Plan Review Details - Permit 01060467
Plan Review Stops For Permit 01060467
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-24 Cont ID  
Sent By dpalmer Date 2001-06-24 Time 12:08 Rev Time 0.00
Received By dpalmer Date 2001-06-24 Time 12:08 Sent To  
Notes
2001-06-24 00:00:00*******************UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE CLARIFY GROUNDING
 ELECTR0DE SYSTEM AT MAIN HOUSE SERVICE
 LOCATIONPLEASE NOTE THAT ZONING WILL
 HAVE TO OK TWO METERS.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3)NOTE: PLEASE NOTE THAT NO PANEL
 SCHEDULES OR LOAD CALCULATIONS WERE
 SUBMITTED.PER 215-5.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE NOTE CLEARENCES PER
 110-26 FOR CLOSET SHOWING PANEL, A/C,
 WATER HEATER ETC ETC.
  
 6)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER IS SHOWN AS EXISTING UNDER PERMIT
 # 01021004. HOW IS THIS POSSIBLE WHEN TH
 AT PERMIT WAS FOR ANOTHER ADDRESS??
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-07-10 Cont ID  
Sent By pkrauss Date 2001-07-10 Time 14:55 Rev Time 0.25
Received By pkrauss Date 2001-07-10 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-20 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 14:00 Rev Time 0.33
Received By kstevens Date 2001-06-20 Time 12:32 Sent To  
Notes
2001-06-20 00:00:00REVIEW NOTES:DENIED
  
 MORE INFORMATION REQUIRED. PLEASE SUBMIT
 A SANITARY AND A WATER RISER DIAGRAM PER
 SPC-94SEC 104.2.1 AND 104.3.1
  
 REVIEW KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-07-10 Cont ID  
Sent By rmcdouga Date 2001-07-10 Time 11:39 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-10 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 4) ALL INFORMATION,DRAWINGS,SPECS.,AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. 104.2.1 CITY AMENDMENTS
 TO THE 97 SBC.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOORS
 - EXTERIOR WINDOWS
 - STORM PANELS
 ROOFING UNDER A SEPERATE PERMIT.
  
 6) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 7) UNLESS DESIGNED BY AN ARCHITECT OR AN
 ENGINEER THE STRUCTURE MUST COMPLY WITH
 SSTD 10-97 THE SBCCI STANDARD FOR
 HURRICANE RESISTANT RESIDENTIAL
 CONSTRUCTION.
  
 8) GIVE SPECIFIC INFORMATION (TYPE AND
 LOADS RESISTED) FOR ALL CONNECTORS USED
 TO ACHIEVE A CONTINOUS LOAD PATH FROM
 THE FOUNDATION TO THE ROOF.
 INDICATE SPECIFIC CONNECTORS AND THEIR
 UPLIFT CAPABILITIES BEING USED TO ANCHOR
 BEAMS TO BLOCK COLUMNS,RAFTERS TO BEAMS,
 RAFTERS TO LEDGERS, POSTS TO SLAB, POSTS
 TO BEAMS, BEAMS TO EXISTING STRUCTURE,
 ETC.
  
 9) CLARIFY TYPE OF FOOTING AT ENCLOSED
 PART OF ENTRY (MONOLITHIC OR STEMWALL).
  
 10) PROVIDE VERTICLE REINFORCEMENT IN
 EACH CORNER AND AT EACH SIDE OF OPENINGS
 AT THE ENCLOSED ENTRY.
  
 11) MONOLITHIC SLAB-ON-GRADE EXTERIOR
 FOOTINGS ARE REQUIRED TO BE 16 INCHES IN
 HEIGHT AND HAVE A 12 INCH BOTTOM WIDTH.
 STEM WALL FOOTINGS MUST BE 8 INCHES IN
 HEIGHT AND HAVE A 16 INCH BOTTOM WIDTH.
  
 12) THE BOTTOM OF FOUNDATIONS SHALL BE A
 MINIMUM OF 12 INCHES BELOW FINISH GRADE.
 97 SBC 1804.1.3
  
 13) PROVIDE A DETAIL OF THE NEW GUARD-
 RAIL AT THE TOP OF THE STAIRS INDICATING
 MATERIALS,STRUCTURAL ATTACHMENTS,SPACING
 BETWEEN INTERMEDIATE RAILS,ETC.
  
 14) INDICATE THE SPECIFIC JOIST HANGERS
 FOR 2X10 FLOOR JOISTS TO LVL ATTACHMENT.
  
 15) SPECIFY ATTACHMENTS OF LAM BEAMS
 USED TO REPLACE BEARING WALLS AT STAIRS.
  
 16) PROVIDE INFORMATION ON LINTELS FOR
 WINDOW AND DOOR OPENINGS IN BLOCK WALLS
 AT ENCLOSED ENTRY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-14 Cont ID  
Sent By sgraham Date 2001-06-14 Time 13:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***