| Plan Review Stops For Permit 01060376 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-04 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-04 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-07-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-07-04 |
Time |
10:45 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-07-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01060376 | | | 1572 PALM BEACH LAKES A 5-7 | | | CONTACT RICHARD WENSING ARCH | | | 684- 1988 | | | | | | PLAN REVIEW: TENANT BUILD OUT | | | | | | 1)- FLORIDA ACC.CODE 4.5 GROUND FLOORS | | | 4.5.3 CARPET & TILE ARE TO HAVE A STATIC | | | COEFFICIENT OF FRICTION OF 0.6 IS RECOM- | | | MENDED FOR ACCESSIBLE ROUTES AND 0.8 FOR | | | RAMPS. ( ADDAAG A-5) | | | | | | 2)- SBC 1204.2 THE WALLSAND FLOORS OF | | | ALL PUBLIC RESTROOMS SHALL BE LINED WITH | | | NONABSORBANT MATERIALS TO A HEIGTH OF | | | 4 FOOT ABOVE THE FLOOR. | | | | | | 3)- SBC 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED: PLEASE INDICATE WHAT RAATING T | | | HE TENANT SEPERATION WALL HAS THAT SEPER | | | ATES THE ELECTRICAL ROOM & LOUNGE. | | | | | | 4)- MISSING IS THE MINIMUM INTERIOR FIN- | | | ISH CLASSIFICATION SCHEDULE TABLE 803.3. | | | GIVING THE FLAMESPREAAD & SMOKE DEVELOP- | | | MENT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-10-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-23 |
Time |
18:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-23 |
Time |
18:47 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-17 |
Time |
21:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-17 |
Time |
21:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-09-17 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | TRANSFERED NOTES FROM #01080151 | | | | | | *************UNSAT****************** | | | | | | 1]NOTE: PLEASE NOTE SERVICE IS SHOWING | | | TAPPED CONDUCTORS FROM METERCAN INTO | | | GUTTER AND THEN TAPPING THE TAP??? | | | PLEASE NOTE THAT INDIVIDUAL RUNS FROM | | | METERCAN TO EACH DISCONNECT IS | | | PERMITTED. PLEASE SUBMIT. | | | | | | 2]NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS WERE | | | SUBMITTED FOR PANELS BUT NOT FOR MAIN | | | DISCONNECTS. PLEASE SUBMIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY | | | QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT. 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-06-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-06-14 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-06-14 |
Time |
21:51 |
Sent To |
|
|
| Notes |
| 2001-06-14 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE CLARIFY PANELS HAVING | | | BOTH BOXES MARKED FOR "MLO" AND "MCB" | | | ?? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS ARE SHOWN | | | FOR PANEL BUT NOT RATINGS FOR MAINS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-06-13 |
Time |
11:40 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-06-13 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | PASSED WITH PROVISOS: | | | 1. PLEASE SUBMIT CIVIL PLANS FOR | | | ENGINEERING REVIEW AS SOON AS THEY ARE | | | DEVELOPED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-10-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-24 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-24 |
Time |
14:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-23 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-18 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-06-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-06-13 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-06-13 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2001-06-13 00:00:00 | 1) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION FOR WALLS AND CEILINGS. | | | INTERIOR FINISH IN EXITS SHALL BE CLASS | | | A OR B. IN OTHER AREAS A,B,OR C | | | PERMITTED. | | | 2) PLEASE INDICATE IF ANY FIRE RATING | | | IS PRESENT BETWEEN LOUNGE AND 106 AND | | | ELECTRICAL ROOM. | | | 3) SIGNS ARE REQUIRED AT EXIT DOORS | | | " THESE DOORS TO REMAIN UNLOCKED | | | DURING BUSINESS HOURS". | | | 4) PLEASE PROVIDE A FURNITURE PLAN AND | | | CLEARLY INDICATE 44" AISLE FOR ANY | | | CORRIDOR AND PASSAGEWAY. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-24 |
Time |
09:51 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-09-24 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2001-09-24 00:00:00 | *****************PROVISO**************** | | | | | | | | | COMMENTS FROM 8-21-01 | | | | | | ALL RTU'S SHALL HAVE DUCT SMOKE | | | DETECTORS AS THE COMBINED AIR EXCEEDS | | | 2,000 CFM. | | | | | | | | | CONDENSATE SHALL TERMINATE TO STORM | | | DRAIN OR APPROVED DRYWELL.IT SHALL | | | NOT TERMINATE ON ROOF OR TO ANY AREA | | | WHERE IT COULD BE A NUISANCE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
C |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-08-21 |
Time |
13:49 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-08-21 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | PROVISO: | | | ALL RTUS SHALL HAVE DUCT SMOKE | | | DETECTORSAS THE COMBINED AIR EXCEEDS | | | 200 CFM | | | CONDENSATE SHALL TERMINATE TO STORM | | | SEWER OR TO APPROVED DRYWELL. IT SHALL | | | NOT TERMINATE ON ROOF OR TO ANY AREA | | | WHERE IT COULD CREATE A NUISANCE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-06-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-26 |
Time |
10:51 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-06-26 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2001-06-26 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.AIR BALANCE SCHEDULE FOR COMPLIANCE | | | WITH 1997 SMC 501.2. | | | | | | 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR UNIT 5 TON AND LARGER | | | OR FOR UNITS SERVING AN AREA USED | | | FOR EGRESS. | | | | | | 4.FAN SHUT DOWN WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS AS PER NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-09-22 |
Time |
09:15 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-09-22 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | PROVISO; | | | 1.REVISED SANITARY RISER DIAGRAM | | | REQUIRED BEFORE FINAL PLUMBING | | | INSPECTION. | | | 2.WATER HAMMER ARRESTORS TO BE INSTALLED | | | PER MANUFACTORS INSTALLATION | | | INSTRUCTIONS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-17 |
Time |
10:13 |
Rev Time |
0.50 |
| Received By |
pschmitz |
Date |
2001-09-17 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | DENIED | | | REFERENCE SPC-94 - FACBC-97 | | | | | | 1) PAGE A-6 WOMENS RESTROOM. FLOOR DRAIN | | | NOT VENTED PROPERLY. | | | | | | 2) PAGE A-7 WATER RISER DIAGRAM. WATER | | | HAMMER ARRESTORS NOT LOCATED PROPERLY. | | | PLEASE LOCATE HAMMER ARRESTORS PER MAN- | | | UFACTURE INSTALLATION INSTRUCTIONS AND | | | WH-PDI 201. SEE ATTACHED SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-08-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-22 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-21 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2001-08-22 00:00:00 | DENIED | | | | | | 1) PAGE A-6, VENT NOT ALLOWED. NO DRY | | | HORIZONTAL VENTS PER SPC-94 906.2.1 | | | | | | 2) WATER HEATER TO BE READILY ACCESSABLE | | | PLEASE SHOW DETAILS. | | | | | | 3) PAGE A-7, P&T RELIEF VALVE SHALL NOT | | | BE TRAPPED PER SPC-94 507.8.4. THIS WAS | | | NOT ADDRESSED FROM FIRST REVIEW. | | | | | | 4) WATER HAMMER ARRESTORS TO BE INSTALL- | | | ED PER MANUFACTURE'S INSTALLATION IN- | | | STRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-06-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-06-23 |
Time |
10:44 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2001-06-23 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2001-06-23 00:00:00 | DENIED; | | | | | | 1.PAGE A-6, VENT FOR LAV 2, MEN'S ROOM, | | | IS REQUIRED TO BE CLOSER TO W/C 2 TO | | | BE VENTED PROPERLY. | | | | | | 2.WATER HEATER TO BE READLY ACCESIBLE. | | | PROVISIONS TO BE MADE SO NO TOOLS | | | ARE REQUIRED TO GET TO HEATER AND IT | | | CAN CHANGED . | | | | | | 3.BREAK SINK TO COMPLY WITH 97 SACBC SEC | | | 4.24.1 THRU 4.24.7. | | | | | | 4.DRINKING FOUNTAIN TO COMPLY WITH SACBC | | | 4.1.3(10) AND 4.15. PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 5.PAGE A-7 P.& T. RELIEF VALVE SHALL NOT | | | BE TRAPPED 94 SPC 507.8.4. | | | | | | 6.ENGINEERED WATER HAMMER ARRESTERS | | | SHALL BE INSTALLED PER SEC. 607.8.2 | | | AND 607.8.3. | | | | | | 7.PAGE A-8 PLUMBING NOTES (NOTE 20). | | | WATER DIAGRAM DOESNOT SHOW HOT WATER | | | TO THE LAV'S. DELETE NOTE 20 OR REVISE | | | WATER RISER DIAGRAM PG. A-7 AND WATER | | | DISTRIBUTION PLAN PG. A-6. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-09-07 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-07 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|