Plan Review Details - Permit 01060807
Plan Review Stops For Permit 01060807
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-17 Cont ID  
Sent By jwitmer Date 2001-07-17 Time 19:39 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-05 Cont ID  
Sent By jwitmer Date 2001-07-05 Time 14:24 Rev Time 1.55
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060807
 ONE N. CLEMATIS # 3 RD FL
 QUEST
 PHONE # 691-9400
  
 1)- OFFICE SPACE DOESN'T MEET THE RE-
 QUIEMENTS FOR A SINGLE MEANS OF EGRESS.
 SBC 1020.1 (1-4) THIS SPACE DOESN'T MEET
 REQUIREMENT 1&4. 1)- BEING THE MAXIMUM
 2 STORIES (BUILDING) IN HEIDTH. 2ND)
 THE MAXIMUM DISTANCE OF TRAVEL TO THE
 EXIT DOES NOT EXCEED 75'.
  
 2)- SINCE THE OFFICE REQUIRES THE (2)
 EXITS SBC 1004.1.4 REQUIRES THAT THE 2
 EXITS OR EXIT ACCESS DOORS SHALL BE
 PLACED A DISTANCEAPART EQUAL TO NOT
 LESS THAN ONE HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE OFFICE. DIAGONAL DISTANCE OF 81'-0".
 81'X 1/2= 40.5' APART. THE PLANS INDI-
 CATE APPROXIMATELY 31'.
  
 3)- DOORS 301 & 307B DO NOT GIVE WHAT
 RATING THEY HAVE? SBC T-705.1.2.
  
 4)- SBC 803.2/ 803.3(TABLE) PLEASE INDIC
 ATE THE MINIMUM INTERIOR FINISH CLASSIFI
 CATION, FLAMESPREAD & SMOKE DEVELOPMENT.
  
 5)- SHEET A-3 FINISH NOTESFOR FLOORS:
 FL ACCEC CODE 4.3.8 CHANGE IN GRADE,
 NOTE 1/4" IN VETICAL CHANGE IN GRADE,
 1/2" IF GRADE HAS A 2/1 RATIO.
  
 6)- FL ACC CODE 4.3.6 SURFACE TEXTURES
 FLOOR SURFACES ALONG THE ACCESSIBLE PATH
 SHALL BE STABLE, FIRM & SLIP RESISTANT.
 (ADDAAG) A-5 A SATATIC COEFIFICIENT OF
 FRICTION OF0.6 ACCESSIBLE ROUTE, 0.8
 ACCESSIBLE ROUTE FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 22:29 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 22:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-06-28 Cont ID  
Sent By dpalmer Date 2001-06-28 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2001-06-28 Time 17:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-02 Cont ID  
Sent By tjonseck Date 2001-07-02 Time 10:31 Rev Time 0.00
Received By tjonseck Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 17:18 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 17:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-07-24 Cont ID  
Sent By rturnque Date 2001-07-24 Time 14:26 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-20 Cont ID  
Sent By mcarsill Date 2001-06-20 Time 15:56 Rev Time 0.00
Received By mcarsill Date 2001-06-20 Time 15:56 Sent To  
Notes
2001-06-20 00:00:001) DOORS 301 AND 307B ARE TO BE PROPERLY
 FIRE RATED. DOOR CLOSERS ARE ALSO
 REQUIRED.
 2) INTERIOR FINISH ON WALLS AND CEILINGS
 SHALL BE AT LEAST A CLASS C FLAME
 SPREAD.
 3) HOW IS THE SUSPENDED TRANSFORMER
 LOCATED IN COPY ROOM 307 AFFECT EXITING.
 WHAT IS THE HEIGHT OF THE TRANSFORMER
 FROM FINISHED FLOOR. DOES THIS
 DEVICE INTERFERE WITH THE DOOR WHEN
 IS IS USED FOR EXITING.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-10-08 Cont ID  
Sent By pkrauss Date 2001-10-08 Time 13:07 Rev Time 0.30
Received By pkrauss Date 2001-10-08 Time 13:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-24 Cont ID  
Sent By pkrauss Date 2001-07-24 Time 09:48 Rev Time 0.45
Received By pkrauss Date 2001-07-24 Time 09:48 Sent To  
Notes
2001-07-24 00:00:00MECHANICAL PERMIT 01060812.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-29 Cont ID  
Sent By pkrauss Date 2001-06-29 Time 09:42 Rev Time 0.40
Received By pkrauss Date 2001-06-29 Time 09:33 Sent To  
Notes
2001-06-29 00:00:00*******************DENIED***************
  
  
 EXISTING DUCTS PENENTRATING CORRIDOR
 WALL INTO TENANT SPACE DO NOT INDICATE
 ANY FIRE DAMPERS.THIS WALL IS
 DESIGNATED 1 HOUR, PLEASE INDICATE FIRE
 DAMPERS ON PLAN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-30 Cont ID  
Sent By jleech Date 2001-06-30 Time 08:27 Rev Time 0.50
Received By jleech Date 2001-06-30 Time 08:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-02 Cont ID  
Sent By tjonseck Date 2001-07-02 Time 10:31 Rev Time 0.00
Received By tjonseck Date   Time   Sent To  
Notes
***NONE***