| Plan Review Stops For Permit 01060373 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-06-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-06-08 |
Time |
12:24 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-06-08 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2001-06-08 00:00:00 | *****************PROVISO**************** | | | | | | ATTIC INSTALLATION OF AHU SHALL COMPLY | | | WITH 1997 SMC 304.4.1, ACCESSIBLE BY AN | | | OPENING & PASSAGEWAY LARGE AS THE | | | LARGEST PIECE OF EQUIPMENT & IN NO CASE | | | LESS THAN 22" X 36". | | | | | | AMMENDED 1997 SMC 304.4.2, SHALL HAVE AN | | | ACCESSIBLE DISCONNECT SWITCH AND A | | | 110-20 VOLT A/C GROUNDING TYPE | | | CONVENIENCE OUTLET & A LIGHT LOCATED ON | | | SERVICE SIDE OF TH EQUIPMENT WITH A | | | SWITCH LOCATED AT REQUIRED OPENING. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|
|
|