Plan Review Details - Permit 01060282
Plan Review Stops For Permit 01060282
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-06-28 Cont ID  
Sent By dpalmer Date 2001-06-28 Time 07:59 Rev Time 0.00
Received By dpalmer Date 2001-06-28 Time 07:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-14 Cont ID  
Sent By dpalmer Date 2001-06-14 Time 07:17 Rev Time 0.00
Received By dpalmer Date 2001-06-13 Time 23:33 Sent To  
Notes
2001-06-14 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NO SIZE OF
 MAINDISCONNECT IS SHOWN. PLEASE SHOW
  
 2) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 3)NOTE: PLEASE SHOW OTHER OUTLETS AS
 GFI/GFI PROTECTED PER 210-8.
 BATH/GARAGE.
  
 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS MAIN DISCONNECT AND PLANS ONLY
 SHOW METER ON GARAGE .
  
 5)NOTE: PLEASE NOTE THAT DISCONNECTS
 SHOWN FOR A/C COND UNIT DO NOT MEET
 110-26.
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 7)NOTE: MISSING OUTLET FOR HALLWAY PER
 210-52H
  
 8)NOTE: PLEASE NOTE MISSING OUTLET PER
 KITCHEN COUNTERTOP SPACING PER
 210-52-C-1.
  
 9)PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL(S). EQUIPMENT
 GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 11)NOTE: PLEASE NOTE THAT THREE AIR
 HANDER UNITS ARE SHOWN WITH A LOAD OF
 30KW
 AND ON LOAD CALCULATIONS, LOAD IS SHOWN
 AT 20KW? PLEASE CLARIFY. THIS IS FOR
 PANEL "B".
  
 12)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 DRYER AT 8KW, 2P 50A AND #8. THIS DOES
 NOT SEEM TO BE COMMON SIZE.
 PLEASECLARIFY.
  
 13)NOTE: PLEASE CLARIFY LOAD,OCP AND
 WIRE SIZE SHOW FOR OVEN? 20A,#12AWG AND
 1.5KW.?IF THISIS A GAS OVEN PLEASE
 INDICATE ON PANEL SCHEDULE.
  
 14)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE MISSING SD`S IN A COUPLE OF
 AREAS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-06-13 Cont ID  
Sent By hmoser Date 2001-06-13 Time 19:47 Rev Time 0.33
Received By hmoser Date 2001-06-13 Time 19:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-08-16 Cont ID  
Sent By jleech Date 2001-08-16 Time 19:40 Rev Time 0.33
Received By jleech Date 2001-08-16 Time 19:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-06-27 Cont ID  
Sent By kstevens Date 2001-06-27 Time 17:33 Rev Time 0.33
Received By kstevens Date 2001-06-27 Time 17:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-06-13 Cont ID  
Sent By kstevens Date 2001-06-13 Time 12:41 Rev Time 0.33
Received By kstevens Date 2001-06-13 Time 12:41 Sent To  
Notes
2001-06-13 00:00:00REVIEW NOTES:PASSED
  
 PROVISO:
  
 PLEASE SUBMIT A SANITARY RISER DIAGRAM
 THAT REFLECTS THE FLOOR PLAN BEFORE
 INSPECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2001-06-28 Cont ID  
Sent By lhatten Date 2001-06-28 Time 18:58 Rev Time 4.00
Received By lhatten Date 2001-06-19 Time 18:58 Sent To  
Notes
2001-06-28 00:00:00REVIEW & STAMPED PLANS 06/19/2001
 CALC. FEES & PRINT CARDS 06/28/2001

Review Stop Z ZONING
Rev No 1 Status P Date 2001-06-11 Cont ID  
Sent By sgraham Date 2001-06-11 Time 10:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***