Plan Review Details - Permit 01060376
Plan Review Stops For Permit 01060376
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-04 Cont ID  
Sent By hpiskura Date 2001-09-04 Time 14:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-07-04 Cont ID  
Sent By jwitmer Date 2001-07-04 Time 10:45 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-07-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060376
 1572 PALM BEACH LAKES A 5-7
 CONTACT RICHARD WENSING ARCH
 684- 1988
  
 PLAN REVIEW: TENANT BUILD OUT
  
 1)- FLORIDA ACC.CODE 4.5 GROUND FLOORS
 4.5.3 CARPET & TILE ARE TO HAVE A STATIC
 COEFFICIENT OF FRICTION OF 0.6 IS RECOM-
 MENDED FOR ACCESSIBLE ROUTES AND 0.8 FOR
 RAMPS. ( ADDAAG A-5)
  
 2)- SBC 1204.2 THE WALLSAND FLOORS OF
 ALL PUBLIC RESTROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIALS TO A HEIGTH OF
 4 FOOT ABOVE THE FLOOR.
  
 3)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED: PLEASE INDICATE WHAT RAATING T
 HE TENANT SEPERATION WALL HAS THAT SEPER
 ATES THE ELECTRICAL ROOM & LOUNGE.
  
 4)- MISSING IS THE MINIMUM INTERIOR FIN-
 ISH CLASSIFICATION SCHEDULE TABLE 803.3.
 GIVING THE FLAMESPREAAD & SMOKE DEVELOP-
 MENT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-10-23 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 18:47 Rev Time 0.00
Received By dpalmer Date 2001-10-23 Time 18:47 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 21:47 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 21:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-17 Cont ID  
Sent By lmartine Date 2001-09-17 Time 08:42 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-17 00:00:00TRANSFERED NOTES FROM #01080151
  
 *************UNSAT******************
  
 1]NOTE: PLEASE NOTE SERVICE IS SHOWING
 TAPPED CONDUCTORS FROM METERCAN INTO
 GUTTER AND THEN TAPPING THE TAP???
 PLEASE NOTE THAT INDIVIDUAL RUNS FROM
 METERCAN TO EACH DISCONNECT IS
 PERMITTED. PLEASE SUBMIT.
  
 2]NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE
 SUBMITTED FOR PANELS BUT NOT FOR MAIN
 DISCONNECTS. PLEASE SUBMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT. 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By dpalmer Date 2001-06-14 Time 06:35 Rev Time 0.00
Received By dpalmer Date 2001-06-14 Time 21:51 Sent To  
Notes
2001-06-14 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY PANELS HAVING
 BOTH BOXES MARKED FOR "MLO" AND "MCB"
 ??
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS ARE SHOWN
 FOR PANEL BUT NOT RATINGS FOR MAINS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-06-13 Cont ID  
Sent By mamini Date 2001-06-13 Time 11:40 Rev Time 1.00
Received By mamini Date 2001-06-13 Time 11:29 Sent To  
Notes
2001-06-13 00:00:00PASSED WITH PROVISOS:
 1. PLEASE SUBMIT CIVIL PLANS FOR
 ENGINEERING REVIEW AS SOON AS THEY ARE
 DEVELOPED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-24 Cont ID  
Sent By mcarsill Date 2001-10-24 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2001-10-24 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 18:48 Rev Time 0.00
Received By mcarsill Date 2001-09-18 Time 08:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-06-13 Cont ID  
Sent By mcarsill Date 2001-06-13 Time 10:40 Rev Time 0.00
Received By mcarsill Date 2001-06-13 Time 10:40 Sent To  
Notes
2001-06-13 00:00:001) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS.
 INTERIOR FINISH IN EXITS SHALL BE CLASS
 A OR B. IN OTHER AREAS A,B,OR C
 PERMITTED.
 2) PLEASE INDICATE IF ANY FIRE RATING
 IS PRESENT BETWEEN LOUNGE AND 106 AND
 ELECTRICAL ROOM.
 3) SIGNS ARE REQUIRED AT EXIT DOORS
 " THESE DOORS TO REMAIN UNLOCKED
 DURING BUSINESS HOURS".
 4) PLEASE PROVIDE A FURNITURE PLAN AND
 CLEARLY INDICATE 44" AISLE FOR ANY
 CORRIDOR AND PASSAGEWAY.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-24 Cont ID  
Sent By pkrauss Date 2001-09-24 Time 09:51 Rev Time 0.35
Received By pkrauss Date 2001-09-24 Time 09:51 Sent To  
Notes
2001-09-24 00:00:00*****************PROVISO****************
  
  
 COMMENTS FROM 8-21-01
  
 ALL RTU'S SHALL HAVE DUCT SMOKE
 DETECTORS AS THE COMBINED AIR EXCEEDS
 2,000 CFM.
  
  
 CONDENSATE SHALL TERMINATE TO STORM
 DRAIN OR APPROVED DRYWELL.IT SHALL
 NOT TERMINATE ON ROOF OR TO ANY AREA
 WHERE IT COULD BE A NUISANCE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status C Date 2001-08-21 Cont ID  
Sent By ndenmark Date 2001-08-21 Time 13:49 Rev Time 0.33
Received By ndenmark Date 2001-08-21 Time 13:49 Sent To  
Notes
2001-08-21 00:00:00PROVISO:
 ALL RTUS SHALL HAVE DUCT SMOKE
 DETECTORSAS THE COMBINED AIR EXCEEDS
 200 CFM
 CONDENSATE SHALL TERMINATE TO STORM
 SEWER OR TO APPROVED DRYWELL. IT SHALL
 NOT TERMINATE ON ROOF OR TO ANY AREA
 WHERE IT COULD CREATE A NUISANCE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-26 Cont ID  
Sent By pkrauss Date 2001-06-26 Time 10:51 Rev Time 0.45
Received By pkrauss Date 2001-06-26 Time 10:51 Sent To  
Notes
2001-06-26 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE FOR COMPLIANCE
 WITH 1997 SMC 501.2.
  
 3.FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR UNIT 5 TON AND LARGER
 OR FOR UNITS SERVING AN AREA USED
 FOR EGRESS.
  
 4.FAN SHUT DOWN WITH NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS AS PER NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-09-22 Cont ID  
Sent By jleech Date 2001-09-22 Time 09:15 Rev Time 1.00
Received By jleech Date 2001-09-22 Time 09:15 Sent To  
Notes
2001-09-22 00:00:00PROVISO;
 1.REVISED SANITARY RISER DIAGRAM
 REQUIRED BEFORE FINAL PLUMBING
 INSPECTION.
 2.WATER HAMMER ARRESTORS TO BE INSTALLED
 PER MANUFACTORS INSTALLATION
 INSTRUCTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-17 Cont ID  
Sent By kstevens Date 2001-09-17 Time 10:13 Rev Time 0.50
Received By pschmitz Date 2001-09-17 Time 10:13 Sent To  
Notes
2001-09-17 00:00:00DENIED
 REFERENCE SPC-94 - FACBC-97
  
 1) PAGE A-6 WOMENS RESTROOM. FLOOR DRAIN
 NOT VENTED PROPERLY.
  
 2) PAGE A-7 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS NOT LOCATED PROPERLY.
 PLEASE LOCATE HAMMER ARRESTORS PER MAN-
 UFACTURE INSTALLATION INSTRUCTIONS AND
 WH-PDI 201. SEE ATTACHED SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-08-22 Cont ID  
Sent By kstevens Date 2001-08-22 Time 08:49 Rev Time 0.00
Received By kstevens Date 2001-08-21 Time 15:24 Sent To  
Notes
2001-08-22 00:00:00DENIED
  
 1) PAGE A-6, VENT NOT ALLOWED. NO DRY
 HORIZONTAL VENTS PER SPC-94 906.2.1
  
 2) WATER HEATER TO BE READILY ACCESSABLE
 PLEASE SHOW DETAILS.
  
 3) PAGE A-7, P&T RELIEF VALVE SHALL NOT
 BE TRAPPED PER SPC-94 507.8.4. THIS WAS
 NOT ADDRESSED FROM FIRST REVIEW.
  
 4) WATER HAMMER ARRESTORS TO BE INSTALL-
 ED PER MANUFACTURE'S INSTALLATION IN-
 STRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-06-23 Cont ID  
Sent By jleech Date 2001-06-23 Time 10:44 Rev Time 1.50
Received By jleech Date 2001-06-23 Time 10:44 Sent To  
Notes
2001-06-23 00:00:00DENIED;
  
 1.PAGE A-6, VENT FOR LAV 2, MEN'S ROOM,
 IS REQUIRED TO BE CLOSER TO W/C 2 TO
 BE VENTED PROPERLY.
  
 2.WATER HEATER TO BE READLY ACCESIBLE.
 PROVISIONS TO BE MADE SO NO TOOLS
 ARE REQUIRED TO GET TO HEATER AND IT
 CAN CHANGED .
  
 3.BREAK SINK TO COMPLY WITH 97 SACBC SEC
 4.24.1 THRU 4.24.7.
  
 4.DRINKING FOUNTAIN TO COMPLY WITH SACBC
 4.1.3(10) AND 4.15. PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 5.PAGE A-7 P.& T. RELIEF VALVE SHALL NOT
 BE TRAPPED 94 SPC 507.8.4.
  
 6.ENGINEERED WATER HAMMER ARRESTERS
 SHALL BE INSTALLED PER SEC. 607.8.2
 AND 607.8.3.
  
 7.PAGE A-8 PLUMBING NOTES (NOTE 20).
 WATER DIAGRAM DOESNOT SHOW HOT WATER
 TO THE LAV'S. DELETE NOTE 20 OR REVISE
 WATER RISER DIAGRAM PG. A-7 AND WATER
 DISTRIBUTION PLAN PG. A-6.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 12:58 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***