| Plan Review Stops For Permit 01060471 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-07 |
Time |
16:38 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-08-07 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | AS BUILT DRAWINGS SUBMITTED BY | | | CATALFUMO. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-06-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-26 |
Time |
14:38 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-06-26 |
Time |
14:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-06-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-14 |
Time |
15:12 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-06-14 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-06-14 00:00:00 | ******************PROVISO*************** | | | | | | | | | OVERFLOW PROTECTION SHALL COMPLY WITH | | | 1997 SMC 304.8.6.A SEPARATE DRAIN | | | LINEOF NOT LESS THAN 3/4" PIPE SIZE | | | SHALL EXTEND FORM THE PAN TERMINATING | | | AT A COMSPICUOUS POINT TO SERVE AS AN | | | ALARM THAT THE REGULAR DRAIN IS | | | RESTRICTED.A WATER LEVEL DETECTOR OR | | | FLOAT SWITCH MAY BE USED IN LIEU OF | | | DRAIN LINE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
|