Plan Review Details - Permit 01060585
Plan Review Stops For Permit 01060585
Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-07 Cont ID  
Sent By pkrauss Date 2001-12-07 Time 16:11 Rev Time 0.35
Received By pkrauss Date 2001-12-07 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-17 Cont ID  
Sent By pkrauss Date 2001-09-17 Time 11:05 Rev Time 0.30
Received By pkrauss Date 2001-09-17 Time 10:48 Sent To  
Notes
2001-09-17 00:00:00*******************PROVISO**************
  
  
 ATTIC ACCESS SHALL COMPLY WITH 1997 SMC
 304.4.1, ACCESSIBLE BY AN OPENING AND
 PASSAGEWAY AS LARGE AS THE LARGEST
 PIECE OF EQUIPMENT AND IN NO CASE LESS
 THAN 22" X 36" CONTINUOUS FROM THE
 OPENING TO THE EQUIPMENT AND ITS
 CONTROLS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-18 Cont ID  
Sent By pkrauss Date 2001-06-18 Time 09:43 Rev Time 0.35
Received By pkrauss Date 2001-06-18 Time 09:36 Sent To  
Notes
2001-06-18 00:00:00*******************PROVISO**************
  
 ATTIC ACCESS FOR AHU SHALL COMPLY WITH
 1997 SMC 304.4.1, ACCESSIBILITY FOR
 SERVICE & AMENDED 1997 SMC 304.4.2,
 SHALL HAVE AN ACCESSIBLE DISCONNECT
 SWITCH & A 11O-120 VOLT AC GROUNDING
 TYPE CONVIENCE OUTLET AS WELL AS A
 LIGHT ON SERVICE SIDE OF EQUIPMENT
 CONTROLLED BY SWITCH AT THE OPENING OF
 THE ATTIC SPACE.
  
 NOTE:PRIOR TO CONNECTING TO ANY
 EXISTING DUCTWORK, CALL FOR AN
 INSPECTION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.