS DOORS SHALL BE | | | PLACED A DISTANCE AAPART EQUAL TO BUT | | | NOT LESS THAN ONE HALF THE LENGTH OF THE | | | MAXIMUMOVERALL DIAGONAL DIMENSION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-07-09 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-07-09 |
Time |
17:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-28 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-28 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2001-06-28 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NO LIGHTING IS | | | SHOWN. EXIT/EGRESS. ETC 210-70 | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | SHOW ALL BRANCH CIRCUIT #`S ON PLANS | | | AND NEED TO CORRELATE W/ PANEL SCHEDULE | | | 215-5 | | | | | | 3)NOTE: PLEASE NOTE THAT LOAD | | | CALCULATIONS DO NOT SHOW ANY OTHER | | | LOADS. | | | | | | PLEASE SUBMIT MORE INFORMATION FOR | | | REVIEW. IF THERE AREANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-09 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-09 |
Time |
12:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-06-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-20 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-20 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2001-06-20 00:00:00 | 1) A SINGLE MEANS OF EGRESS IS NOT | | | PERMITTED FROM EXISTING STORAGE SPACE. | | | AT LEAST TWO MEANS OF EGRESS ARE | | | REQUIRED SINCE EXCEPTIONS FOR A SINGLE | | | MEANS OF EGRESS DOES NOT APPLY | | | ACCORDING TO THE DRAWINGS THAT WERE | | | SUBMITTED. | | | 2) PLEASE PROVIDE A SECOND MEANS OF | | | EGRESS FROM THE BUILDING THAT IS AT | | | LEAST 1/2 THE DIAGONAL DISTANCE FROM | | | THE EXISTING ONE. | | | 3) PLEASE IDENTIFY LOCATIONS OF EXIT | | | SIGNS AND EMERGENCY LIGHTING EQUIPMENT. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|