Plan Review Details - Permit 01060407
Plan Review Stops For Permit 01060407
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-07 Cont ID  
Sent By rmcdouga Date 2001-07-07 Time 08:52 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-07-07 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS, PRIOR TO
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-25 Cont ID  
Sent By rmcdouga Date 2001-06-25 Time 11:39 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-25 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE ATTIC VENTILATION AND ATTIC
 ACCESS. 97 SBC 2309.7 AND 2309.6
  
 3) PROVIDE CRAWL SPACE ACCESS AND
 VENTILATION. 97 SBC 1804.6.2.1 AND
 1804.6.2.2
  
 4) PROVIDE NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR DESIGN ON EACH SHEET OF
 PLANS. 97SBC 104.2.1
  
 5) PROVIDE DIMENSIONS ON PLANS FOR
 KITCHEN ADDITION AND LOGGIA.
  
 6) PLANS INDICATE KITCHEN ADDITION AND
 NEW LOGGIA, HOWEVER ONLY ADDITION TO
 KITCHEN IS INDICATED ON APPLICATION.
 PLEASE CLARIFY.
  
 7) THE PERMIT APPLICATION INDICATES A 90
 SQFT KITCHEN ADDITION, HOWEVER THE
 FLORIDA ENERGY EFFICIENCY CODE FORM
 LISTS 80 SQFT OF CONDITIONED FLOOR AREA.
 PLEASE CLARIFY.
  
 8) PROVIDE DETAIL OF THE ROOF AND
 FLOOR STRUCTURAL ATTACHMENTS AT THE
 LOGGIA AND KITCHEN ADDITION.
  
 9) INDICATE INTERIOR WALL, CEILING AND
 FLOOR MATERIAL FOR KITCHEN AND CEILING
 MATERIAL AT LOGGIA. INDICATE ROOF
 SHEATHING FOR KITCHEN ADDITION.
  
 10) INDICATE SIZE AND SPACING OF RAFTERS
 AT LOGGIA.
  
 11) INDICATE POST TO HEADER CONNECTION
 AND CLARIFY POST TO SLAB CONNECTOR AT
 LOGGIA.
  
 12) INDICATE STUD TO TOP AND BOTTOM
 PLATES CONNECTORS AT KITCHEN ADDITION.
  
 13) PROVIDE INSTALLATION SCHEDULE AND
 KEY PLAN FOR STORM PANELS AND INDICATE
 THE SPECIFIC ANCHORS TO BE USED.
  
 14) PROVIDE ADEQUATE BLOCKING AT ALL
 EXTERIOR GLAZED OPENINGS FOR ATTACHMENT
 OF STORM PANELS.
  
 15) PROVIDE DIMENSIONS OF STEM WALL AND
 INDICATE SIZE AND SPACING OF VERTICLE
 REINFORCEMENT.
  
 16) INDICATE SPACING OF WOOD POSTS AT
 LOGGIA.
  
 17) INDICATE ROOF PITCH AT LOGGIA AND
 KITCHEN ADDITION.
  
 18) PROVIDE ELEVATIONS FROM FINISH GRADE
 OF FLOORS AND CEILINGS AT LOGGIA AND
 KITCHEN ADDITION.
  
 19) PROVIDE ADDITIONAL COPY OF PRODUCT
 APPROVAL FOR WINDOWS. (2) COPIES ARE
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2001-06-25 Cont ID  
Sent By rmcdouga Date 2001-06-25 Time 15:25 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-06-25 00:00:00NO ELECTRICAL PLANS SUBMITTED. OWNER TO
 HIRE AN ELECTRICAL CONTRACTOR TO PULL A
 SEPARATE PERMIT. 6-25-01 RM

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-20 Cont ID  
Sent By sgraham Date 2001-06-20 Time 14:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***