Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-06-07 Cont ID  
Sent By mcarsill Date 2001-06-07 Time 12:04 Rev Time 0.00
Received By mcarsill Date 2001-06-07 Time 11:59 Sent To  
Notes
2001-06-07 00:00:001) NO REVIEW WAS PERFORMED ON THE
 BURGLAR ALARM EQUIPMENT SHOWN ON THESE
 DRAWINGS. THE REVIEW FOCUSED ON SECURITY
 EQUIPMENT PLANNED FOR THE EXIT DOORS.
 ON JUNE 7, 2001 WRITER CALLED MARK
 SACHAROW OF ADVANCED ALARM. HE ADVISED
 THAT ALL DEVICES PLACED ON EXIT DOORS
 WILL BE FAIL SAFE AND NOT FAIL SECURE.
 HE EXPLAINED THAT IN A NORMAL CONDITION
 EXITING IS FAIL SAFE. IN AN EMERGENCY
 CONDITION THEY ARE ALSO FAIL SAFE. THE
 LOCKING DEVICES PLANNED FOR THE
 SPACE ARE TO MEET THE REQUIREMENTS FOR
 "SPECIAL LOCKING ARRANGEMENTS" PER THE
 LIFE SAFETY CODE, 1985 EDITION. WHEN
 INSTALLED, THE SECURITY DEVICES ON THE
 EXIT DOORS ARE TO BE INSPECTED WITH
 FIRE RESCUE PERSONNEL TO ENSURE
 COMPLIANCE WITH NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION, SECTION
 5-2.1.6
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910