Plan Review Details - Permit 01060486
Plan Review Stops For Permit 01060486
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2001-06-28 Cont ID  
Sent By mamini Date 2001-06-28 Time 15:50 Rev Time 0.00
Received By mamini Date 2001-06-28 Time 15:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-06-28 Cont ID  
Sent By mamini Date 2001-06-28 Time 15:51 Rev Time 0.00
Received By mamini Date 2001-06-28 Time 15:51 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2002-02-13 Cont ID  
Sent By mamini Date 2002-02-13 Time 09:27 Rev Time 2.00
Received By mamini Date 2002-02-13 Time 09:27 Sent To  
Notes
2002-02-13 00:00:00PASSED:
 1. REVISION FOR PAVING AND DRAINAGE AS
 SUBMITTED APPROVED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-07-17 Cont ID  
Sent By mamini Date 2001-07-17 Time 10:52 Rev Time 5.00
Received By mamini Date 2001-07-17 Time 10:52 Sent To  
Notes
2001-07-17 00:00:00PASSED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 6-14-01 SATISFACTORY.
 PLANS HAVE BEEN REVISED.
 2. ALL REQUESTED ITEMS IS PROVIDED.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8496 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By mamini Date 2001-06-14 Time 11:37 Rev Time 5.00
Received By mamini Date 2001-06-14 Time 11:36 Sent To  
Notes
2001-06-14 00:00:00FAILED:
 1. INSUFFICIENT INFORMATION FOR CIVIL
 ENGINEERING REVIEW, PLEASE RESUBMIT
 WHEN CIVIL PLANS ARE COMPLETELY
 DEVELOPED.
 2. PLEASE SUBMIT SURVEYING PLANS
 3. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN FOR ENTIRE SITE.POLLUTION
 PREVENTION MUST BE INSTALLED IN THE
 FIELD PRIOR TO ANY EARTH WORKS AND IT
 SHOULD INCLUDE PREVENTION OF TRACKING
 CONSTRUCTION DEBRIES AND DUST INTO THE
 PUBLIC R.O.W .THE PLAN SHOULD BE KEPT
 ON THE SITE DURING CONSTRUCTION.
 4. PLEASE PROVIDE THE STATUS OF APPROVAL
 FROM THE SFWMD IN REGARD TO THIS PROJECT
 5. ANY WORK WITHIN CITY PUBLIC R.O.W
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 OFFICE OF CITY ENGINEER.659-8040
 6. ANY WORK WITHIN FDOT R.O.W WILL
 REQUIRE A SEPARATE PERMIT THROUGH FDOT
 DISTRICT OFFICE.
 7. ANY NEW CONNECTION TO CITY SERVICES
 WILL REQUIRE A SEPARATE PERMIT THROUGH
 PUBLIC UTILITIES ENGINEERING SERVICES
 DEPARTMENT. 659-8040
 8. PLEASE PROVIDE STORM WATER
 CALCULATIONS AND DETAILS FOR OUR REVIEW
 IF YOU HAVE NOT SUBMITTED TO JOSE DEL
 RIO, STORM WATER ENGINEER AT 1000 45TH
 STREET WPB, FL 33407.IF ALREADY SUB-
 MITTED, PLEASE PROVIDE THE STATUS OF
 APPROVAL.
 9. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 AREA CALCULATIONS.THE TOTAL AMOUNT
 MUST BE EQUAL TO 100% OF TOTAL SITE AREA
 IN ACRES OR S.F.
 10. PLEASE PROVIDE ADDRESS AND PROPERTY
 CONTROL NUMBER.
 11. PLEASE PROVIDE SIGNING AND MARKING
 FOR ENTIRE SITE.
 12. PLEASE PROVIDE LANDSCAPING PLANS.
 13. DUMPSTER ENCLOSURE MUST BE AT MIN.
 PER CITY STANDARD.SEE PREVIOUS REVIEW
 COMMENTS.
 14. PLEASE PROVIDE ADDITIONAL
 INFORMATION & DETAILS FOR EXISTING LIFT
 STATION.HAS THIS BEEN COORDINATED
 WITH PUBLIC UTILITIES ENGINEERING
 SEVICES DEPARTMENT FOR INSTALLATION,
 CONNECTION AND MAINTENANCE?
 15. NOTE 4 ON SHEET 7 OF 9A REFERS TO
 MANHOLES 20 AND 21
 A. THEY ARE NOT SHOWN ON SANITARY PLANS
 AND PROFILE SHEETS
 B. WHY ONLY THESE TWO WILL HAVE INSIDE &
 OUTSIDE COATINGS.
 16. CITY STANDARD AND DETAILS MAY BE
 OBTAINED FROM PUBLIC UTILITIES ENGINEER-
 ING SERVICES DEPARTMENT. 659-8040
 17. ALL BACKFLOW PREVENTERS SHALL BE
 COMPLETELY HIDDEN FROM VIEW WITH SHRUBS
 AND LANDSCAPING.
 18. SHEET 4 OF 11C IS MISSSING, PLEASE
 INCLUDE WITH RESUB.
 19. PLEASE REFER TO SHEET 3 & 5 OF 11C
 NOTES NO. 1, 11 AND VERIFY.
 20. PROVIDE TYP. SECTION FOR PERIMETER
 BERM AND FOR WATER MANAGEMENT TRACTS,
 SHOW SLOPE BOTTEM ELEVATIONS, ETC..
 21. PROVIDE DETAILS FOR PARKING STALLS
 H.C AND NONE-H.C
 22. PROVIDE DETAILS FOR PAVEMENTS,BASE
 AND SUB-BASE
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-02-14 Cont ID  
Sent By mcarsill Date 2002-02-14 Time 10:00 Rev Time 0.00
Received By mcarsill Date 2002-02-14 Time 10:00 Sent To  
Notes
2002-02-14 00:00:001) ALL ACESS ROADS SHALL BE A MINIMUM
 OF TWENTY FEET IN CLEAR WIDTH. ON
 2.14.02 WRITER SPOKE TO MARTHA CARTER
 OF MICHAEL B. SCHORAH AND ASSOCIATES,
 INC., REGARDING THIS ISSUE. MS. CARTER
 WAS ALSO ADVISED THAT FIRE HYDRANTS
 SHOULD BE PROVIDED ON WINDSOR WAY.
 THIS WRITER SPOKE TO MS CARTER ABOUT
 THE AREA WHEN LEAVING THE CIRCLE WHERE
 THE PARKING STALL STARTS. ACCORDING TO
 MS. CARTER THIS AREA PROVIDES FOR
 TWENTY FEET IN CLEAR WIDTH. SHE ALSO
 STATED THAT WHERE THE 18'- 5" OCCURS,
 20 FEET IN CLEAR WIDTH IS PRESENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-06-13 Cont ID  
Sent By mcarsill Date 2001-06-13 Time 13:04 Rev Time 0.00
Received By mcarsill Date 2001-06-13 Time 13:01 Sent To  
Notes
2001-06-13 00:00:001) FIRE HYDRANTS ARE TO BE SPACED
 BETWEEN 300-500 FEET APART.
 2) ALL UNDERGROUND FIRE LINES ARE TO
 BE LISTED FOR FIRE PROTECTION SERVICE.
 3) ALL UNDERGOUND FIRE LINES AND THEIR
 APPURTENANCES ARE TO MEET THE
 REQUIREMENTS OF NFPA 24.
 4) ALL UNDERGROUND FIRE LINES ARE TO
 BE PRESSURE TESTED AND INSPECTED BY
 CITY OF WEST PALM BEACH OFFICIALS.
 5) PER CITY CODE SECTION 11-4 NO OBJECTS
 ARE TO BE PLACED WITHIN 18 FEET OF ANY
 FIRE HYDRANT.
 6) WET FIRE HYDRANTS ARE TO BE PROVIDED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
 7) TAMPER SWITCHES, CHAINS AND LOCKS ARE
 TO BE PROVIDED FOR BACKFLOW DEVICE.
 8) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL ACCESS.
 9) FIRE DEPARTMENT CONNECTIONS FOR THE
 APARTMENT BUILDINGS ARE TO BE NO MORE
 THAN 150 FEET FROM NEARBY FIRE HYDRANTS.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-06-27 Cont ID  
Sent By pkrauss Date 2001-06-27 Time 15:37 Rev Time 0.30
Received By pkrauss Date 2001-06-27 Time 15:37 Sent To  
Notes
2001-06-27 00:00:00NO MECHANICAL PLANS WITH THIS PERMIT APP
 LICATION...STRICTLY CIVIL PLANS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-25 Cont ID  
Sent By kstevens Date 2001-06-25 Time 14:38 Rev Time 0.75
Received By kstevens Date 2001-06-25 Time 14:37 Sent To  
Notes
2001-06-25 00:00:00PROVISO...
  
 THIS PLAN HAS BEEN REVIEW FOR COMPLIENCE
 WITH THE CITY OF WEST PALM BEACH UTILITY
 STANDARDS.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-06-28 Cont ID  
Sent By mamini Date 2001-06-28 Time 15:50 Rev Time 0.00
Received By mamini Date 2001-06-28 Time 15:50 Sent To  
Notes
***NONE***