| 2001-07-05 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01060797 | | | 2200 S DIXIE HWY | | | L. DAVIS CONSTRUCTION | | | P: 848-0577 | | | F: 848-0954 | | | C: 718-8161 | | | | | | 1)- SBC REQUIRES THAT THE RESTROOM WALLS | | | & FLOOR TO BE LINED WITH NONABSORBANT | | | MATERIALS TO A HEIGTH OF 4 FT ABOVE THE | | | FINISH FLOOR. | | | | | | 2)- SBC 803.3.1 INTERIOR FINISH SCHEDULE | | | BASED ON OCCUPANCY, TABLE 803.3. | | | FLAMESPREAD & SMOKE DEVELOPMENT. | | | | | | 3)- FL 1997 ACCESSIBILITY CODE 4.5.1: | | | GROUND AND FLOOR SURFACES ALONG ACCESSIB | | | LE ROUTES AND IN ACCESIBLE ROOMS & | | | SPACES INCLUDING FLOORS RAMPS SHALL BE | | | FIRM, SLIP-RESISTANT. A STATIC COEFIC- | | | IENT OF FRICTION OF 0.6 IS RECOMMENDED | | | FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS. | | | | | | 4)- FL ACC CODE REQUIRES 36" CLEAR | | | ACCESS ISLES, SBC T-1004 REQUIRES CLEAR | | | ISLE WIDTH OF 44" WITH AN OCCUPANT LOAD | | | OF 50 OR >. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-17 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | APPROVED BY JAKE LEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-03 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-03 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-24 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-24 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2001-06-24 00:00:00 | *************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT BOTH EXISTING/ | | | AND NEW PANELS ARE SHOWN W/OUT HAVING | | | MAINS? PLEASE NOTE NO MAIN IS SHOWN | | | OUTSIDE? SOME FORMOF MAIN IS REQ`D PER | | | 225-31/225-32 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE SANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-07-09 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-07-09 |
Time |
08:25 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-07-09 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2001-07-09 00:00:00 | PASSED WITH PROVISOS: | | | 1. IF GARBAGE IS TO BE PICKED UP BY THE | | | CITY THEN, CITY REQUIREMENT MUST BE MET, | | | SEE ATTACHED. | | | 2. SEE ATTACHED CITY STANDARD/DETAILS | | | FOR GREASE TRAP. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-07-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-07-31 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-07-31 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2001-07-31 00:00:00 | 1) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR THE HOOD, DUCT AND EXTINGUISHING | | | SYSTEMS. NO DETAILS PROVIDED FOR THE | | | 3M FIREWRAP SHOWN ON PLANS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-06-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-19 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-19 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2001-06-19 00:00:00 | 2200 SOUTH DIXIE HIGHWAY | | | PERMIT NUMBER 01060797 | | | | | | 1) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION. | | | 2) PLEASE PROVIDE MORE DETAILS ON | | | SANDWICH GRIDDLE. IF THIS ITEM PRODUCES | | | SMOKE OR GREASE LADEN VAPORS, IT MUST | | | BE PROTECTED BY A HOOD,DUCT AND | | | EXTINGUISHING SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-08-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-06 |
Time |
08:00 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-08-06 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2001-08-06 00:00:00 | *******************PROVISO************** | | | | | | | | | AHU BEING RELOCATED SHALL HAVE ADEQUATE | | | ACCESS FOR SERVICE AS PER 1997 SMC | | | 304.2.1. | | | | | | ADDITIONAL PLANS AND PERMIT REQUIRED | | | FORHOOD, FIRE SUPRESSION AND WALK-IN | | | COOLERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-07-10 |
Time |
08:03 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-07-10 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2001-07-10 00:00:00 | *******************DENIED*************** | | | | | | | | | | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | PROVIDE INFORMATION ON EXHAUST FANS FOR | | | GREASE HOOD. | | | | | | ADDITIONAL PERMITS REQUIRED FOR GREASE | | | HOOD SYSTEM, FIRE SUPRESSION AND | | | WALK-IN COOLERS.PLEASE PROVIDE | | | MAUFACTURER SUBMITTAL DATA AND PLANS | | | WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-07 |
Time |
09:10 |
Rev Time |
2.00 |
| Received By |
kstevens |
Date |
2001-08-07 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | PASSED | | | PROVISO | | | | | | 1) LOCKS REQUIRED ON RESTROOOMS FOR | | | PRIVIACY. | | | | | | 2) SEPARATE PERMITS FOR GAS - IRRIGATION | | | AND GREASE TANK (BY PROVIDER). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-08-02 |
Time |
10:38 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | PREVIOUS NOTES FOR PLBG & GAS 06-25-01 | | | REMOVED NO RESPONSE, ADDRESS (9) ITEMS | | | FOR GAS,(12) ITEMS FOR PLUMBING. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-06-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-06-25 |
Time |
17:36 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
2001-06-25 |
Time |
17:36 |
Sent To |
|
|
| Notes |
| 2001-06-25 00:00:00 | FAILED.. | | | | | | 1) SHOW LOCATION OF DISHWASHER. LOCAL | | | ORD. 2839-96. DISHWASHER TO SANT. SEWER. | | | | | | 2) GREASE TRAP SIZE AND LOCATION TO BE | | | APPROVED BY RODNEY COMPO OF THE UTILITY | | | DEPARTMENT. (561) 837-4074 | | | | | | 3) SEPARATE PERMIT FOR GREASE TRAP, | | | ISSUED TO PROVIDER OF GREASE TRAP. | | | | | | 5) PAGE 1.0, EQUIPMENT LIST DOES NOT | | | MATCH EQUIPMENT FLOOR PLAN. | | | | | | 6) TWO WAY CLEAN OUTS REQUIRED OUTSIDE | | | OF BUILDING LINE IN BOTH SANITARY AND | | | GREASE LINES EXITING THE BLDG. | | | | | | 7) SHUT OFF VALVES FOR MENS ROOM NOT | | | SHOWN ON WATER RISER DIAGRAM. PAGE 3.0 | | | | | | 8) SHOW WATER HEATER DETAIL AND LOCATION | | | | | | 9) MENS AND WOMENS RESTROOMS ARE NOT | | | LARGE ENOUGH. PER TABLE 407, TWO W/C'S | | | AND TWO LAVS ARE REQUIRED FOR 65 PERSONS | | | HANDICAP STALL REQUIRED IN EACH REST- | | | ROOM. A URNAL IN REQUIRED IN MENS' REST- | | | ROOM. | | | | | | 10) IRRIGATION PERMIT REQUIRED. WATER | | | SUPPLY BY PLUMBING CONTRACTOR. | | | | | | 11) PAGE 3.0 PLUMBING NOTES #8, PIPING | | | 2" AND SMALLER TO HAVE 1/4" PER FOOT | | | FALL PER SPC-94 SEC 705.2 | | | | | | 12) PAGE 3.0 PLUMBING NOTES #12, AIR- | | | CHAMBERS TO BE ACCESSABLE AND RECHARGE- | | | ABLE PER SPC-94 607.8.2 & 607.8.3 | | | APPROVED MECHANICAL WATER HAMMER ARREST- | | | ORS TO BE INSTALLED PER MANUFACTURE IN- | | | STRUCTIONS. | | | | | | 13) SEPARATE GAS PERMIT REQUIRED. | | | GAS PERMIT APPLICATION REQUIREMENT SHEET | | | INFORMATION TO BE SUBMITTED. PLEASE ADD- | | | RESS ALL CIRCLED SECTIONS. | | | PLEASE SUBMIT A COPY OF APPROPRIATE GAS | | | SIZING CHART FROM SGC-97 (305.4A). | | | ALSO SUBMIT MANUFACTURE SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA, 54 AND THE STANDARD GAS | | | CODE. 1" PIPE AT 66 TOTAL DEVELOPED | | | LENGTH IS NOT LARGE ENOUGH TO DELIVER | | | 351,000 BTU, 1-1/4" WILL BE REQUIRED. | | | | | | 14) GAS RISER DETAIL PAGE 3.0 SHOWS | | | UNIONS BEFORE SHUT OFF VALVES AT THE | | | EMERGENCY SHUT OFF. THE VALVES SHOULD | | | BE OUTSIDE OF THE UNIONS TO SERVICE | | | THE VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|