Plan Review Details - Permit 01060172
Plan Review Stops For Permit 01060172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By jwitmer Date 2001-07-05 Time 07:40 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-06-08 Cont ID  
Sent By jwitmer Date 2001-06-08 Time 07:31 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-06-08 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060172
 1214 ROEBUCK CT.
 BAYS 5 & 6
 ABE SCHWARTZ A/C UNLIMITED
 (561) 758-5593
  
 1)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, SUBMIT THE PRE-ENGINEERED
 SHOP DRAWINGS.
  
 2)- SBC407.1.3.5. SPRAY BOOTHS WHERE
 FLAMMABLES ARE USED SHALL BE PROTECTED
 BY AN AUTOMATIC SPRINKLER SYSTEM.
  
 3)- SPRAY BOOTHS SHALL BE CONSTRUCTED OF
 STEEL NOT LESS THAN 1.2 MM THICK,
 SECURELY & RIGIDLY SUPPORTED, OF
 CONCRETE OR MASONARY OR OTHER APPROVED
 NON COMBUSTIBLE MATERIAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-07-03 Cont ID  
Sent By dpalmer Date 2001-07-03 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2001-07-03 Time 16:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By dpalmer Date 2001-06-07 Time 12:31 Rev Time 0.00
Received By dpalmer Date 2001-06-07 Time 12:31 Sent To  
Notes
2001-06-07 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE PLACE LAYOUT ON PLANS
 PERTAINING TO ART:516 OF THE NEC.
 PLEASE SHOW AREAS OF REQ`D BY 516.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-07-02 Cont ID  
Sent By lsmith Date 2001-07-02 Time 11:36 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-06-26 Cont ID  
Sent By mcarsill Date 2001-06-26 Time 11:08 Rev Time 0.00
Received By mcarsill Date 2001-06-26 Time 11:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-06-06 Cont ID  
Sent By mcarsill Date 2001-06-06 Time 12:28 Rev Time 0.00
Received By mcarsill Date 2001-06-06 Time 12:28 Sent To  
Notes
2001-06-06 00:00:001) WARNING SIGNS TO BE PROVIDED "NO
 SMOKING OR OPEN FLAMES" PER NFPA 33.
 2) SPRAY BOOTH IS TO BE GROUNDED OR
 BONDED TO PREVENT STATIC ELECTRICITY.
 3) PLEASE PROVIDE PRODUCT APPROVALS FOR
 THE PRE-FAB, PRE-ENGINEERED SPRAY BOOTH.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-07-05 Cont ID  
Sent By pkrauss Date 2001-07-05 Time 07:45 Rev Time 0.25
Received By pkrauss Date 2001-07-05 Time 07:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-06-07 Cont ID  
Sent By pkrauss Date 2001-06-07 Time 08:01 Rev Time 0.30
Received By pkrauss Date 2001-06-07 Time 08:01 Sent To  
Notes
2001-06-07 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE CUT SHEETS/PRODUCT
 APPROVALS FOR PRE-FABRICATED SPRAY
 BOOTH.
  
 SHOW COMPLIANCE WITH 1997 SMC 501.2,
 PLEASE PROVIDE INFORMATION ON AIR
 MAKE-UP.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-07-02 Cont ID  
Sent By lsmith Date 2001-07-02 Time 11:37 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***