Plan Review Details - Permit 01060828
Plan Review Stops For Permit 01060828
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-07-13 Cont ID  
Sent By hpiskura Date 2001-07-13 Time 11:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-13 Cont ID  
Sent By hpiskura Date 2001-07-13 Time 11:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-04 Cont ID  
Sent By jwitmer Date 2001-07-04 Time 09:37 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060828
 2805-A PINEWOOD AVE
 CONT: ALLIANCE CONST.
 PHONE: 748-9135
  
 1)- IN REVIEWING THIS PLAN THE 1997
 STANDARD BUILDING CODE DOES NOT ALLOW
 A WAREHOUSE OF 3150 SQ FT TO HAVE A SIN-
 GLE MEANS OF EGRESS.
 SBC 1027.1.1 SINGLE EXIT REQUIREMENTS
 FOR STORAGE OCCUPANCY:
 1- ONE STORY MAXIMUM
 2- THE FLOOR AREA DOES NOT EXCEED
 2,500 SQ FT
 3- THE MAXIMUM DISTANCE OF TRAVEL TO
 THE EXIT DOES NOT EXCEED 50 FT.
  
 2)- SBC 1004.1.4: WHERE 2 OR MORE EXITS
 OR EXIT DOORS ARE REQUIRED, AT LEAST 2
 EXITS OR EXIT ACCESS DOORS SHALL BE
 PLACED A DISTANCE AAPART EQUAL TO BUT
 NOT LESS THAN ONE HALF THE LENGTH OF THE
 MAXIMUMOVERALL DIAGONAL DIMENSION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By dpalmer Date 2001-07-09 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2001-07-09 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-28 Cont ID  
Sent By dpalmer Date 2001-06-28 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2001-06-28 Time 15:55 Sent To  
Notes
2001-06-28 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NO LIGHTING IS
 SHOWN. EXIT/EGRESS. ETC 210-70
  
 2)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW ALL BRANCH CIRCUIT #`S ON PLANS
 AND NEED TO CORRELATE W/ PANEL SCHEDULE
 215-5
  
 3)NOTE: PLEASE NOTE THAT LOAD
 CALCULATIONS DO NOT SHOW ANY OTHER
 LOADS.
  
 PLEASE SUBMIT MORE INFORMATION FOR
 REVIEW. IF THERE AREANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-09 Cont ID  
Sent By mcarsill Date 2001-07-09 Time 12:26 Rev Time 0.00
Received By mcarsill Date 2001-07-09 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-20 Cont ID  
Sent By mcarsill Date 2001-06-20 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2001-06-20 Time 10:37 Sent To  
Notes
2001-06-20 00:00:001) A SINGLE MEANS OF EGRESS IS NOT
 PERMITTED FROM EXISTING STORAGE SPACE.
 AT LEAST TWO MEANS OF EGRESS ARE
 REQUIRED SINCE EXCEPTIONS FOR A SINGLE
 MEANS OF EGRESS DOES NOT APPLY
 ACCORDING TO THE DRAWINGS THAT WERE
 SUBMITTED.
 2) PLEASE PROVIDE A SECOND MEANS OF
 EGRESS FROM THE BUILDING THAT IS AT
 LEAST 1/2 THE DIAGONAL DISTANCE FROM
 THE EXISTING ONE.
 3) PLEASE IDENTIFY LOCATIONS OF EXIT
 SIGNS AND EMERGENCY LIGHTING EQUIPMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910